Boilers and hydronics Flashcards
a pressuretrol operates due to
an increase in steam pressure AND a decrease in steam pressure
pressuretrols that operate the main burner are manual reset.
false
to set an additive operating pressurtrol that shuts the main burner ‘off’ at 130 psig and turns the main burner “on” at 120 psig, you the technician would set the adjustment screws as follows:
main scale setting 120 psig/ differential scale setting to 10 psig
the maximum setting for a high limit pressurtrol on a low pressure steam boiler would be:
15 psig
why do high input gas appliances with power burners require gas pressure switches?
because proper combustion would be affected if the manifold pressure varies too much
the maximum setting on a high-pressure gas switch is:
25% in excess of the manifold pressure stated on the rating plate
the minimum setting on a low pressure gas switch is:
50% less than the manifold pressure on the rating plate
A LWCO should be installed to maintain what level of water above the highest set of tube in a fire-tube boiler?
1 inch
referencing a float type LWCO what could happen if the blow down valve is opened too quickly?
the float could be damaged
how often does a relief valve on a steam boiler have to be recertified?
every year
the manual valve can be installed between the pressure vessel and the relief valve?
false
the aquastat utilises this control principal to operate:
hydraulic
the high limit aquastat utilised on a commercial hot water tank is known as:
ECO (energy cut off)
An aquastat used to control the main burner would be considered:
Normally closed
a flow switch on a hot water boiler system verifies operation of what device?
water flow through the boiler itself.
an “indoor/outdoor” control controls what
water temperature