When sizing a circuit vent what is the developed length of the piping that should be used?
the horizontal soil or waste pipe to the VS, SV, VH, or outside air
list the 3 situations that a trap need not be protected by a vent:
4) A trap need not be protected by a vent pipe
a) where it serves
i) a subsoil drainage pipe, or
ii) a storm drainage system, or
b) where it forms part of an indirect drainage system (see also
2.5.1.1. 4) a) b)
What table is used to size vent stacks?
2.5.8.4.
List the requirements for venting an oil interceptor?
2 vents, opposite ends, extend independently, not less than 2 metres and differing by 300 mm.
State the minimum size of vent pipe required for a 4” wc:
1 1/2”
which table is used to size wet vents?
2.5.8.1.
When sizing a branch vent, what is the developed length?
from the most distant soil or waste pipe connection to a VS, SV, VH, our outside air.
what is the maximum size of every vent for a sewage sump?
not less than 2”, but need not be greater than 4”
what is the maximum hydraulic load that may be connected to a circuit vent?
3 fus
list the minimum size of vent pipping for a circuit vent (30 meters, 96 fus)
3”
When is a vent stack required with fixtures draining into it:
more than 4 storeys.
what size soil or waste stack, stack vent, and vent stack are required for an 8 storey building draining 250 fixture units? The length of the stack vent is 3 metres and the length of the vent is 25 metres.
WS/SS 4”, SV 2”, VS 3”
What size of vent pipe would be required for a sewage sump with a 3” inlet?
2”
2.5.7.7. one size smaller then the largest branch or fixture drain
not smaller than 2” not larger than 4”
how far away from an openable window or door can a vent terminate:
not less then 1 m above or not less than 3.5 m any other direction
What is the minimum size of branch vent required when connecting two bathroom groups with a total vent length of 7 meteres?
1 1/2”