  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

Function of Non-Class 1E Vital 120 VAC

A

Provide reliable power for Non-Safety Related Vital instrumentation and control loads necessary for normal power generation and shutdown

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

Function of 20 KVA 120 V UPS

A

Located in 31’ TGB battery charging room

  • feeds uninterruptable power to DP048A (55’ TGB)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

DP048A location and loads

A

55’ TGB outside East Stairwell

  • Steam Generator Feed Pump indications and vibration monitoring
  • EHC Control Cabinet (one of two power supplies)
  • N-16 Instrument Cabinet ZLC-950
  • RT- 8092 and 8093 29 TGB
  • ARM Instrument Air Controller ZLP-134
  • other items (POP4-VC-0001 Addendum 17)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

Function of 25 KVA 120 V UPS

A

Located in EAB 10’ main corridor

  • Provides single phase 120 VAC uninterruptable power to DP-005 & DP-006 (EAB 10’)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

DP 005 and DP 006 locations and loads

A

EAB 10’

  • Main Turbine controls
  • Main Feedwater control valves
  • CVCS controls
  • Steam Dumps
  • others (0POP04-VC-0001 addendum’s 12, 13, 14,15, and 16 )
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

Function of 45 KVA 120 VAC UPS

A

Located in EAB 60’ MG set room

  • feeds DP003 and DP004
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

DP003/DP004 locations and loads

A

EAB 60’ MG Det Room

  • DRPI
  • Multiple Control Room recorders
  • RHR valves
  • One source of auctioneered Rod control power Others (0POP04-VC-001 Addendums 10,11, and 14)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

Probable causes of DP048A Inverter/Rectifier Trouble Alarm / Annunciator Location

A

Annunciated on CP003, 3M02 B-7

  • Loss of 480 VAC power to rectifier
  • Rectifier trouble
  • Loss of all incoming power to inverter
  • Inverter trouble
  • Instrument failure
  • System ground
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

Actions for DP048A Inverter/Rectifier Trouble Alarm

A
  • May auto transfer to alternate power source
  • Dispatch operator to check local alarm lights
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

Probable causes and automatic actions of an “120 VAC INVRTR N1VCIV005 OR N1VCIV006 TRBL” alarm.

A

Loss of power to inverter

Inverter failure

Instrument failure

May auto transfer to alternate power source

Dispatch operator to check local alarm lights

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

DP048A (20KVA) Power Supplies

A
  • Normal - 1F2
  • B/U DC - 125 VDC 1A battery bus
  • B/U VRT - 1G1 Switchback delay 30 secs
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

DP005, DP006 (25KVA) Power Supplies

A
  • Normal - 125 VDC 1B battery bus
  • B/U DC - none
  • B/U VRT - 1J1 (DP005), 1J2 (DP006) Switchback delay 5 minutes
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
  • 201.34 Non-Class 1E Vital 120 VAC*
    • *

DP003, DP004 (45KVA) Power Supplies

A
  • Normal - 1L1 (DP003), 1L2 (DP004)
  • B/U DC - none
  • B/U VRT - 1G8, 1G8 Switchback delay 30 secs
How well did you know this?
1
Not at all
2