Code, Standards, and Practices 1, Based on the 2020 NEC Online Materials: Lesson 10 Specific Receptacle Installation Requirements Flashcards

1
Q

What is the minimum rating required for a receptacle?
Select one:

a. 10 A

b. 15 A

c. 20 A

d. 30 A

A

15 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A single receptacle connected to a 30-ampere branch circuit must generally have a rating not less than ? .
Select one:

a. 15 A

b. 20 A

c. 30 A

d. none of the above

A

30 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If 15- and 20-ampere duplex receptacles are not marked with “CO/ALR,” they are suitable for use with ? .

Select one:

a. aluminum conductors only

b. aluminum or copper conductors

c. copper conductors only

d. copper and copper-clad aluminum conductors only

e. copper-clad aluminum conductors only

A

copper and copper-clad aluminum conductors only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Duplex receptacles are required to be installed so that the equipment grounding contact is orientated in which of the following positions?
Select one:

a. Grounding contact in the down position
`
b. Grounding contact in the horizontal position

c. Grounding contact in the up position

d. No grounding contact orientation requirements in the NEC

A

No grounding contact orientation requirements in the NEC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Receptacles mounted in boxes that are flush with the finished surface or project from the finished surface must be installed so that the mounting yoke or strap of the receptacle is held rigidly against the ? .
Select one:

a. box or box cover

b.extension ring

c.finished surface

d.support means for the box

A

box or box cover

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A ground-fault circuit-interrupter receptacle is a Class A device intended to interrupt the circuit when the current to ground is ? or higher.
Select one:

a. 6 mA

b. 20 mA

c. 15 A

d. 20 A

A

6 mA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Isolated ground receptacles are required to be identified by ? .
Select one:

a.a green dot on the face of the receptacle

b.a triangle symbol on the face of the receptacle

c.an orange triangle on the face of the receptacle

d.the receptacle must be totally orange in color

A

an orange triangle on the face of the receptacle

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Isolated ground receptacles are only permitted to be used ? .
Select one:

a.in data processing (information technology) equipment rooms

b.for sensitive electronic equipment branch circuits

c.where the grounding terminal of the receptacle(s) are connected to ground rods only

d.with equipment grounding conductors of branch circuits that are isolated and installed to meet the provisions of NEC 250.146(D)

A

with equipment grounding conductors of branch circuits that are isolated and installed to meet the provisions of NEC 250.146(D)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

In general, the equipment grounding conductor terminal on a receptacle or switch is required to be identified in accordance with which of the following?
Select one:

a.A green-colored hexagonal terminal nut that cannot be easily removed
Incorrect

b.A green-colored pressure wire connector
Incorrect

c.A green-colored terminal screw provided with a hexagonal head that cannot be easily removed
Incorrect

d.Any of the above

A

Any of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

In general, the equipment grounding conductor terminal on a receptacle or switch is required to be identified in accordance with which of the following?
Select one:

a.A green-colored hexagonal terminal nut that cannot be easily removed

b.A green-colored pressure wire connector

c.A green-colored terminal screw provided with a hexagonal head that cannot be easily removed

d.Any of the above

A

Any of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where a grounding means does not exist in a receptacle outlet box, a nongrounding-type receptacle is permitted to be replaced with a ? .
Select one:

a. grounding-type receptacle not supplied through a GFCI

b.grounding-type receptacle only

c.nongrounding-type receptacle

d.surge-protective device (SPD) receptacle

A

nongrounding-type receptacle

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which of the following locations require hospital grade receptacles to be installed?
Select one:

a. A patient bed location in a critical-care area

b.A patient bed location in a general patient care area

c.An examining room in a doctor’s office

d.Both a. and b.

A

Both a. and b.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

All 15- and 20-ampere receptacles installed in a wet location are required to be provided with which type of cover?
Select one:

a.A cover that is weatherproof when no attachment plug is inserted

b.A damp location cover

c.A listed outlet hood identified as “extra-duty” with an enclosure that is weatherproof, whether or not an attachment plug is inserted

d.A standard weatherproof cover that is not weatherproof when an attachment plug is inserted

A

A listed outlet hood identified as “extra-duty” with an enclosure that is weatherproof, whether or not an attachment plug is inserted

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the maximum cord- and plug-connected load permitted on 20-ampere duplex receptacles connected to a 20-ampere branch circuit where more than two receptacles connect to this branch circuit?
Select one:

a.12 A

b.15 A

c.16 A

d.20 A

A

16 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The ampere rating of a range receptacle shall be permitted to be based on a single-range demand load as specified in NEC Table 220.55.
a. True
b. False

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the minimum size aluminum equipment grounding conductor for an individual branch circuit supplying a twist-lock receptacle rated at 20 amperes?
Select one:

a. 14 AWG

b. 12 AWG

c. 10 AWG

d. 8 AWG

A

10 AWG

17
Q

All 15- and 20-ampere receptacles installed in wet or damp locations are required to meet which of the following?
Select one:

a. They shall be listed weather-resistant type.

b. They shall be locking type.

c. They shall be water tight.

d. They shall be waterproof.

A

They shall be listed weather-resistant type.

18
Q

Receptacles listed as tamper-resistant are not required in ? .
Select one:

a. dwelling unit bedrooms
Incorrect

b. dwelling unit kitchens
Incorrect

c. patient care areas of pediatric wards
Incorrect

d. restaurant dining rooms

A

restaurant dining rooms

19
Q

Which of the following receptacles are generally required to be listed as weather-resistant?
Select one:

a.15A, 125V locking receptacles indoors

b.20A, 125V non-locking receptacles outdoors

c.20A, 250V locking receptacles outdoors

d.30A, 250V non-locking receptacles outdoors

A

20A, 125V non-locking receptacles outdoors

20
Q

Which UL Standard is used to evaluate and list receptacles?
Select one:

a.UL 20

b.UL 489

c.UL 498

d.UL 891

A

UL 498

21
Q

When attaching receptacles or covers to outlet boxes, what type of screw is acceptable per NEC 314.25?
Select one:

a.Drywall screws

b.In accordance with the manufacturer’s instructions

c.Machine screws matching the thread gauge or size integral to the box

d.Whatever is on hand

e.Both b. and c.

A

Both b. and c.