EOP-1 Turbine Script Flashcards
CRS: (NCOT First Name) Is the Main Turbine tripped?
No contingencies
All contingencies
- Yes, the Main Turbine is tripped.
Contingencies taken:
- Yes, the Main Turbine is tripped.
However, it required tripping from C-01
- Yes, the Main Turbine is tripped.
However, required trip from C-01 failed, MSIVs were closed.
CRS: Is the Main Generator disconnected from the grid?
No contingencies
All contingencies
No Contingencies
- Yes, the Main Generator is disconnected from the grid.
Contingencies
- Yes, the Main Generator is disconnected from the grid.
However, Generator Breakers at C-01 were openned.
- Yes, the Main Generator is disconnected from the grid.
However, Generator Breakers would not open at C-01, Relay 487U was jumpered.
CRS: Are both Main Feed Pump Speed Controls in Manual at minimum speed?
No Contingencies
- Yes, both Main Feed Pumps Speed Controls are in Manual at minimum speed.
Contingencies
- Yes, both Main Feed Pumps Speed Controls are in Manual at minimum speed.
However, A Main Feed Pump is tripped.
- Yes, both Main Feed Pumps Speed Controls are in Manual at minimum speed.
However, B Main Feed Pump is tripped
- Yes, both Main Feed Pumps Speed Controls are in Manual at minimum speed.
However, Both Main Feed Pumps are tripped
CRS: Are both Main Feed Reg and Feed Reg Bypass Valves closed?
No contingencies.
All contingencies.
No contingencies:
- Yes, both Main Feed Reg Valves and Feed Reg Bypass Valves are closed.
All contingencies:
- No, xx Main Feed Reg Valve did not close. Both Main Feed pumps are tripped and xx Feed Reg Block Valve is closed.
- No, xx Main Feed Reg Valve and xx Feed Reg Block valve did not close. Both Main Feed pumps and both Condensate pumps are tripped.
- No, xx Bypass Feed Reg Valve did not close. Both Main Feed pumps and both Condensate pumps are tripped.
CRS: Are Buses 1C and 1D energized?
No contingencies.
All contingencies.
Yes, both Charlie and Delta bus are energized.
Yes, both Charlie and Delta bus are energized, however I had to start xx DG and close the output breaker.
No Charlie bus is energized, Delta bus is not.
CRS: Is Bus 1E energized.
Yes, Bus 1E is enegized.
No, Bus 1E is not energized due to SIAS.
CRS: Are Buses 1A and 1B energized?
Yes, Bus 1A and 1B are energized.
No, Bus 1A is Not energized. Bus 1B is energized.
No, Bus 1A is energized. Bus 1B is Not energized.
CRS: Is Y-01 energized?
Yes, Y-01 is energized.
No, Y-01 is Not energized.
CRS: Are the six DC buses energized?
Yes, All six DC buses are energized.
No, ____ buses are energized, ____ is/are not energized.
CRS: Are at least 3 out of 4 perferred AC buses energized?
Yes, all four preferred AC buses are energized.
Yes, three preferred AC buses are energized. Y-xx is Not
No, ____ is/are energized, ___ is/are not energized.
CRS: (NCOT First Name) Do we have at least 1 Steam Generator with level between 5 and 70% with feedwater available?
No contingencies
All contingencies
Yes, A S/G level is at xx% and rising/lowering/stable, B S/G level is at xx% and rising/lowering/stable, being feed by P-8A/B/C Aux Feedwater Pump at xxx gpm to each S/G.
No, A S/G level is at xx% and rising/lowering/stable, B S/G level is at xx% and rising/lowering/stable, being feed by P-8A/B/C Aux Feedwater Pump at xxx gpm to each S/G.
CRS: Are the Steam Generators intact?
Yes, both Steam Generators are intact.
No, I have indications of an ESDE or SGTR on A/B Steam Generator.
ESDE: Diverging pressure on MSIV closure
SGTR: Rising S/G level greater than feed.
CRS: Is Tave between 525F and 540F?
Yes, Tave is xx F and rising/lowering/stable being controlled by TBV or ADVs.
Yes, Tave is xx F and rising/lowering/stable being controlled by ADVs, However the TBV controller failed open and was taken to manual and closed.
No, Tave is xx F and rising/lowering/stable being controlled by TBV or ADVs.
CRS: Are both Steam Generator pressures between 800 psia and 970 psia?
Yes, both steam generator pressures are at xx pounds and rising/lowering/stable.
CRS: (NCOT First Name): Are the Containment Area Monitor alarms clear and not rising?
Yes, the Containment Area Monitor alarms are clear and not rising.
No, Containment Area Monitor alarms are rising. I have actions at 10R.
No, Containment Area Monitor alarms are in and CIS has been initiated, Readings are / are Not corroborated by Containment High Range Monitors RIA-2321/2322.