2008 NRC RO Exam Flashcards
- Following a plant transient, the following conditions exist:
- Drywell Pressure is 2.5 psig, rising.
- RPV Water Level is 90 inches, lowering at 1 inch per minute.
- Reactor Pressure is 500 psig, lowering at 5 psig per minute.
- THEN annunciator 601447, RHR A INJ VLV 24A OPEN PERMISSIVE alarms.
Which one of the following is the indicated flow on the 2RHS*F114A Division 1 RHS Loop Total Flow Indicator five minutes after annunciator 601447 is received?
A. 0gpm
B. 1,000gpm
C. 3,500gpm
D. 7,000gpm
Correct Answer: A. When 601447 alarms, Reactor Pressure is 130 psid above RHR Pressure, which was already operating at minimum flow due to High Drywell Pressure. 5 minutes later, Reactor Pressure is 105 psid above RHR Pressure, resulting in Shutoff Head conditions. Minimum Flow Valve, 4A taps off BEFORE the Flow Element, which results in 0 gpm indicated flow.
Plausible Distractors:
B is plausible; would be true if Minimum Flow path produced flow indication.
C is plausible; would be true if Reactor Pressure were -250 psig.
D is plausible; would be true if Reactor Pressure were -150 psig.
- The following conditions exist:
- The reactor is in Mode 3.
- RHR Loop “A” is in Shutdown Cooling.,
- RHR Loop “B” is in Suppression Pool Cooling.
- DIVISION I RHR/LPCS REAC WTR LVL LOW alarms.
- DIVISION II RHR REAC WTR LVL LOW alarms.
Which one of the following describes the automatic RHR system response?
A. RHR Loop A continues to operate to shutdown cooling and RHR B pumps trips.
B. RHR A and B pumps trip, RHR Loop B realigns to the injection mode and the RHR B pump restarts.
C. RHR pump A trips and RHR Loop B realigns to the injection mode and the RHR B pump continues to run.
D. RHR Loop A continues to operate in shutdown cooling and RHR Loop B.
Correct Answer: C An RPV Level signal will cause a Group 5 isolation. (This is satisfied by RPV level 1). Since the RHS-A loop is in Shutdown cooling, the isolation signal will cause closure of MOV112, which will result in a pump trip. RHS-B will realign and inject per design
Plausible Distractors:
A is plausible; would be true for RHR B Pump overload condition.
B is plausible; identifies potential misconception on Suppression Pool Cooling / LPCl automatic reaIignment .
D is plausible; identifies potential misconception on Shutdown Cooling Isolation.
- RHS B Loop is operating in Shutdown Cooling Mode, with conditions as follows:
- The plant is in MODE 4, Cold Shutdown.
- NO Reactor Recirculation Pumps are in operation.
- RHR B Loop Flow is 5000 gpm.
- Cooldown Rate is 100°F/hr.
- RHS*MOV8B, HEAT EXCHANGER 1B-INLET BYPASS VLV THROTTLE is 50% open.
Which one of the following valve throttling manipulations is required to operate at rated system flow conditions?
A. RHSMOV40B, SDC B RETURN THROTTLE in the OPEN direction and throttling RHSMOV8B, HEAT EXCHANGER 1 B INLET BYPASS VLV in the OPEN direction.
B. RHSMOV40B, SDC B RETURN THROTTLE in the OPEN direction and throttling RHSMOV8B, HEAT EXCHANGER I B INLET BYPASS VLV in the CLOSED direction.
C. RHSMOV40B, SDC B RETURN THROTTLE in the CLOSED direction and throttling RHSMOV8B, HEAT EXCHANGER 1 B INLET BYPASS VLV in the OPEN direction.
D. RHSMOV40B, SDC B RETURN THROTTLE in the CLOSED direction and throttling RHSMOV8B, HEAT EXCHANGER 1 B INLET BYPASS VLV in the CLOSED direction.
