EPC 38 - Installation & Connection of Consumers Mains Flashcards
What is the minimum permissible current carrying capacity of the consumer’s mains in a single phase single domestic installation?
63A.
WAER Clause 9.2.1.
What is the minimum permissible current carrying capacity of the consumer’s mains in a three phase single domestic installation?
32A.
WAER Clause 9.2.1.
Which Clause in the WA Electrical Requirements specifies the general requirements for the installation of consumer’s mains and sub-mains?
WAER_ Section 5 — LV underground network.
What is the minimum permissible depth of underground residential consumer’s mains?
(Give the Wiring Rules Clause Number).
500mm.
Table 3.6
Where does the consumer’s mains begin in a domestic installation in which the consumer’s mains are installed underground?
At the supply authority termination pillar.
WAER Section 5.
Is it permissible to use heavy duty corrugated PVC conduit to enclose underground residential consumer’s mains?
(Give the Wiring Rules Clause Number).
Yes.
AS/NZS 3000 Clause 3.10.2.1 (a) (iv), Table 3.5.
If a supply authority’s 2 core parallel-webbed aerial SERVICE LINE has one ribbed conductor, should it be the active or the neutral?
(Give the Wiring Rules Clause Number).
The neutral.
AS/NZS 3000 Clause 3.8.3.3 (c).