interior finishes
interior linings

A

plaster
gypsum wallboard
wood panelling
ceiling tiles
plastic
fiberboard
wall covering including vegetation draperies and decorations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

interior finishes are considered trim

A

they do not exceed ten percent of the wall or ceiling
distributed throughout the space
do not constitute a large continuous surface

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

surface burning characteristics

A

composition, orientation and thickness of material
ventilation
shape and size of compartment
finish material

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

thin surface treatments

A

buildings codes usually exclude reference to surface treatments such as paint and wallpaper that are no thicker than 1/28 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

types of fire retardant coatings for interior finishes

A

intumescent coatings
mastics
gas firing paints
cementation and mineral fiber coatings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

intumescent paint

A

expands upon exposure to heat and creates a thick puffy coating that insulates the wood surface from heat and excludes oxygen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

mastic coating

A

form a thick noncombustible coating over the surface of wood

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

ASTME 84

A

uses the Steiner tunnel test
standard test to measure the surface burning characteristics of interior finish materials

ASTME 84 UL 723 test for surface burning characteristics of building materials
the Steiner tunnel test
the tunnel test

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

flame spread rating

A

established by ASTME 84 compares the surface flammability

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

smoke developed ratings

A

red oak is standard at 100
max score of 450
does not detect or measure CO or heat irritation or toxicity or volitility
onlu visual obscuration

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

NFPA 286

A

standard methods of fire tests for evaluating contribution of wall and ceiling interior finish to room fire growth

tests things that may not stay in place like things that will drip

tested on ceiling and walls

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

NFPA 265

A

STandard methods for fire test for evaluating room fire growth contribution of textile or expanded vinyl wall coverings on full height panels and walls

tested on walls
carpet walls

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

any kind of rated assembly used as a fire wall must match the listed parameters of the assembly in order to be compliant

A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

parapet walls

A

prevent fire spread on roofs. could be between 18-36 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

fire walls

A

four hour fire walls must be constructed of masonry or concrete
walls can be 2,3,4 hours
in structures as close as 18 inches apart rated construction may take the place of the clearance space to prevent fire spread

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

fire partitions

A

do not extend full length
interior
encoring an exit corridor need 1 hour rating

17
Q

enclosure walls

A

prevents fire spread vertically through stairwells, stairwell exit passage ways
elevators and pipe chases
need 1-2 hour rating
less thean 4 stories stairs need 1 hour

18
Q

curtain walls

A

came with steel frame construction. separates interior from exterior
resist environmental loads
control heat loss
limit noise transmission
limit solar radiation

often non load bearing
some have no fire resistance such as those made of aluminum and glass

19
Q

fire doors

A

rated in increments of 20 minutes to 4 hours
1/2and 1/3 hour doors are rated for smoke barriers and into corridors
rated in hours and letters:
Class A- openings in fire walls
Class B- Openings in vertical shafts and openings in 2 hour rated partitions
Class C- Openings between rooms and corridors having a fire resistive rating of 1 hour or less
Class D- Openings in exterior walls subject to severe fire exposure from outside of the building
Class E- openings in exterior walls subject to moderate or light exposure from the outside

20
Q

fire doors

A

codes require 3-4 hour rating in doors in a wall with a 2 hour rating
doors rated 1.5 hours required for 2 hour vertical enclosures
1 hour doors for 1 hour vertical shafts and exit enclosures

21
Q

rolling overhead doors

A

along corridors to protect convenience openings
protect an opening in a fire wall in industrial occupancy
one or both sides of a wall opening
opening in a wall that separates buildings

made of interlocking steel slats, releasing device, speed governor, counterbalance mechanism, wall guides

closes when fusible link melts or smoke detector releases hold open device

22
Q

horizontal sliding doors

A

used in older industrial buildings

23
Q

swinging fire doors

A

protect stairwells
ratings from 20 minutes to 3 hours

24
Q

special fire doors

A

horizontally sliding accordion doors or folding doors
motor driven and require electricity

25
Q

glazed doors

A

ratings up to 3 hours can have glazing, NFPA 80 requires that it is visible after installation