Topic Quiz, 4-Hour, Plumbing Flashcards
The water service pipe should be installed at least _____ below grade or ____ below the frost line.
a. 6’’, 12’’
b. 12’’, 6’’
c. 12’’, 18’’
d. 6’’, 6’’
b. 12’’, 6’’
[IRC P2603.5]
The minimum size pipe used from a water main to a house is: _____
a. 1/2’’
b. 1’’
c. 1 1/2’’
d. 3/4’’
d. 3/4’’
[IRC P2903.7]
PEX (Cross-linked polyethylene) tubing should be supported at least every _____ horizontally & vertically every_____.
a. 32’’, 10’
b. 32’’, 2’
c. 3’’, 10’
d. 6’’, 10’
a. 32’’, 10’
[IRC TABLE P2605.1]
Shower compartments shall have at least ____ of interior cross-sectioned area.
a. 300 sq in
b. 666 sq in
c. 900 sq in
d. 1200 sq in
c. 900 sq in
[IRC P2708.1]
Plumbing fixtures OTHER than _______, shall be provided with strainers.
a. bathtubs
b. shower stalls
c. water closets
d. water receptors
c. water closets (toilets)
[IRC P2702.1]
What is the minimum size trap for a bidet?
a. 1.5’’
b. 1.25’’
c. 2’’
d. 2.5’’
b. 1.25’’
[IRC TABLE P3201.7]
What is the minimum size of a drain pipe on any appliance?
a. 1 1/4’’
b. 2’’
c. 1 1/2’’
d. 3’’
a. 1 1/4’’
P2713.1 Bathtub Waste Outlets
P2714.1 Sink Waste Outlets
P2715.1 Laundry Tub Waste Outlet
P2716.1 Food-Waste Disposer Waste Outlets
P2717.2 Sink and Dishwasher
*** IRC states all serviced by 1 1/2’’ drain
A kitchen drain, if properly trapped, will have a minimum water seal of: _______
a. 4’’
b. 3’’
c. 2 1/2’’
d. 2’’
d. 2’’
[IRC P3201.2]
The minimum diameter of a floor drain waste outlet is: _____
a. 1 1/4’’
b. 1 1/2’’
c. 2’’
d 3’’
c. 2’’
[IRC P2719.1]
The minimum diameter for a dry vent is: ______
a. 1 1/4’’
b. 1’’
c. 1 1/2’’
d. 2’’
c. 1 1/2’’
[IRC P3108.3]
When a vent terminates less than 2’ above a window, what is the minimum horizontal distance required to the window opening?
a. 10’
b. 4’
c. 6’
d. 5’
a. 10’
[IRC P3103.5]
The minimum size of a plumbing exhaust vent is _____?
a. 1’’
b. 1 1/2’’
c. 2’’
d. 1 1/4’’
d. 1 1/4’’
[IRC P3113.1]
Water heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion air will not be taken from the ______ space.
a. entire
b. immediate
c. living
d. ALL OF THE ABOVE
c. living
[IRC M2005.2]
A water heater inspection includes checking for all of the following features EXCEPT:
a. Pressure relief valve
b. A fullway valve
c. Vacuum breaker installation
d. Minimum clearance above garage floor of 18’’ to source of ignition
c. Vacuum breaker installation
[TAC §535.231(b) (iv), (viii) & (xii)
Access to water heaters located in an attic or underfloor crawl space is permitted to be through a ______ located in a sleeping room or bathroom where ventilation of those spaces is in accordance with code.
a. access door
b. shower
c. closet
d. ALL OF THE ABOVE
c. closet
[IRC M2005.2.1]
What is the maximum length of a gas line that connects to a gas appliance?
a. 6’
b. 8’
c. 3’
d. 12’
a. 6’
[IRC G2420.5.1 & G2422.1.2.1]
There should be NO gas pipe in circulating or ventilating air ducts (TRUE/FALSE)
TRUE
[IRC G2415.3]
Gas piping must be buried at least _____ underground
a. 18’’
b. 12’’
c. 24’’
d. 8’’
b. 12’’
[IRC G2415.12]
For a whirlpool tub, access openings size minimum _____ must be provided.
a. 12’’ X 12’’
b. 12’’ X 18’’
c. 20’’ X 30’’
d. 22’’ X 30’’
a. 12’’ X 12’’
[IRC P2720.1]
Whirlpool tub pump must be accessible & installed above the _____ of the traps.
a. Trap arm
b. Crown weir
c. Slip joint
d. Vacuum breaker
b. Crown weir
[IRC P2720.2]