Correct Answer: A With Loop Flow LOW, it is required to throttle RHSMOV40B, SDC B RETURN THROTTLE in the OPEN direction. This will RAISE Cooldown rate. To LOWER Cooldown rate, it is required to throttle RHSMOV8B, HEAT EXCHANGER 1B INLET BYPASS VLV in the OPEN direction.
Plausible Distractors:
B is plausible; identifies misconception on RHR Loop Flow acceptable value (7450 gpm) and action to reduce Cooldown Rate.
C is plausible; identifies misconception on RHR Loop Flow acceptable value (7450 gpm).
D is plausible; identifies misconception om action to reduce Cooldown Rate.
- The plant is in Mode 2, with the following:
- Annunciator 870121, DIVISION I UNIT COOLERS MOTOR OVERLOAD alarms.
- Computer Point HVRTC08, LPCS PMP RM UC402B MOT, Source 49X-2HVRB12 caused the alarm.
Which one of the following describes the affect, if any, of this condition on the operation of the Low Pressure Core Spray System?
If the Low Pressure Core Spray System is INITIATED due to a Loss of Coolant Accident, excessive motor temperatures:
A. will not occur due to this failure, because of the present Mode.
B. will not occur due to this failure, because one Unit Cooler will meet the cooling requirements of the Low Pressure Core Spray System.
C. will not occur due to this failure, because Reactor Building HVAC Supply Fans provides the required cooling for the Low Pressure Core Spray System.
D. will occur as a result of this failure, because BOTH Unit Coolers are required to meet the cooling requirements of the Low Pressure Core Spray System.
Correct Answer: B ONE of TWO LPCS Room Coolers is required to provide adequate cooling. With HVR*UC402A still available, LPCS Room Cooler requirements will be met.
- Following a Loss of Coolant Accident, the following conditions exist:
- ALL Control Rods are inserted.
- Reactor Pressure is 950 psig.
- ONLY High Pressure Core Spray is injecting.
- NO OTHER Injection Systems are operating.
- When RPV Water Level LOWERED to -30 (actual) inches, Automatic Depressurization System Safety Relief Valves were MANUALLY OPENED.
- RPV Water Level LOWERED and stabilized at -60 (actual) inches, with High Pressure Core Spray injecting 6500 gpm.
Which one of the following describes the status of adequate core cooling during this event sequence?
A. NOT been maintained, because RF’V Water Level LOWERED below the Minimum Zero Injection RPV Water Level.
B. NOT been maintained, because RPV Water Level LOWERED below the Minimum Steam Cooling RPV Water Level.
C. IS maintained because RPV Water Level has continuously provided adequate cooling to the fuel by SUBMERGENCE.
D. IS maintained, because RPV Water Level and Core Spray Flow provided adequate cooling by CORE SPRAY’ COOLING.
Correct Answer: D Adequate Core Cooling has been maintained, because Core Spray exceeds 6350 gpm with RPV Water Level above -62 (minus 62) inches.
Plausible Distractors:
A is plausible; would be true with NO Injection, because RPV Water Level LOWERED below -55 (minus 55) inches. (MZIRWL)
B is plausible; would be true if RPV Water Level LOWERED to -39 (minus 39) inches prior to Blowdown. (MSCRWL)
C is plausible; would be true if RPV Water Level remained above -14 (minus 14) inches.
- The plant is operating at 100% power with the Standby Liquid Control System (SLS) in a normal standby configuration.
Which one of the following abnormal conditions will result in a loss of continuity to (SLS) Explosive Valve 2SLS*VEX3A?
A. Trip of SLS Pump A motor thermal overload device.
B. Trip of SLS Pump A suction valve power supply breaker.
C. Blown power supply fuse for Div I Redundant Reactivity Control logic.
D. Blown control power fuse for SLS Pump A motor power supply breaker.
Correct Answer: D 2EHSMCC102 provides motor operating power (600 VAC) and motor control power for Explosive Squibs for 2SLSVEX3A.
