201.39 ESF Diesels Flashcards
- 201.39 ESF Diesels*
- *
Function of ESF Diesels
Provides source of power to Class 1E busses following a Loss of Off-Site Power
Provides essential safety function by supplying ESF loads during DBA when normal power is unavailable
- 201.39 ESF Diesels*
- *
Location of ESF DG controls, panels, components
D/G building
Remote D/G controls on CP-003
HVAC controls on CP-022
- 201.39 ESF Diesels*
- *
ESF DG Design Basis
Capable of supplying sufficient power to perform Safe Reactor Shutdown from full power operation during normal Ops also, during and after a DBA.
Start and commence loading within 10 seconds on a LOOP
Seismic Category – Class 1
Normally inactive except during testing or emergency use.
Cooper-Bessemer
600 RPM
5500 KW
20 cylinder
- 201.39 ESF Diesels*
- *
ESF DG Engine Driven Auxiliaries
- 201.39 ESF Diesels*
- *
ESF DG Auxiliary Skid Equipment
Lube Oil Cooler
STBY Lube Oil Pump
Lube Oil Recirc Pump / Heater
Main Lube Oil Strainer
Jacket Water Standpipe
Jacket Water Cooler
STBY Jacket Water Pump
Jacket Water Circ Pump / Heater
- 201.39 ESF Diesels*
- *
ESF DG Major External Equipment
Starting Air Compressors / Dryers
Starting Air Receivers
Intake Filter
Intake Silencer
Combustion Air Intake and Exhaust Piping
Exhaust Silencer
STBY D/G Fuel Oil Storage Tank
Fuel Oil Drain Tank
Fuel Oil Transfer Pump
STBY Fuel Oil Booster Pump
Engine Control panel
Generator Control panel
High Voltage Control panel
Grounding Reactor
Remote Control Panel (on CP-003)
Diesel Generator Building HVAC fans
- 201.39 ESF Diesels*
- *
ESF D/G Fire Protection
Sprinkler Heads for Engine Compartment
Foam / Water Deluge for DGFOST
Automatic actuation on heat or smoke
Manual Actuation available from deluge valve enclosure (north of DGB in yard) or outside DGFOST room
Fire Protection Actuation will not preclude engine operation
- 201.39 ESF Diesels*
- *
Effect of Fire in one ESF DG on other DGs
No effect
Complete Train Seperation
- 201.39 ESF Diesels*
- *
Location of ESF DG Fire Protection Foam Tank
55’ South side of DG room, normally accessed from ladder
- 201.39 ESF Diesels*
- *
What will happen if ESF DG paralled with grid in isochronous mode?
Will not have any speed droop characteristics.
Will try to maintain constant speed regardless of the load on the generator.
Will become overloaded and cause damage and/or trip.
OR
It will shed all load and trip the output breaker on reverse power.
- 201.39 ESF Diesels*
- *
ESF DG Electrical Ratings
5500 KW for 8760 hours run time ( 365 days)
5935 KW (108%) for 2000 hours run time (83 days)
6050 KW (110%) for 168 hours run time (7 days)
60 hz, synchronous 3 phase AC generator, at 0.8pf
Generator voltage limits are 3744 volts to 4576 volts. Nominal Generator voltage in automatic is 4160 volts.
Continuous rating of 6875 KVA at .8pf lagging
- 201.39 ESF Diesels*
- *
ESF DG Exciter Ratings
96.7 - 181.2 Volts
40 KW
320 amps
- 201.39 ESF Diesels*
- *
ESF DG STBY Fuel Oil Pump Auto Actions
With HS in Auto:
Auto Starts if engine speed < 540 RPM
OR
Fuel Pressure < 25 psig at filter inlet
STOPs when conditions met
- 201.39 ESF Diesels*
- *
ESF DG Filter / Strainer / Supply Alarms
Filter D/P alarm at 10 psid
Strainer D/P alarm at 5 psid
Supply Header alarm at 10 psig
(all D/G Trouble on CP-003)
- 201.39 ESF Diesels*
- *
Jacket Water 3-Way Thermostat
Modulates to maintain jacket water approx. 170 F.
< 165 all flow bypasses cooler
> 175 all flow through cooler