Systems Test 6 Flashcards
- LOT 202.23 OL-ACW*
- *
Which loads have auto TCV’s?
Gen H2 cooler (1)
Turbine Lube Oil Coolers (2)
SGFPT Lube Oil Coolers (6)
Gen H2 Cooler TCVs controlled on CP007.

- LOT 202.15 SGWLC*
- *
How does the LPRVs control SGWL?
- SG Water Level Mismatch:*
- *Actual Level - Program Level**
- PR NI Compensation:*
- *Auctioneered High NI**
Low Power Feed Reg Valves are level dominant.
- LOT 202.22 Circulating Water*
- *
What will auto start the CW Screen Wash Pumps?
Lead Pump:
Screen D/P > 6”
One Screen Running
First Lag Pump:
10 Sec after lead pump start, Pressure < 102 psig
4 Screens Running
Second Lag Pump:
10 Sec after 1st lag pump start, Pressure < 102 psig
7 Screens Running
If pump started on low pressure will not stop. (Must reset)
Note:
Spray valves will open when pressure > 90 psig
- LOT 202.22 Circulating Water*
- *
What will energize the blue start permissive light on CP009?
Discharge Column filled*
- *Seal Pressure > 30 psig**
- < 50 psig starts standby pump*
Discharge Valve Closed
> 5 mins since last CW pump start
Can use Jet pump to draw air and moisture out of CW discharge column.
- Uses screen wash header as prime water

- LOT 202.15 SGWLC*
- *
How does the SGFPTs control SGWL?
- Pressure Mismatch:*
- *Actual D/P - Reference D/P**
- Actual D/P:*
- *Feed Pressure (PT-558) - Steam Pressure (PT-557)**
- Reference D/P:*
- *0% - 20% Steam Flow: 65 psid**
- *100% Steam Flow: 169 psid**
- Goes up linearly from 20% - 100%*
- PT-558 (Common Header Feed Pump Discharge Pressure)
- PT-557 (MS Equalizing Header)
- Same as steam dumps
Note:
Steam flow is the selected steam flow channel on CP006.

- LOT 202.28 AFW*
- *
What level in the AFWST requires the operators to enter FLEX?
- Loss of All AC Power:*
- *< 164,000 gals**
- LOT 201.29 Fire Protection*
- *
If the fire protection pump auto starts, what is the only thing that will trip the pump?
Mechanical Overspeed

Applies if pumps start on Low Header Pressure, Loss of power, or remote start from either control room. (CP018)
Note:
Cannot be stopped from control room.
- LOT 202.24 CL-ACW*
- *
What will auto start/trip the CL-ACW pumps?
Auto Starts:
Discharge Header Pressure - Low (60 psig)
Trip of running pump
- Trips:*
- *Ground Fault**
Overcurrent
Undervoltage
Controlled from CP009/Local
Note:
SW/FW HX Common discharge pressure on CP009 NOT pump discharge pressure.
- LOT 201.40 AMSAC*
- *
When will AMSAC actuate?
SGNR Level ≤ 15% [1/1 on 3/4] [25 sec TD]
Initiates:
- Turbine Trip
- Aux Feed Actuation
- Blowdown Isolation
- SG Sampling Isolation
Note:
Armed if ≥ C-20 (≥ 30% Impulse Pressure) [2/2] ≈ 40% RTP
- Peak pressure not a concern if < 70% RTP
- Stays armed for 360 sec after falling below 30% impulse pressure
- LOT 202.24 CL-ACW*
- *
What does CL-ACW cool?
Turbine:
EHC (120 ˚F)*
Air Side Seal Oil (105 ˚F)*
H2 Side Seal Oil (105 ˚F)*
Exciter Coolers (113 ˚F)*
Isophase
Stator Cooling Water (105 ˚F)*
Feed / Condensate:
Condensate Pump Bearings
Feed Booster Pump Bearings / Lube Oil
SUFW Seals / Lube Oil*
TCV closes at low temps
Misc:
IA Compressors (11/12/13)
After Cooler / Lube Oil
Secondary Sampling
MSDT pumps Seal Water
CARS
Note:
Coolers have automatic TCVs
- LOT 202.20 Stator Cooling Water*
- *
What D/P across the stator will trip the turbine?
Stator Cooling Water D/P - Low (19 psid) [2/3] [40 sec TC]
Will get alarm in ZLP-150 (Basement Shelter) after 10 sec [1/3]
Note:
This is D/P across the stator. Do not confuse with D/P across the running pump. (Auto Start of standby SCW pump)
- LOT 202.22 Circulating Water*
- *
What is the CW pump start sequence?
- First Pump:*
- *10 sec after start, Discharge MOV opens to 40%**
- Second Pump:*
- *10 sec after start, 2nd Pump’s Discharge MOV fully opens**
Once 2nd Pump’s Discharge MOV is 35% open, 1st Pump’s Discharge MOV fully opens
- Third / Fourth Pump:*
- *10 sec after start, Discharge MOVs fully open**
Pump trips:
- Discharge MOV NOT moving after 24 sec
- Discharge MOV NOT 35% open in 32 sec
- LOT 202.20 Stator Cooling Water*
- *
What stator cooling water parameters would cause the operators to manually trip the reactor and turbine if > P-9?
- *SCW D/T - High (≥ 21.5 ˚F)**
- U5524 / U5525*
- *SCW Temperature - High (194 ˚F)**
- U5520 / U5521*
- LOT 202.12 FW Heaters / Drips/ Vents*
- *
What are the influents/effluents of HP Htr 11A/B?
Influents:
RHDT’s
HP Turb 4th Stage
MSR Vent Chamber
- Effluents:*
- *Deaerator**