Plausible Distractors:
A is plausible; would be true if Motor Breaker power were supplied to Explosive Squibs.
B is plausible; Suction Valve power is from a separate breaker on 2EHS*MCC102.
C is plausible; RRCS provides an SLS Initiation signal, does not provide power to Explosive Squibs.
- The plant is operating at full power. Both NORM-TEST-SRI Toggle Switches are placed in TEST on the Hydraulic Control Unit of a withdrawn control rod.
Which one of the following is the control rod response, if any?
A. Remains at the same position.
B. Inserts at SCRAM speed. Displaced water will drain from the Scram Discharge Volume.
C. Inserts at SCRAM speed. Displaced water will accumulate in the Scram Discharge Volume resulting in a Control Rod Block.
D. Inserts at SCRAM speed. Displaced water will completely fill the Scram Discharge Volume resulting in a Reactor Scram.
Correct Answer: B is correct, Scram Valves remain OPEN. The control rod will insert a SCRAM speed. Displaced water will drain from the Scram Discharge Volume. SDV Vents and Drains REMAIN OPEN.
- Which one of the following describes the AXIAL LOCATION within the Reactor Vessel of a FULLY INSERTED Intermediate Range Monitor (IRM) Detector AND a FULLY WITHDRAWN IRM Detector?
FULLY INSERTED IRM Detector, FULLY WITHDRAWN IRM Detector
A. Top of Active Fuel, 2.5 feet BELOW the Bottom of Active Fuel
B. 1.5 feet ABOVE Core Centerline, Bottom of Active Fuel
C. Top of Active Fuel, 1.5 feet BELOW Core Centerline
D. 1.5 feet ABOVE Core Centerline, 2.5 feet BELOW the Bottom of Active Fuel
Correct Answer: D When an IRM Detector is FULLY INSERTED, it is axially located at 1.5 feet ABOVE Core Centerline and when an IRM Detector is FULLY WITHDRAWN, it is axially located at 2.5 feet BELOW Bottom of Active Fuel.
- Which one of the following conditions will cause the IRM B Detector Retract Permit green indicating lamp to be illuminated?
A. The Reactor Mode Switch in RUN.
B. ALL IRMs are on Range 3 or above.
C. IRM Channel B Detector is fully withdrawn.
D. IRM Channel B indicates greater than 108/125.
Correct Answer: A The Reactor Mode Switch in RUN will illuminate the IRM B Detector Retract Permit green indicating lamp.
Plausible Distractors :
B is plausible; ALL IRMs are on Range 3 or above bypasses SRM Detector Retract function.
C is plausible; IRM Channel B Detector fully withdrawn results in white OUT indicating lamp illuminated.
D is plausible; IRM Channel B indicates greater than 108/125 results in UPSCALE ind icating lamp illuminated .
- The following conditions exist for SRM A, during a plant startup:
- SRMs are fully inserted.
- SRM Channel A indicates 1x10^5 cps.
- Annunciator 603203, SRM UPSC/INOPERABLE alarms.
- Annunciator 603442, CONTROL ROD OUT BLOCK alarms.
- Amber SRM “UPSC ALARM OR INOP” light on P603 is LIT.
- Red SRM “UPSC TRIP” lights on P603 are OFF.
- White “INOP” light at the drawer is OFF.
Which one of the following actions is required, by procedure, to clear the Control Rod Out Block being generated by SRM A?
A. Retract SRM Detector to clear the UPSC condition.
B. Bypass SRM A Channel to clear the INOP condition.
C. Wait until ALL IRMs are on Range 8, THEN retract SRM Detector to clear the UPSC condition.
D. Wait until ALL IRMs are on Range 3, THEN verify the Control Rod Out Block automatically clears.
Correct Answer: A Upscale Alarm condition is indicated by light status. With a startup in progress, SRMs are required to be maintained on scale by retracting detectors.
