MSIV Closure and Setpoints Flashcards

1
Q

What will cause the MSIVs to close?

A

1) Low Main Steam Line Pressure. 2) Low Condenser Vacuum. 3) Low Reactor Level. 4) High Main Steam Line Flow. 5) High Turbine Building Temperature. 6) High Steam Tunnel Temperature. 7) Manual.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the closure setpoint for Low Main Steam Line Pressure?

A

807 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the closure setpoint for Low Condenser Vacuum?

A

21.5 in HgA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the closure setpoint for Low Reactor Level?

A

Level 1(16.5 inches)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the closure setpoint for High Main Steam Line Flow?

A

254 psid

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the closure setpoint for High Turbine Building Temperature?

A

145.8 F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the closure setpoint for High Steam Tunnel Temperature(2)?

A

156 F or 152.5 F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is required to bypass the MSIV closure on Low Main Steam Line Pressure?

A

The Mode Switch being in a position other than RUN.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly