What is the major functional difference between a switch and a typical circuit breaker?
A circuit breaker is usually ON in the UP position; or a circuit breaker operates automatically.
What are the main colours used on a danger tag marked ‘DANGER, DO NOT OPERATE’?
Red and black.
What are the main colours used on a danger tag marked ‘OUT OF SERVICE’?
Yellow and Black.
What MAIN precaution must be taken before touching the terminals of any fixed 230V/400V device?
Test for zero volts.
What additional precaution must be taken before touching the terminals of a fixed 230V/400V device AFTER you have tested the terminals for 0V?
Test the testing device.
Who should remove a danger tag from an electrical isolator under normal working conditions?
The person who placed it there.
Re-arrange the following actions in the correct sequence for a typical correct isolation procedure:
Tag | Test | Isolate | Switch-off | Identify
- Identify.
- Switch off.
- Isolate.
- Tag.
- Test.