201.34 Non-Class 1E Vital 120 VAC Flashcards
- 201.34 Non-Class 1E Vital 120 VAC*
- *
Function of Non-Class 1E Vital 120 VAC
Provide reliable power for Non-Safety Related Vital instrumentation and control loads necessary for normal power generation and shutdown
- 201.34 Non-Class 1E Vital 120 VAC*
- *
Function of 20 KVA 120 V UPS
Located in 31’ TGB battery charging room
- feeds uninterruptable power to DP048A (55’ TGB)
- 201.34 Non-Class 1E Vital 120 VAC*
- *
DP048A location and loads
55’ TGB outside East Stairwell
- Steam Generator Feed Pump indications and vibration monitoring
- EHC Control Cabinet (one of two power supplies)
- N-16 Instrument Cabinet ZLC-950
- RT- 8092 and 8093 29 TGB
- ARM Instrument Air Controller ZLP-134
- other items (POP4-VC-0001 Addendum 17)
- 201.34 Non-Class 1E Vital 120 VAC*
- *
Function of 25 KVA 120 V UPS
Located in EAB 10’ main corridor
- Provides single phase 120 VAC uninterruptable power to DP-005 & DP-006 (EAB 10’)
- 201.34 Non-Class 1E Vital 120 VAC*
- *
DP 005 and DP 006 locations and loads
EAB 10’
- Main Turbine controls
- Main Feedwater control valves
- CVCS controls
- Steam Dumps
- others (0POP04-VC-0001 addendum’s 12, 13, 14,15, and 16 )
- 201.34 Non-Class 1E Vital 120 VAC*
- *
Function of 45 KVA 120 VAC UPS
Located in EAB 60’ MG set room
- feeds DP003 and DP004
- 201.34 Non-Class 1E Vital 120 VAC*
- *
DP003/DP004 locations and loads
EAB 60’ MG Det Room
- DRPI
- Multiple Control Room recorders
- RHR valves
- One source of auctioneered Rod control power Others (0POP04-VC-001 Addendums 10,11, and 14)
- 201.34 Non-Class 1E Vital 120 VAC*
- *
Probable causes of DP048A Inverter/Rectifier Trouble Alarm / Annunciator Location
Annunciated on CP003, 3M02 B-7
- Loss of 480 VAC power to rectifier
- Rectifier trouble
- Loss of all incoming power to inverter
- Inverter trouble
- Instrument failure
- System ground
- 201.34 Non-Class 1E Vital 120 VAC*
- *
Actions for DP048A Inverter/Rectifier Trouble Alarm
- May auto transfer to alternate power source
- Dispatch operator to check local alarm lights
- 201.34 Non-Class 1E Vital 120 VAC*
- *
Probable causes and automatic actions of an “120 VAC INVRTR N1VCIV005 OR N1VCIV006 TRBL” alarm.
Loss of power to inverter
Inverter failure
Instrument failure
May auto transfer to alternate power source
Dispatch operator to check local alarm lights
- 201.34 Non-Class 1E Vital 120 VAC*
- *
DP048A (20KVA) Power Supplies
- Normal - 1F2
- B/U DC - 125 VDC 1A battery bus
- B/U VRT - 1G1 Switchback delay 30 secs
- 201.34 Non-Class 1E Vital 120 VAC*
- *
DP005, DP006 (25KVA) Power Supplies
- Normal - 125 VDC 1B battery bus
- B/U DC - none
- B/U VRT - 1J1 (DP005), 1J2 (DP006) Switchback delay 5 minutes
- 201.34 Non-Class 1E Vital 120 VAC*
- *
DP003, DP004 (45KVA) Power Supplies
- Normal - 1L1 (DP003), 1L2 (DP004)
- B/U DC - none
- B/U VRT - 1G8, 1G8 Switchback delay 30 secs