201.30 Off-site Electrical Flashcards
- LOT 201.30 Off-site Electrical*
- *
DESCRIBE the theoretical operation of transformers.
Expanding, collapsing, and reversing field caused by AC current flow through primary windings induces EMF in the secondary windings.
- LOT 201.30 Off-site Electrical*
- *
Characteristics of Wye connected transformer.
Phase voltage is less than line voltage by a factor of √3 (1.73) and phase current equals line current.
E1 = √3 E ɸ
I1 = I ɸ
- LOT 201.30 Off-site Electrical*
- *
Characteristics of Delta connected transformers.
the line voltage equals the phase voltage and phase current is less than line current by a factor of √3 (1.73).
- LOT 201.30 Off-site Electrical*
- *
Where/why are potential transformers used?
on high voltage AC sources for indication and protection
(UV and OV relays)
- LOT 201.30 Off-site Electrical*
- *
Where/why are current transformers used?
measure current flow on high voltage circuits for indication and protection
- LOT 201.30 Off-site Electrical*
- *
Function of Off-site Electrical Distribution System
provides reliable distribution of power generated from both units and a reliable source for plant auxilary power systems
- LOT 201.30 Off-site Electrical*
- *
Mitsubishi Pneumatic Controlled Breakers (PCB)
(Function/Voltage)
Allow control of power distribution and protect grid stability by isolating transmission line faults. “Breaker and a half” scheme allows isloation of any line maintaining distribution from others
345 KV
- LOT 201.30 Off-site Electrical*
- *
Disconnects
Manual isolation of components to ensure safety of workers. NOT designed to break load.
- LOT 201.30 Off-site Electrical*
- *
Main Transformer
Step up generator output to yard voltage when generator is online, or step down yard voltage to supply UAT when generator is off-line.
345/25 KV
- LOT 201.30 Off-site Electrical*
- *
Standby Transformer
Supply the standby buses
345/13.8 KV
2 secondary windings
- LOT 201.30 Off-site Electrical*
- *
Unit Auxiliary Transformer
(UAT)
Supply the Aux Buses and designated Standby Buses (F, H)through cross tie with respective Aux Bus
25/13.8 KV
- LOT 201.30 Off-site Electrical*
- *
Emergency Transformer
Provides backup power to one ESF bus in each unit at a time only, via emergency outdoor bus 1(2)K and MODs
138/13.8 KV
- LOT 201.30 Off-site Electrical*
- *
Draw and Label Off-Site Electrical Distribution System
- LOT 201.30 Off-site Electrical*
- *
Who is responsible to coordinate switching orders involving offsite elctrical distribution?
Unit 1 Control Room
- LOT 201.30 Off-site Electrical*
- *
Who can accept and execute switching orders?
Designated Qualified Personnel
- LOT 201.30 Off-site Electrical*
- *
Which lines cannot be used to satisfy Tech Spec requirements for Off-Site Power?
Hillje 44, 64
Blessing 44, 138 KV