- With the plant operating at full power, a loss of power from 2VBB-UPS3A occurs.
Which one of the following describes the impact of this power loss of the Average Power Range Monitors?
A. APRM Channels 1 and 2 are de-energized and produces an RPS A Half Scram.
B. APRM Channels 3 and 4 are de-energized and produces an RPS B Half Scram.
C. APRM Channels 1 and 2 lose a power source, but remain energized. Loss of power to a 214 Logic Module produces an RPS A Half Scram.
D. APRM Channels 3 and 4 lose a power source, but remain energized. Loss of power to a 214 Logic Module produces an RPS B Half Scram.
Correct Answer: C APRMs are powered from Quadruple Low Voltage Power Supplies with redundant supply sources. Loss of 2VBB-UPS3A removes one of two inputs of power to QLVPS, and a loss of power to the 214 Logic Module which produces an RPS A Half Scram.
- Following a reactor scram, the following conditions exist:
- Reactor Core Isolation Cooling was manually initiated and is injecting.
- Annunciator 601343, RClC CNDS TK 1A WATER LEVEL LOW alarms.
Which one of the following will occur as a result?
A. ICS”MOV129, PMP 1 SUCT FROM CONDENSATE STOR TK will shut, AND 601318 RClC PUMP 1 DISCH FLOW LOW will alarm.
B. ICSMOV129, PMP 1 SUCT FROM CONDENSATE STOR TK will shut, AND 601327 RClC PUMP 1 SUCTION PRESS LOW will alarm.
C. ICSMOV129, PMP 1 SUCT FROM CONDENSATE STOR TK will shut, then ICSMOV136, PMP SUCT FROM SUPPRESSION POOL will open.
D. ICSMOV136, PMP SUCT FROM SUPPRESSION POOL will open, then ICS*MOV129, PMP 1 SUCT FROM CONDENSATE STOR TK will shut.
Correct Answer: D With a CST Low Level condition, ICSMOV136, PMP SUCT FROM SUPPRESSION POOL will open, then ICSMOV129, PMP 1 SUCT FROM CONDENSATE STOR TK will shut.
- Following a MANUAL initiation of the Automatic Depressurization System (ADS), the following conditions exist:
- Reactor Pressure LOWERED to 80 pig.
- ALL Low Pressure ECCS Pumps have degraded, due to Suction Strainer clogging and have been TRIPPED.
- ONLY the High Pressure ECCS Pump is STILL injecting.
- RPV Water Level reached a MlNlMLlM of 15 inches and is 30 inches, RISING.
What is the status of the ADS Safety Relief Valves (SRVs)?
A. ADS SRVs remain OPEN, due to a logic seal-in.
B. ADS SRVs will SHUT, due to loss of logic seal-in.
C. ADS SRVs will SHUT, due to recovering RPV Water Level.
D. ADS SRVs will remain OPEN, because an ECCS Pump is providing a permissive.
Correct Answer: A Initially, LP ECCS Pumps were RUNNING. Manual Initiation switches energize K6A Initiation Relay AND K8A Seal In Relay. When K8A is energized, it seals itself in by closing a contact above the Seal In Reset pushbutton in the diagram. ADS Valves REMAIN OPEN, even if LP ECCS Pump permissives are
subsequently LOST.
- The plant is operating at 100%, when the following occurs:
- Annunciator 602228, MN STEAM LINE PIPE TUNNEL TEMP HI-HI DIFF TEMP HI, alarms.
- Trip Units E31-N604A and B, MSL TUNNEL EL 263 FT indicate 170°F.
Which one of the following describes the PClS response to these annunciators, and what action is required?
