When sizing a circuit vent what is the developed length of the piping that should be used?

A

the horizontal soil or waste pipe to the VS, SV, VH, or outside air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

list the 3 situations that a trap need not be protected by a vent:

A

4) A trap need not be protected by a vent pipe
a) where it serves
i) a subsoil drainage pipe, or
ii) a storm drainage system, or
b) where it forms part of an indirect drainage system (see also

2.5.1.1. 4) a) b)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What table is used to size vent stacks?

A

2.5.8.4.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

List the requirements for venting an oil interceptor?

A

2 vents, opposite ends, extend independently, not less than 2 metres and differing by 300 mm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

State the minimum size of vent pipe required for a 4” wc:

A

1 1/2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

which table is used to size wet vents?

A

2.5.8.1.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When sizing a branch vent, what is the developed length?

A

from the most distant soil or waste pipe connection to a VS, SV, VH, our outside air.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

what is the maximum size of every vent for a sewage sump?

A

not less than 2”, but need not be greater than 4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

what is the maximum hydraulic load that may be connected to a circuit vent?

A

3 fus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

list the minimum size of vent pipping for a circuit vent (30 meters, 96 fus)

A

3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When is a vent stack required with fixtures draining into it:

A

more than 4 storeys.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

what size soil or waste stack, stack vent, and vent stack are required for an 8 storey building draining 250 fixture units? The length of the stack vent is 3 metres and the length of the vent is 25 metres.

A

WS/SS 4”, SV 2”, VS 3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What size of vent pipe would be required for a sewage sump with a 3” inlet?

A

2”

2.5.7.7. one size smaller then the largest branch or fixture drain

not smaller than 2” not larger than 4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

how far away from an openable window or door can a vent terminate:

A

not less then 1 m above or not less than 3.5 m any other direction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the minimum size of branch vent required when connecting two bathroom groups with a total vent length of 7 meteres?

A

1 1/2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

what is the developed length that is used to size a vent header?

A

from the most distant soil or waste pipe connection to outside air

17
Q

what is the minimum size of wet vent for a bathroom group with a kitchen sink, not symmetrically connected, to the wet vent?

A

3”

18
Q

a soil or waste stack with 1.5 m offset, with 120 fixture units draining into the upper 3 storeys will require an offset relief vent?

2.5.4.4.

T or F

A

False

19
Q

what is the minimum size stack vent required for a 3” wet vented soil or waste stack draining 43 fixture units from 6 storeys? the vent’s length is 12 m.

A

3”

20
Q

what are the requirements for offsets in a wet vent?

A

no more than 1, does not exceed 1.2m for 2”, does not exceed 2.5m for 3”

21
Q

list one requirement for connecting fixtures to a vent stack:

A

no more than 8 fus connect to the lowest or below lowest connection

22
Q

when are additional circuit vents required with circuit vented branches?

A

when there is more than a 45 deg horizontal change OR more than 8 traps between the circuit vent and relief vent

23
Q

how is a vent pipe protected from a frost closure?

A

making it a minimum of 3”, increasing it one size or insulating it.

24
Q

how do you size a yoke vent?

A

one size smaller than the smallest pipe to which it is connected.

25
Q

what is the largest size trap arm or fixture that can drain into a wet vent?

A

3” emergency floor drain

26
Q

what would be the maximum number of tank type WCs that could drain into a wet vent?

A

0

27
Q

What is the largest size trap arm or fixture drain that can drain into a wet vent?

A

3” emergency floor drain

28
Q

What is the maximum number of tank type WC’s that can drain into a wet vent.

A

0

29
Q

How do you size a wet vent?

A

Hydraulic load

30
Q

How do you size a circuit vent?

A

By its FUs and developed length

31
Q

How do you size a relief vent?

A

one size smaller then the circuit vent but not larger then 2”

2.5.7.3. 2)

32
Q

what is the maximum number of circuit vented branch traps that can be installed between a circuit vent and a relief vent?

A

8 traps

33
Q

“A circuit vented branch, including the fixture drain downstream of the circuit vent connection, shall be sized in accordance with article 2.4.10.7. , except that it shall be not less than b) _________ inches, where traps 2 inches in size or larger are circuit vented”

A

3”

urinals, toilets, showers

CVB = is 3” when 2” traps are circuit vented

34
Q

“Additional circuit vents shall be required b) where more than _____ circuit vented fixtures are connected to a branch between vent pipe connections”

A

8

35
Q

“A soil-or-waste pipe may serve as an additional circuit vent in accordance with sentence (6) provided that the soil-or-waste pipe is sized as a wet vent in conformance with article 2.5.8.1. and is not less than _______ inches in size”

A

2”

an additional circuit vent must be sized as a wet vent and is not smalle

36
Q

“A section of horizontal branch may be circuit-vented provided no soil-or-waste stack is connected to it _________ of a circuit vented fixture”

A

upstream