What are the ADS Logic Initiation signals?
Level 3(130 inches) and Level 1(16.5 inches) and RHR Pump discharge pressure of 125 psig or LPCS Pump discharge pressure of 145 psig and 105 seconds
What type of logic does ADS utilize?
1) 2 out of 2 taken once 2) Time delay and Instantaneous signals both required
What are the RRCS Alternate Rod Insertion initiation signals?
1) Level 2(130 inches) 2) 1083 psig 3) Manual Arm and Depress 4) Test
What is the RRCS Feedwater Runback initiation signal?
1083 psig and APRMS not downscale within 25 seconds
What is the RRCS Reactor Recirc Pump Downshift initiation signal?
1083 psig
What is the RRCS Reactor Recirc Pump Trip initiation signal?
1) Level 2( 130 inches) 2) 1083 psig if APRMs are not downscale within 25 seconds
What are the RPS Bus EPA Breaker trip signals?
1) 132 VAC 2) 108 VAC 3) 57 Hertz
What is the Low Pressure Coolant Injection initiation signal?
1) Level 1( 16.5 inches) 2) Drywell Pressure 1.68 psig
What type of logic does LPCI utilize?
Series/Parallel Logic
What is the Containment Spray Logic initiation signal?
LPCI initiation for 10 minutes( 10 minutes 35 seconds for B) and Drywell pressure 1.68 psig and Containment pressure 7.72 psig
What are the RHR pump trip signals?
1) Under-Voltage 2) Over-Current 3) No Suction Path( A/B Only)
What is the maximum injection pressure for the RHR pumps?
280 psig
What conditions cause the RHR Pump Minimum Flow Valve to automatically open?
RHR Pump breaker closed with less than 1650 gpm for 8 seconds
What condition causes the RHR Pump Minimum Flow Valve to automatically close?
Greater than 1650 gpm
What are the RHR Shutdown Cooling Isolation signals?
1) Level 3(178 inches) 2) RHR Room high temperature( 157 F) 3) Reactor Pressure 135 psig
What valves are closed by the RHR Shutdown Cooling Isolation signal?
1) E12-F008 RHR SDC Outboard Isolation 2) E12-F009 RHR SDC Inboard Isolation 3) E12-F023 RHR A Head Spray Isolation 4) E12-F037A/B RHR SDC Upper Pool Isolations 5) E12-F053A/B RHR SDC Feedwater Isolations
What are the LPCS Initiation signals?
1) Level 1(16.5 inches) 2) High Drywell Pressure 1.68 psig
What type of logic does LPCS utilize?
Series/Parallel Logic
What conditions cause the LPCS Minimum Flow Valve to automatically open?
LPCS Pump Breaker closed with flow less than 1350 gpm
What condition causes the LPCS Minimum Flow Valve to automatically close?
Greater than 1380 gpm for 5 seconds
What condition causes a LPCS Pump breaker trip?
Over-current
What is the maximum injection pressure for the LPCS Pump?
450 psig
What are the HPCS initiation signals?
1) Level 2(130 inches) 2) High Drywell Pressure of 1.68 psig
What type of logic does HPCS utilize?
Series/Parallel Logic
What conditions cause the HPCS Minimum Flow Valve to automatically open?
Discharge Pressure greater than 145 psig and Flow less than 725 gpm
What conditions cause the HPCS Minimum Flow Valve to automatically close?
1) Discharge Pressure less than 145 psig 2) Flow greater than 725 gpm
What condition causes a HPCS Pump Breaker trip?
Over-Current
What conditions cause the HPCS Suppression Pool Suction Valve to automatically open?
1) Suppression Pool High Level(18.4 feet) 2) Condensate Storage Tank Low Level(98K gallons)
What condition causes the HPCS Injection Valve to automatically open?
Level 2(130 inches)
What condition causes the HPCS Injection Valve to automatically close?
Level 8(219 inches)
What is the RCIC Initiation signal?
Level 2(130 inches)
What conditions cause the RCIC Minimum Flow Valve to automatically open?
Discharge Pressure greater than 125 psig and Discharge Flow less than 120 gpm
What conditions cause the RCIC Minimum Flow Valve to automatically close?
1) Discharge Flow greater than 180 gpm 2) E51-F045 RCIC Steam Isolation closed 3) E51-F510 RCIC Trip Throttle Valve closed
What conditions cause the RCIC Suppression Pool Suction Valve to automatically open?
1) Suppression Pool High Level(18.4 feet) 2) Condensate Storage Tank Low Level(98K gallons)
What conditions produce a RCIC Isolation signal?
1) RCIC Room High Temperature 2) Steam Tunnel High Temperature 3) RHR Room High Temperature 4) High Steam Flow 5) High Steam Flow RHR 6) Low Steam Supply Pressure 7) Turbine Rupture Disk 8) Manual
What is the setpoint for the RCIC Room High Temperature Isolation signal?
143 F
What is the setpoint for the RCIC Steam Tunnel High Temperature Isolation signal?
156 F
How long is the time delay for the RCIC Steam Tunnel High Temperature Isolation signal?
29 Minutes
What is the setpoint for the RCIC RHR Room High Temperature Isolation signal?
157 F
What is the setpoint for the RCIC High Steam Flow(RHR) Isolation signal?
52.1 Inches of Water
What is the setpoint for the RCIC High Steam Flow Isolation signal?
290 Inches of Water
What is the setpoint for the RCIC Low Steam Supply Pressure Isolation signal?
60 psig RCIC Steam Line Pressure
What is the setpoint for the RCIC Turbine Rupture Disk Isolation signal?
10 psig
What condition causes the RCIC Injection Valve to automatically open?
Level 2(130 inches)
What condition causes the RCIC Injection Valve to automatically close?
Level 8(219 inches)
What conditions produce a Control Room Ventilation Emergency Recirculation Initiation signal?
1) RHR LOCA( Level 1 or 1.68 psig in the Drywell) 2) LOOP 3) High Control Room Atmosphere Radiation(on the gas channel)
What conditions produce a Control Room Venitilation and Emergency Recirculation Train Trip signal?
1) Loss of power or control power to any fan 2) Low flow on any running fan