article 215 (1pg 7q) Flashcards
the feeder conductor ampacity shall not be less than that of the service-enterance conductors where the feeder conductors carry the total load supplied by service conductors with an ampacity of _______or less
55 A
215.2(A)(2)
dwelling unit or mobile home feeder conductors need not be larger than the service conductors and can be sized according to 310.15(B)(6)
TRUE
215.2(A)(3)
when a feeder supplies ________ in which equipment grounding conductors are required, the feeder shall include or provide an equipment grounding conductor
branch circuits
215.6
on a 4-wire, delta-connected, three-phase system, where the midpoint of one phase winding is grounded, the conductor with the higher phase to voltage-to-gound must be durably and permanently marked by an outer finish _____ in color, or other effective means
orange
(on every test)
ground-fault protection of equipment shall be required for a feeder disconnect if ____
the disconnect is rated 1,000A, 480V
ground fault protection of equipment shall not be required at a feeder disconnect if ground-fault protection of equipment is provided on the _____ side of the feeder and on the load side of any transformer supplying the feeder
supply
215.10 (exception 2)
where a premises wiring system contains feeders supplied from more than one nominal voltage system, each ungrounded conductor of a feed shall be identified by phase and system by ________, or other approved means
any of these:
-color coding
-marking tape
-tagging