A. ONLY the MSlVs will isolate. It is required to enter N2-SOP-101 C, REACTOR SCRAM.
B. The MSlVs AND the INBOARD MSL Drains will isolate. It is required to enter N2-SOP-101 C, REACTOR SCRAM.
C. The MSlVs AND the OUTBOARD MSL Drains will isolate. It is required to enter N2-SOP-101 C, REACTOR SCRAM.
D. NO automatic actions will occur. It is required to Dispatch an operator to 2CES-IPNL202, TURBINE BLDG HVAC panel, to confirm proper HVAC operation.
Correct Answer: A With Logic inputs A and B tripped, ONLY the MSlVs will isolate. It is required to enter N2-SOP-IOIC REACTOR SCRAM.
Plausible Distractors:
B is plausible; would be true if B and C tripped.
C is plausible; would be true if A and D tripped.
D is plausible; would be true if temperature provided were below the isolation setpoint of 167.2°F.
ARP 602228
• If Channel A or C (Div.1) AND Channel B or D (Div.2) are tripped, then the MSIVs will isolate.
• If Channel A (Div.1) and Channel D (Div.2) are tripped, then the MSIVs and the Outboard MSL Drains (2MSSMOV112 and MOV208) will isolate.
• If Channel C (Div.1) and Channel B (Div.2) are tripped, then the MSIVs and the Inboard MSL Drain (2MSSMOV111) will isolate.
- The plant is operating at full power, when the following indications occurred:
- Reactor Pressure LOWERED from 1020 psig to 101 5 psig and stabilized.
- Main Steam Line A Flow is 3.7 Mlbmlhr.
- Main Steam Line B Flow is 2.9 Mlbm/hr.
- Main Steam Line C Flow is 3.7 Mlbm/hr.
- Main Steam Line D Flow is 3.7 Mlbmlhr.
Which one of the following failures is indicated?
A. OPEN Safety Relief Valve.
B. SHUT Turbine Control Valve.
C. OPEN Turbine Bypass Valve.
D. SHUT Main Steam Isolation Valve.
Correct Answer: A With LOW MSL Flow and LOWERING Reactor Pressure, an OPEN Safety Relief Valve is indicated.
Plausible Distractors:
B is plausible; Reactor Pressure would RISE and MSL Flows would be equal.
C is plausible; Reactor Pressure would remain the same and MSL Flows would remain balanced .
D is plausible; Reactor Pressure would RISE and MSL Flow would be ZERO in one MSL.
- The LEVEL Leg of N2-EOP-C5, Failure to Scram, contains the following override statement condition:
“An SRV is open OR Drywell Pressure is above 1.68 psig”
Per the EOP Basis, which one of the following does this condition indicate?
A. Loss of Coolant Accident has occurred or an RPV Blowdown has been performed.
B. Heat is being added to the Suppression Pool by either the Downcomers or the SRV Tailpipes.
C. Reactor Coolant System is breached and injected Boron will NOT remain in the core.
D. Conditions exist which jeopardize the continued availability of Reactor Water Level Instruments.
Correct Answer: B These conditions indicate that heat is being added to the Suppression Pool by either the Downcomers or the SRV Tailpipes.
Plausible Distractors:
A is plausible; Drywell Pressure > 1.68 psig is a LOCA signal, and SRVs are open following an RPV Blowdown.
C is plausible; Drywell Pressure > 1.68 psig indicates the RCS barrier is breached.
D is plausible; if SRVs are opened and Reactor Pressure lowered with conditions of High Drywell Temperature, Reactor Water Level Instruments may become unavailable.
- The plant is operating at 100% with the following with FWS-P1A and FWS-P1B in service.
At 12:00:00, FWS-LV10A has a loss of control power
At 12:00:30 the following results:
- Reactor scrams
- Power LOWERS to 40%
- SRVs are cycling to control Reactor Pressure
Which one of the following describes the condition of FWS-LV10B and FWSLV10A at 1201:00, with NO operator actions?
FWS-LVI0A ; FWS-LV10B A. Auto and Open ; Auto and Shut B. Auto and Open ; Auto and Open C. Manual and Open ; Manual and Shut D. Manual and Shut ; Manual and Shut
C. Manual and Open ; Manual and Shut
On a loss of control power, the LV10’s will not re-position to the closed position, the valve control logic needs power to process the LV10 close signal from RRCS
On a LV10 Lock-up, the lockup will be cleared by RRCS and the valve will go closed so long as it has control power. This will occur even if there is a loss of “Control Signal”
- The plant is in COLD SHUTDOWN with one train of Standby Gas Treatment (GTS) inoperable.
Which one of the following plant changes results in the requirement for BOTH trains of GTS to be operable?
A. Reactor Water Temperature unexpectedly rises above 200°F.
B. Loss of Secondary Containment Differential Pressure.
C. New Fuel is being placed in the Spent Fuel Pool.
D. Operational Mode is changed to MODE 5.
A TWO GTS trains are required to be OPERABLE in MODES 1,2, and 3 (MODE 3 is RPV temperature above 200°F)
- The plant is at 100% power with the following:
Division I Diesel Generator has been started and is being set up to perform a load test in parallel with 2ENSSWG101 in accordance with N2-OP-100A. The
operator is ready to parallel the engine with 2ENSSWG101.
Which one of the following conditions will ensure the Division I Diesel Generator does NOT trip due to excessive Reactive Load?
A. SYNCHROSCOPE (EMERGENCY POWER-DIV I) is rotating slowly in the clockwise direction.
B. 4.16KV 2ENSSWG101 INCOMING VOLTS indicates 5.20 kV AND 4KV RTX-XSR1A/ABSX1/ EGSEG1 RUNNING VOLTS indicates 4.20 kV.
C. 4.16KV 2ENSSWG101 INCOMING VOLTS indicates 4.20 kV AND 4KV RTX-XSR1A/ABSX1/ EGSEG1 RUNNING VOLTS indicates 4.20 kV.
D. BREAKER 2ENS*SWG101-1 is closed when SYNCHROSCOPE (EMERGENCY POWER-DIV I) is at 5 minutes before the 12 o’clock position.
Correct Answer: C
Voltage match prevents excessive Reactive Load during
synchronization. Running Voltage is 2ENS*SWG101, Incoming Voltage is Division I Diesel Generator.
- With a LOSS of power from UPS1A, which one of the following prevents Control Rod movement?
Control Rod movement is prevented by a loss of power to the:
A. PMS Process Computer
B. Intermediate Range Monitors
C. Reactor Manual Control System
D. Scram Discharge Volume Level Instrumentation.
Correct Answer: C The Reactor Manual Control System loses power, which prevents Control Rod movement.
Plausible Distractors:
A is plausible; The PMS Process Computer does not lose power from UPS 1A loss. It is powered from UPS G
B is plausible; IRMs are powered from 24/48 VDC.
D is plausible; SDV Level Instruments do riot lose power from UPS 1A loss. The SDV Level Instruments are powered from UPS 3A/3B (GE Drawing 105E1503T4)
- 2VBB-UPS1B has been placed on battery power with 2VBB-TRS1 out of service for repair.
- DC Bus 2BYS-SWG001C is LOST.
Which one of the following describes the condition of Uninterruptible Power Supply (UPS) 2VBB-UPS1B loads following the DC Power Loss?
A. DE-ENERGIZED, due to loss of ALL redundant power sources.
B. ENERGIZED, because 2VBB-UPS1B Inverter Output is UNAFFECTED by this DC Power failure.
C. ENERGIZED, due to MAINTENANCE power AUTOMATICALLY aligned through the Static Switch.
D. DE-ENERGIZED until MAINTENANCE power is MANUALLY aligned through the 2VBB-UPS1B Maintenance Switch.
Correct Answer: C With NORMAL and DC (Inverter Input) Power lost, the Static Switch will automatically align Maintenance Power to UPS Loads. Loads will remain
ENERGIZED.
- The plant is operating at full power, when DC Power from 2BYS*SWG002B is LOST.
Which one of the following describes the affect, if any, of this failure on Reactor Recirculation Pump Breakers?
A. ONLY B Reactor Recirculation Pump FAST Speed Breakers TRIP.
B. BOTH Reactor Recirculation Pumps FAST Speed Breakers TRIP.
C. ONLY B Reactor Recirculation Pump SLOW Speed Breakers have lost control power.
D. BOTH Reactor Recirculation Pumps FAST and SLOW Speed Breakers are unaffected.
Correct Answer: B Plant at full power implies FAST Speed Recirculation Pump operation. With a Loss of DC power from 2BYS*SWG002B, BOTH Reactor Recirculation Pumps FAST Speed Breakers TRIP.
- Given the following conditions:
- A Loss of Offsite Power and LOCA have occurred.
- 2EGSEG3 TRIPS on overspeed during start and CANNOT be started.
- 2EGSEG1 & 2 operate as designed and power their respective buses.
Which one of the following lists includes ALL the ECCS Pumps that have power available?
A. CSHP1, CSLP1 , and RHSP1A ONLY.
B. CSHP1, RHSP1B, and RHSP1C ONLY.
C. CSHP1, CSLP1, RHSP1B, and RHSP1C ONLY.
D. CSLP1, RHSP1A, RHSP1B, and RHSP1 C ONLY.
Correct Answer: A. 2EGSEG3 powers Division II ECCS Pumps, which are RHSP1B, and RHS*P1C.
- The plant is operating at 100% power with the following:
- EMERGENCY DSL GEN 1 LOCA SIGNAL BYPASS switch is ON.
- RPV Water Level LOWERS to 15 inches.
Which one of the following describes the affect of these conditions on the Division 1 EDG?
Division 1 EDG will:
A. NOT START when DIVISION 1 2EGSEG1 START switch is placed in START.
B. MANUALLY START when DIVISION 1 2EGSEG1 START switch is placed in START.
C. AUTOMATICALLY START with NO Emergency Diesel Generator TRIP signals BYPASSED.
D. AUTOMATICALLY START with SOME Emergency Diesel Generator TRIP signals BYPASSED.
Correct Answer: B With the EMERGENCY DSL GEN 1 LOCA SIGNAL BYPASS switch ON, LOCA start signals are bypassed.
Plausible Distractors:
A is plausible; would be true for MAINTENANCE Mode.
- The plant is operating at 100% power, when the following occurs:
- Annunciator 603306, CRD SCRAM VALVE PILOT AIR HDR PRESS HIGH/LOW, alarmed.
- Instrument Air (IAS) header pressure is 120 psig.
- Auxiliary Operator reports the Scram Air Header pressure is steady at 62 psig.
- NO control rods are drifting.
Which one of the following statements describes the action that is to be attempted to restore Scram Air Header pressure, per N2-SOP-19, Loss of Instrument Air?
A. Verify all IAS Compressors are loaded and bypass IAS Dryers.
B. Swap Scram Air Header Supply Filters and Pressure Control Valves.
C. Bypass Scram Air Header Supply Filters and Pressure Control Valves.
D. Verify all IAS Compressors are loaded and isolate Service Air Header.
Correct Answer: B Per N2-SOP-19, it is required to swap Scram Air Header Supply Filters and Pressure Control Valves.
- Piping failures resulted in a loss of Reactor Building Closed Loop Cooling (CCP) flow. Which one of the following components can still be cooled following the
loss of CCP?
A. Drywell Unit Coolers
B. RDS Pump Seal Coolers
C. RHS Pump Seal Coolers
D. Drywell Equipment Drain Coolers
Correct Answer: C RHS Pump Seal Coolers can also be supplied with Service Water.
- N2-OSP-RDS-Q001, SCRAM DISCHARGE VOLUME (SDV) VENT AND DRAIN VALVE OPERABILITY TEST is in progress. The two Scram Discharge Volume
Vent and Drain Pilot Valve TEST pushbuttons are DEPRESSED.
