Topic Quiz, 4-Hour HVAC Flashcards
A forced air furnace, according to the IRC (International Residential Code) furnace room passage way should be a minimum of _____ wide?
a. 15’’
b. 24’’
c. 15’’
d. 20’’
b. 24’’
[IRC M1305.1.3]
What is the maximum distance a furnace in the attic should be from the access opening?
a. 16’
b. 8’
c. 12’
d. 20’
d. 20’
[IRC M1305.1.3]
The opening or door to a furnace room shall be large enough to permit the removal of the largest piece of equipment, but not less than _____ in width.
a. 20’’
b. 24’’
c. 30’’
d. 36’’
b. 24’’
[IRC M1305.1.2]
Which of the following is NOT true for a Type-B gas vent?
a. Type-B vents shall terminate not less than 1’ above the roof.
b. Type-B vents shall conform to UL-441
c. Type-B vents are permitted for use with oil burning appliances.
d. Type-B vents shall NOT be less than 8’ from a vertical wall or similar obstruction.
c. Type-B vents are permitted for use with oil burning appliances.
{IRC TABLE M1804.1]
(R202 Definitions: TYPE L-VENT. A listed and labeled vent conforming to UL 641 for venting oil-burning appliances listed for use with Type L vents or with gas appliances listed for use with Type B vents.)
How far must a forced air vent or gas flue terminate below a horizontal window?
a. 2’
b. 4’
c. 6’
d. 8’
b. 4’
[IRC G2427.8 (2)]
You cannot take return air from a: ______
a. Bedroom
b. Kitchen
c. Dining room
d. Hallway
b. Kitchen
[IRC M1602.2 (4) & G2442.4, Exc-6]
What is the differential for A/C?
a. 10 deg
b. 20 deg
c. 25 deg
d. 30 deg
b. 20 deg
Per Principles of of Home Inspection, Systems & Standards, 3rd Ed, Chp 12, 15-20 degrees
Access to A/C equipment in the attic shall not be smaller than:
a. 22’’ X 36’’
b. 22’’ X 30’’
c. 22’’ X 24’’
d. 18’’ X 24’’
b. 22’’ X 30’’
[IRC M1305.1.3]
What is the location of the ID-Plate on an A/C unit?
a. On the wall
b. Inside the evaporative coil housing
c. On the condensing unit
d. Next to the electrical cutoff
c. On the condensing unit (outside unit)
A device used for reducing air temperatures by the process of evaporating water into an airstream.
a. Evaporative cooler
b. Water Heater
c. Bathroom exhaust
d. A/C condenser
a. Evaporative cooler
[IRC R202 Definitions]
Evaporative cooling equipment & appliances shall comply with:
a. UL 1995
b. According to the manufacturers instructions
c. On level platforms
d. ALL OF THE ABOVE
d. ALL OF THE ABOVE
[IRC M1413.1 (1-5)]
A receptacle outlet shall NOT be required for the servicing of evaporative coolers (TRUE/FALSE)
TRUE
[IRC E3901.12 Exception]
[SCENARIO]
When the space between studs in walls or partitions is used as a duct for circulating air, the portions of such space used shall be cut off from all remaining un-used portions of the stud space by: _______
a. Any type of air-tight material
b. Tapes, mastic or gasketing
c. Only non-combustible materials
d. Tight-fitting sheet metal or 1 1/2’’ thick wood stops
d. Tight-fitting sheet metal or 1 1/2’’ thick would stops
[IRC M1601.1.1 (7)]