EPC 25 - Installation in Damp Situations Flashcards
Which Table in AS/NZS 3000 summarises restrictions in Bathrooms?
Table 6.1.
Where may socket outlets be installed in a pool zone for the connection of equipment?
0.45m above ground and 1.25m from the rim; or beneath a barrier (0.5m from the edge).
AS/NZS 3000 Clause 6.3.4.3. (B - ii)
What is ONE method of supply for luminaries immersed in water in a swimming pool?
12V a.c. from a double wound transformer.
AS/NZS 3000 Clause 6.3.4.5.2
Under what circumstances does steel fencing around a pool need to be bonded to exposed
metal in the pool zone?
Within arm’s reach of the edge of the pool.
AS/NZS 3000 Clause 5.6.2.6.5.
Is it permissible to install socket outlets within zone 2 of a bathroom?
No - unless enclosed in a cupboard and protected by an RCD. AS/NZS 3000 Clause 6.2.4.2.
What is the minimum permissible distance from the internal rim of a 40 litre wash basin to a socket outlet on a vertical wall beside the basin in a bathroom?
0.15m (150mm).
AS/NZS 3000 Clause 6.2.2.2 ( B - i ) or Figure 6.13.
Select an appropriate IP rating for a light switch which is to be installed in a Zone 1 area near a swimming pool.
IP X5.
AS/NZS 3000 Clause 6.3.4.1. or Table 6.2.
Is it permissible to install a 230V/240V socket outlet inside a sauna room?
No.
AS/NZS 3000 Clause 6.5.4.4.