Code, Standards, and Practices 1, Based on the 2020 NEC Online Materials: Lesson 11 Specific Switch Installation Requirements Flashcards
Which UL Standard is required to be used by qualified electrical testing laboratories to evaluate snap switches for electrical safety?
Select one:
a.
UL 20
b.
UL 467
c.
UL 498
d.
UL 891
UL 20
A motor circuit switch is generally required to be rated in ? .
Select one:
a.
amperes
b.
horsepower
c.
locked rotor amperes
d.
voltage and short-circuit current
horsepower
A general-use dimmer switch is generally only permitted to control ? .
Select one:
a.
ceiling-suspended paddle fans
b.
fluorescent luminaires
c.
incandescent luminaires
d.
standard duplex or single receptacles
incandescent luminaires
Where the white or gray conductor of a cable assembly is used as a switch loop for circuits of 50 volts or more, the switch loop must be permanently reidentified as an ungrounded conductor by ? .
Select one:
a.
an effective means of any color
b.
marking tape, painting, or other effective means of a color other than white, gray, or green
c.
the use of gray or white paint
d.
the use of gray or white tape
marking tape, painting, or other effective means of a color other than white, gray, or green
The white or gray conductor of a cable assembly, where used in switch loop wiring, is not permitted to be used as a ? .
Select one:
a.
return conductor from a switch to a switched outlet
b.
supply side of single pole switch
c.
supply side (point wire) of a 3-way switch
d.
none of the above
return conductor from a switch to a switched outlet
A general-use snap switch used to supply a one-horsepower motor shall be permitted to control a load of not greater than ? .
Select one:
a.
50% of the rating of the switch
b.
80% of the ampere rating of the switch
c.
100% of the rating of the switch
d.
125% of the switch
80% of the ampere rating of the switch
Where switches or other devices are ganged in a four-gang box, and the voltage between adjacent switches exceeds 300 volts, which of the following is required?
Select one:
a.
Each switch requires its own device box.
b.
Electrical tape is required around the device terminals.
c.
Permanently installed barriers are required between adjacent devices.
d.
Switches without screw terminals are required to be used.
Permanently installed barriers are required between adjacent devices.
Switches are required to be marked in accordance with which of the following?
Select one:
a.
Hospital grade when used at patient bed locations in a critical-care area
b.
Ivory in color
c.
To indicate the load they serve
d.
Voltage and current ratings
Voltage and current ratings
Generally, multipole switches are permitted for use only on ? circuits unless listed and marked for other than single circuit use.
Select one:
a.
277 V
b.
480 V
c.
multiple circuits where clearly identified in the field
d.
single
single
? are generally required to be grounded.
Select one:
a.
Dimmer switches
b.
Fan controls and other similar switch controls
c.
Snap switches
d.
All of the above
All of the above
Switch faceplates made of nonmetallic (insulating), noncombustible material must generally not be less than ? in thickness.
a.
0.76 mm (0.030”)
b.
1.02 mm (0.040”)
c.
2.54 mm (0.100”)
2.54 mm (0.100”)
Where a snap switch is marked “CO/ALR,” it is suitable for use with which of the following types of conductors?
Select one:
a.
Aluminum conductors
b.
Copper conductor
c.
Copper-clad aluminum conductors
d.
All of the above
All of the above
Snap switches with “push-in” terminal connection means are permitted for use with ? conductors.
Select one:
a.
aluminum
b.
solid copper
c.
stranded aluminum
d.
stranded copper
solid copper
Switches marked with an off position are required to ? .
Select one:
a.
be capable of being locked in the open position
b.
completely disconnect all ungrounded conductors to the load they control
c.
partially disconnect the load they control
d.
none of the above
completely disconnect all ungrounded conductors to the load they control
A general-use dimmer switch is required to be counted as ? where installed in a single-gang box on a circuit wired with 12 AWG copper conductors.
a.
1 conductor (2.25 in.3 total)
b.
2 conductors (4.00 in.3 total)
c.
2 conductors (4.50 in.3 total)
d.
3 conductors (2.25 in.3 total)
2 conductors (4.50 in.3 total)