24 Hour, Electrical Systems Quiz Flashcards
All electrical materials, components, devices, luminaries (fixtures) & equipment shall be _____ for the application, shall bear the label of an approved _____.
a. approved/company
b. permitted/manufacturer
c. listed/agency
d. in-compliance/Engineer
a. approved/company
[IRC E3403.3]
or c. listed/agency
(Electrical materials, components, devices, fixtures & equipment shall be LISTED for the application, shall bear the label of an approved AGENCY & shall be installed, & used, or both, in accordance with the manufacturer’s installation instructions.)
Direct buried conductors & cables emerging from the ground shall be protected by enclosures or raceways extending to a minimum height of ____ above finished grade.
a. 7’
b. 8’
c. 10’
d. 12’
b. 8’
[IRC E3803.3]
A metal underground water pipe used as part of the grounding electrode system shall be in direct contact with the earth for a minimum of _____.
a. 8’
b. 10’
c. 15’
d. 20’
b. 10’
[IRC E3608.1.1]
Workspace in front of an electrical panel board shall be a minimum of _____ in width, but no less than the width of the panel board.
a. 30’’
b. 36’’
c. 42’’
d. 48’’
a. 30’’
[IRC E3405.2]
The dedicated space above a panel board shall be a minimum of ____ high or to the structural ceiling, whichever is lower.
a. 4’
b. 5’
c. 6’
d. 6.5’
c. 6’
[IRC E3405.3]
Panelboards & overcurrent protection devices are prohibited in ______ .
a. Clothes closets
b. Sleeping rooms
c. Garages
d. Storage rooms
a. Clothes closets
[IRC E3405.4]
(clothes closets, bathrooms, over steps of stairways)
Bonding is?
a. Another word for grounding.
b. Joining two electrical connectors together.
c. The act of putting an “anti-oxidant” on 2 dissimilar metals.
d. Refers to “pig-tailing” aluminum wires.
b. Joining two electrical connectors together.
[CSRE, Book #3, pg. 160]
Reverse polarity means?
a. The BLACK wire is HOT & the WHITE wire is NEUTRAL
b. The WHITE wire is HOT & the BLACK wire is NEUTRAL
c. The GROUND wire is OPEN
d. The NEUTRAL wire is OPEN
b. The WHITE wire is HOT & the BLACK wire is NEUTRAL
[CSRE, Book #3, pg. 166]
An OPEN wire means?
a. NOT connected
b. REVERSE Polarity
c. The outlet is NOT grounded
d. The wire is POLARIZED
a. NOT connected
The minimum size of conductors for feeders & branch circuits shall be ____ (AWG) copper.
a. No. 14
b. No. 12
c. No. 10
d. No. 22
a. No. 14
[IRC E3406.3]
[IRC TABLE E3702.13]
(The minimum size of conductors for feeders and branch circuits shall be 14 AWG copper & 12 AWG aluminum)
Insulated grounded conductors of sizes No. 6 (AWG) & smaller may be identified by all BUT which one of the following methods?
a. Continuous WHITE outer finish.
b. Continuous NATURAL GRAY outer finish.
c. Continuous BLACK outer finish.
d. 3 Continuous WHITE stripes (on other than GREEN insulation)
c. Continuous BLACK outer finish.
[IRC E3407.1]
What is the minimum permitted size of a grounded service conductor serving a maximum load of 150 amps?
a. No. 1 (AWG) AL
b. No. 1 (AWG) CU
c. No. 1/0 (AWG) AL
d. No. 1/0 (AWG) CU
b. No. 1 (AWG) CU
[IRC TABLE E3603.1]
The rating of any one cord-&-plug-connected utilization equipment shall be a maximum of ____ the branch-circuit ampere rating.
a. 80%
b. 100%
c. 110%
d. 125%
a. 80%
[IRC E3702.3]
A minimum of _____ branch circuit shall be provided for receptacles located in the laundry room & a minimum of _____ branch circuit(s) shall be provided to supply bathroom receptacle outlet(s).
a. 1-15 amp rated/1-15 amp rated
b. 1-20 amp rated/1-20 amp rated
c. 1-15 amp rated/2-15 amp rated
d. 1-20 amp rated/2-20 amp rated
b. 1-20 amp rated/1-20 amp rated
[IRC E3703.3 & E3703.4]
What is the maximum over current protection device rating permitted for No. 12 (AWG) CU conductors?
a. 15 amps
b. 20 amps
c. 25 amps
d. 30 amps
b. 20 amps
[IRC TABLE E3705.5.3]
Houses are generally wired in ____ ?
a. Parallel
b. Series
c. Current
d. Red
a. Parallel
[CSRE, Book #3, pg. 154]
What would 4 wires mean?
a. 3-phase electricity
b. 120V service
c. There is no neutral wire
d. The house has a large pool or spa
a. 3-phase electricity
Gas Piping, “Black Pipe”, can be used as a ground (TRUE/FALSE)
FALSE
[IRC E3608.6]
(A metal underground gas piping system shall not be used as a grounding electrode.)
How far can a GFCI be located from a tub or shower?
a. 3’
b. 2’
c. 1’
d. NO MINIMUM
d. NO MINIMUM
At a kitchen counter, countertop receptacle outlets shall be installed with a maximum horizontal distance of ____ from any point along the wall line to an outlet.
a. 12’’
b. 18’’
c. 24’’
d. 36’’
c. 24’’
[IRC E3901.4.1]