Article 230 (5pg 52q) Flashcards
a building or structure shall be supplied by a maximum of _____ service(s), unless specifically permitted otherwise
one
additional services shall be permitted for a single building or other structure sufficiently large to make two or more services necessary if permitted by _______
special permission
additional services shall be permitted for different voltages, frequencies, or phases, or for different uses such as for _______
different rate schedules
where a building or structure is supplied by more than one service, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services supplying that building or structure and the area serves by each
TRUE
service conductors supplying a building or other structure shall not ______ of another building or other structure
pass through the interior
conductors are considered outside a building when they are installed
-under not less than 2 in of concrete beneath a building or structure
-within a building or structure in a raceway encased in not less than a 2 in. thickness of concrete or brick
-installed in a vault that meets the construction requirements of Article 450
-conductors other than service conductors shall not be installed in the same
-service raceway
-service cable
where a service raceway enters a building or structure from a(n) ________, it shall be sealed in accordance with 300.5(G)
underground distribution system
service conductors installed as unjacketed multi-conductor cable shall have a minimum clearance of _____ from windows that are designed to be opened, doors, porches, stairs, fire escapes, or similar locations
3 feet
overhead service conductors to a building shall maintain a vertical clearance of final spans above, or within, _______ measured horizontally from the platforms, projections, or surfaces from which they might be reached.
3 feet
service conductors shall not be installed beneath openings through which materials may be moved and shall not be installed where they will obstruct entrance to these buildings’ openings
TRUE
overhead service conductors spans can be supported to hardwood trees
FALSE
service-drop conductors shall have ___________
-sufficient ampacity to carry the load
-adequate mechanical strength
the minimum size service-drop conductor permitted is _____ AWG copper or _______ AWG aluminum or copper-clad aluminum
8, 6
service drops installed over roofs shall have a vertical clearance of _____ above the roof surface, unless a lesser distance is permitted by an exception
8 feet