EPC 35 - Installation of Cables & Final Sub-circuits Flashcards
List FOUR factors which must be considered when selecting a wiring system for a particular installation? (Give the Wiring Rules Clause Number).
Protection against shock. Protection against external influences. Mutual detrimental influences. Cable selection. Reliability of terminations. Identification of conductors. Protection against fire.
AS/NZS 3000 Clause; 3.1.2
Describe EIGHT different types of wiring system and give a typical example of where each one could be used. (Give the Wiring Rules Clause Number).
TPS, PVC conduit, Steel conduit, Underground, Catenary, Aerial, Ducting, Cable tray, Busway, Armoured, MIMS.
AS/NZS 3000 Clause; Table 3.1
According to AS/NZS 3000, what is the maximum number of 10A socket outlets that may be installed on a 2.5mm final sub-circuit protected by a 16A circuit breaker in a domestic installation?
(Give the Wiring Rules Clause Number).
16 points. AS/NZS 3000 Table C9
Is it necessary to clip cables in a roof space if the roof is less than 0.6m above the ceiling?
(Give the Wiring Rules Clause Number).
No. AS/NZS 3000 Clause 3.9.3.3.1(c).
Is it permissible to clip TPS cables to a ceiling joist within 50mm of the ceiling?
(Give the Wiring Rules Clause Number).
No. AS/NZS 3000 Clause 3.9.4.3.2.
What is the largest diameter hole that is allowed in a wall for cables to pass through without fire rating protection? (Give the Wiring Rules Clause Number).
25mm. Clause 3.9.9.3 (ii).
May conductors that form part of a different electrical installation be installed within the same enclosure? (Give the Wiring Rules Clause Number).
No. Clause 3.9.8.2.1(a).
Underground wiring systems are classified as one of three types. Name them.
(Give the Wiring Rules Clause Number).
Cat A, Cat B, Cat C.
AS/NZS 3000 Clause 3.11.2.
What is the minimum depth of cover for a Cat B underground wiring system installed under 80mm of poured concrete, external to a building?
(Give the Wiring Rules Clause Number).
300mm.
AS/NZS 3000 Table 3.6.
How deep must Orange Marker tape be buried above an underground wiring system?
(Give the Wiring Rules Clause Number).
50% of the depth of cover.
AS/NZS 3000 Clause 3.11.4.5.