Condenser Vacuum Trip Setpoints Flashcards
1
Q
What action occurs at a Main Condenser Vacuum of 5.6 inches HgA?
A
Input to the Main Turbine Load Limit Setback Logic and the Reactor Recirc Flow Control Valve Runback logic
2
Q
What action occurs at a Main Condenser Vacuum of 8.1 inches HgA?
A
Main Turbine Trip
3
Q
What action occurs at a Main Condenser Vacuum of 11.5 inches HgA?
A
Reactor Feed Pump Turbines Trip
4
Q
What action occurs at a Main Condenser Vacuum of 20 inches HgA?
A
Main Turbine Bypass Valves close
5
Q
What action occurs at a Main Condenser Vacuum of 21.5 inches HgA?
A
Main Steam Isolation Valves close