EPG&D Flashcards
Purpose
The purpose of the EPG&D system is to produce stable NATO standard electrical power from the ship’s generators or shore power and distribute it to the ship’s systems and services requiring electrical power.
DG’s
Caterpillar C32 Diesel Generator
Powered by a 12 cylinder, four-stroke, turbo-charged diesel engine.
Generate NATO standard power for the ship’s switchboards.
Inside raft mounted acoustic enclosures.
1800 rpm.
830 kW
Started by HP air in dedicated flasks, one in FER and one in AER.
Cooled by a plate type heat exchanger which uses ASWC.
DGs can be controlled from MEC or DG LCP.
DG 1 & 2 located in FAMR
DG 3 and 4 located in AAMR
AVRs
Automatic Voltage Regulators
Each DG has 2 AVRs.
Automatic control of DC exciter voltage which regulates generator output voltage.
One is active, one on standby.
Will automatically change over to standby if primary fails.
Switchboards
2 switchboards distribute power from DGs or shore to various users.
5 ACB’s
55 MCCBs
Can be operated in Split operation (bus ties open) or Parallel (one or both bus ties closed.
Located in Fwd and Aft Switchboard Rooms
Switchboard Modes (List)
Automatic
Manual Permissive
Manual
Automatic (SWBD Mode)
DGs started and paralleled automatically.
Manual Permissive (SWBD Mode)
Parallelling done manually using the synchroscope.
Safeties protect the plant if paralleling is done incorrectly.
Manual (SWBD Mode)
Paralleling is done manually using the snychroscope.
No safeties are in place.
What is paralleling?
Synonym with “Synchronizing”
Adjusting the voltage, frequency, and phase of the DG to match with the other DGs.
EPCS
Electrical Power Control System
Responsible for monitoring and controlling the EPG&D system.
ESCs are in RTU 10 and 11 and communicate with eachother via IPMS LAN.
IF ESCs cannot communicate, they open bus ties and operate independantly.
CONSOLE CONTROL: Switchboard operated via IPMS.
SWITCHBOARD CONTROL: Switchboard controlled locally at the switchboard itself.
List ESC Functions
Load Sharing
Load Sheding
Preference Tripping
ACB Interlock
Blockout Sequence
Voltage Adjust
Automatic Synchronization
Load Sharing
Automatically adjusting the frequency of online DGs so that each DG shares an equal amount of load.
Load Shedding
When a sudden electrical load >110% rated load for the number of online generators, load shed breakers are tripped.
Preference Tripping
Same as load shedding but only when 1 DG is running and demand >150%.
Helps ensure we do not black out by allowing higher percentage before breakers trip.
ACB Interlock
Ensures only designed bus tie configurations occur.
1 DGs: 0,1,2
2 DGs: 0,1,2
3 DGs: 0,1
4 DGs: 0
Blackout Sequence
Ensures power to switchboards is quickly re-established if it is lost.
<22 volts sensed at bus bars of both switchboards:
All bus ties open
All DG ACBs open
All DGs start
First DG online will be loaded
All other DGs synch to that one