EPC 38 - Installation & Connection of Consumers Mains Flashcards

1
Q

What is the minimum permissible current carrying capacity of the consumer’s mains in a single phase single domestic installation?

A

63A.

WAER Clause 9.2.1.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the minimum permissible current carrying capacity of the consumer’s mains in a three phase single domestic installation?

A

32A.

WAER Clause 9.2.1.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Which Clause in the WA Electrical Requirements specifies the general requirements for the installation of consumer’s mains and sub-mains?

A

WAER_ Section 5 — LV underground network.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the minimum permissible depth of underground residential consumer’s mains?
(Give the Wiring Rules Clause Number).

A

500mm.

Table 3.6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where does the consumer’s mains begin in a domestic installation in which the consumer’s mains are installed underground?

A

At the supply authority termination pillar.

WAER Section 5.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Is it permissible to use heavy duty corrugated PVC conduit to enclose underground residential consumer’s mains?
(Give the Wiring Rules Clause Number).

A

Yes.

AS/NZS 3000 Clause 3.10.2.1 (a) (iv), Table 3.5.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

If a supply authority’s 2 core parallel-webbed aerial SERVICE LINE has one ribbed conductor, should it be the active or the neutral?
(Give the Wiring Rules Clause Number).

A

The neutral.

AS/NZS 3000 Clause 3.8.3.3 (c).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly