Turbine Trip Setpoints Flashcards
What is the Turbine Thrust Bearing Wear trip setpoint?
Greater than 48 Mils( 8 psig oil pressure)
What is the basis for the Turbine Thrust Bearing Wear trip signal?
Indicates Thrust Bearing failure
What is the Turbine Generator Lockout Relay trip setpoint?
86G
What is the basis for the Turbine Lockout Relay trip signal?
Prevent Turbine Overspeed on a sudden loss of load
What is the Turbine RCIC Initiation trip setpoint?
RCIC Initiation
What is the basis for the Turbine RCIC initiation trip signal?
Prevent damage to the Main Turbine caused by carryover from the Reactor
What is the Turbine Overspeed Mechanical trip setpoint?
110%( 1980 rpm)
What is the basis for the Turbine Overspeed Mechanical trip signal?
Prevent damage to the Turbine Blades
What is the Turbine Overspeed Backup trip signal?
110.5%( 105% in Standby)
What is the basis for the Turbine Overspeed Backup trip signal?
Backup to Mechanical Overspeed Trip
What are the two Manual trips for the Main Turbine?
1) Manual Pushbutton 2) Manual Trip Lever at the Front Standard
What is the Turbine High RPV Level trip setpoint?
Level 8( 219 inches)
What is the basis for the Turbine High RPV Level trip signal?
Prevent damage to the Main Turbine caused by carryover from the Reactor
What is the Turbine High Vibration trip setpoint?
12 Mils
What is the basis for the Turbine High Vibration trip signal?
Prevent loosened part damage - Indication of a severe problem
What is the Turbine High-High MSR Level trip setpoint?
1) 195 inches 1A/1B 2) 217 inches 2A/2B
What is the basis for the Turbine High-High MSR Level trip signal?
Prevent moisture carryover to the Low Pressure Turbine
What is the Turbine Loss of Stator Cooling Runback trip setpoint?
1) 81 degrees C at the Stator outlet 2) 42.5 psig at the Stator inlet
What is the basis for the Turbine Loss of Stator Cooling Runback trip signal?
Prevent overheating of the Generator Stator Windings
What is the Turbine Loss of 125 VDC trip setpoint?
Turbine less than 75% rated speed
What type of trip signal is the Turbine Loss of 125 VDC(energize/de-energize)?
Loss of 125 VDC signal energizes to cause a trip
What is the basis for the Turbine Loss of 125 VDC trip signal?
Loss of Control Power source
What is the Turbine Loss of 24 VDC trip setpoint?
Loss of 24 VDC
What is the basis for the Turbine Loss of 24 VDC trip signal?
Loss of Trip Power