Which one of the following describes system response?
Air is:
A. ALIGNED to the valve actuators causing the SDV Vent and Drain Valves to SHUT.
B. ALIGNED to the valve actuators causing the SDV Vent and Drain Valves to OPEN.
C. ISOLATED and VENTED from the valve actuators causing the SDV Vent and Drain Valves to SHUT.
D. ISOLATED and VENTED from the valve actuators causing the SDV Vent and Drain Valves to OPEN.
Correct Answer: C When the two Scram Discharge Volume Vent and Drain Pilot Valve TEST pushbuttons are DEPRESSED, air is ISOLATED and VENTED from the valve actuators causing the SDV Vent and Drain Valves to SHUT.
- The plant is operating at 98% power, with the following:
- Control Rod 34-19 (a non-peripheral rod) is selected for movement
- APRM #2 fails DOWNSCALE.
- NO operator actions are taken.
Which one of the following identifies the ability of Rod Block Monitor (RBM) Channels A and B to generate a rod block on high local power?
RBM Channel A; RBM Channel B
A. Can generate blocks; Can generate blocks
B. Can generate blocks; Cannot generate blocks
C. Cannot generate blocks; Can generate blocks
D. Cannot generate blocks; Cannot generate blocks
Correct Answer: B APRM #2 is the Reference APRM for RBM Channel 6. If APRM #2 fails downscale, it would provide a signal to the RBM B that is below 26% power. This would result in RBM B being automatically bypassed, so no blocks will be generated. RBM A is not affected
Plausible Distractors:
A is plausible; would be true if a non-reference APRM failed DOWNSCALE.
C is plausible; would be true if APRM 1 failed DOWNSCALE.
D is plausible; would be true if a peripheral rod were SELECTED.
- The plant is operating at full power when the following alarms occur:
- Annunciator 603318, CRD PUMPS SUCTION FLTR DlFF PRESSURE HIGH
- Annunciator 603309, CRD PUMP 1A SUCTION PRESS LOW.
- Annunciator 603308, CRD PUMP 1A/1B AUTO TRIP.
- Annunciator 602324, RWCU PUMP CLG WTR TEMP HIGH.
Which one of the following actions is required?
A. ISOLATE the WCS System
B. START the standby CRD Pump.
C. PLACE the Reactor Mode Switch in SHUTDOWN.
D. THROTTLE WCS*MOV200 until in-service Filter Demins are in HOLD and TRIP the WCS Pump.
Correct Answer: D With NO CRD Pump operating and RWCU PUMP CLG WTR TEMP HIGH alarming, it is required to THROTTLE WCS*MOV200 until in-service Filter Demins are in HOLD.
Plausible Distractors:
A is plausible; Group 6 Isolation occurs due to a different High (NRHX Outlet) Temperature condition.
B is plausible; Low Suction Pressure condition precludes a start of the standby CRD Pump until suction filters are swapped.
C is plausible; and required if Reactor Pressure were LOWER and a withdrawn Control Rod had an Accumulator Trouble.
- The plant is operating at 100% power, with the following:
- Control rod 30-31 is withdrawn to 12
- Rod 30-31 is selected at the Rod Select Module (P603)
- RPS Trip System “B” is tripped due to a failed sensor
- Scram Pilot Valve “A” solenoid fuse at the HCU for the rod blows
Which one of the following describes the resulting 4 Rod Display rod position indication?
A. Double X
B. Double Blank
C. Double Dash
D. Double Zero
Correct Answer: B The rod is scrammed and inserted past the 00 reed switch and displays blanks, if selected on the RSM.
Plausible Distractors:
A is plausible; XX indicates lost RPlS due to bad reed switch
C is plausible; - - indicates rod is passing through odd notch position.
D is plausible; 00 indicates rod is settled at full in notch position zero.