HW Test #2 Flashcards
Two or more ______ small appliance branch circuits shall be provided to supply power for receptacle outlets in the dwelling unit kitchen, dining room, breakfast room, pantry, or similar dining areas.
20 amp
(A. 210)
There shall be a minimum of one ____ branch circuit for laundry outlets required by 210.52
20 amp
(A. 210.52)
As per NYC NEC in addition to the number of branch circuits required in a dwelling unit an individual branch circuit shall be provided for each _______ receptacle
Air Conditioner
the maximum total voltage drop on branch-circuit conductors is _______ percent
3%
dwelling unit circuits running through another dwelling unit in common areas. what percentage of change will require it to be brought up to the current code
50%
outlets may be installed in a dwelling unit for specific appliance such as laundry equipment. what is the maximum distance allowed between this outlet and the appliance
6 feet
(A. 210.50)
receptacle outlets in floors shall not be counted as part of the required number of receptacle outlets unless located within ________ of the wall
18”
a receptacle connected to one of the dwelling unit small appliance branch circuits can be used to supply an ______ in any of the rooms specified in 210.52(B)(1)
Electric Clock
receptacle outlets installed for a specific appliance in a dwelling unit, such as a laundry equipment, shall be located within ______ of the intended location of the appliance
6 feet
How many receptacles are required within the perimeter of a balcony, deck or porch with a usable area of less than 20 Sq. feet
1
(Amend. 210.52 except 3)
the number of receptacle outlets for guest rooms in hotels and motels shall not be less than that required for a dwelling unit. these receptacles can be located to be convenient for permanent furniture layout but at least _____ receptacle outlets shall be readily accesible
two
(A. 210.60(b) )
at least one receptacle outlets shall be installed within ______ of the top of a show window for each 12 linear feet measured horizontally across its length
18inches
A. 210.62
a 125-volt, single phase, 15 or 20 ampere rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air conditioning, and refrigeration equipment. the receptacle shall be located on the same level and within ______ of the heating, air conditioning, and refrigeration equipment. the receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
25 feet
A. 210.63