- LOT 202.23 OL-ACW*
- *
What does OL-ACW cool?
Main Turbine Lube Oil (2)
SGFPT Lube Oil (6)
Generator H2 (1)
CL-ACW (2)
RCB Chillers (3)
MAB Chillers (4)

- LOT 202.28 AFW*
- *
What will auto start the AFW pumps?
- Motor Driven:*
- *SG Level - Low 2 (20%) [2/4 on 1/4]**
AMSAC (15%) [1/1 on 3/4] [25 sec TC]
- *Sequencers (MODE I,II,III)**
- MODE II starts pump but valves do NOT open*
- Turbine Driven:*
- *SG Level - Low 2 (20%) [2/4 on 1/4]**
AMSAC (15%) [1/1 on 3/4] [25 sec TC]
SI
Regulating Valves throttle and OCIVs open for:
- SG Level - Low 2 (20%) [2/4 on 1/4]
- AMSAC (15%) [1/1 on 3/4] [25 sec TC]
- SI
- LOT 202.28 AFW*
- *
What are the design bases for the AFW system?
- Automatic Operation:*
- *Starts within 1 min and can run unattended for 10 mins**
- Flowrate:*
- *Supplies 500 gpm to 1 S/G for FW Rupture / SLB**
Supplies 500 gpm to 2 S/Gs for loss of FW / LOOP
- Cooldown:***
- *50 ˚F/hr with 1 RCP**
25 ˚F/hr on natural circ
- AFWST:***
- *Maintain plant in hot standby for 4 hrs and then go to RHR conditions**
- Containment Integrity:*
- *Prevents reaching containment design pressure (56.5 psig)**
- Note:*
- Showed up on instructor’s NRC exam*
- LOT 201.40 AMSAC*
- *
What is the design basis casualty for AMSAC?
Loss of Feedwater with no RPS Actuation
- PZR PORVs, Rx Trip, Turbine Trip, SG Safeties, and AFW still function.
- Peak pressure: 2833 psig
- Emergency Pressure limit is 3200 psig
Note:
Protected as long as turbine trips in 30 secs and AFW starts in 60 secs
- LOT 202.15 SGWLC*
- *
How does the MFRVs control SGWL?
- SG Water Level Mismatch:*
- *2.5 (Actual Level - Program Level)**
- Flow Mismatch:*
- *0.6 (Steam Flow - Feed Flow)**
MFRVs are level dominant.

- LOT 202.22 Circulating Water*
- *
What will trip a CW pump?
- Starting Pump:*
- *Discharge MOV NOT moving after 24 sec**
Discharge MOV NOT ≥ 35% open in 32 sec
- Stopping Last 2 CW Pumps:*
- *Stopping 1 pump trips both**
- Discharge valves remain open*
- LOT 201.29 Fire Protection*
- *
What is required to be FUNCTIONAL in the Fire Protection System?
2 Tanks (300,000 gal each)
2 Pumps (2500 gpm each)
- 1 Pump FUNCTIONAL (Restore in 7 days)
- Total Volume ≥ 300,000 gal but < 600,000 gals (Restore in 7 days)
- Pumps AND Volume NOT FUNCTIONAL (Restore in 24 hours)
- Underground Piping NOT FUNCTIONAL (Restore in 24 hours)
Note:
Only Safety Related portion of the system is the CIVs
- LOT 202.12 FW Heaters / Drips/ Vents*
- *
What are the influents of the deaerator?
- Influents:*
- *HP Turb 8th Stage**

MSDT
FWH 11
Main Steam
Aux Steam
- LOT 201.40 AMSAC*
- *
What powers AMSAC?
- AMSAC:*
- *DP006**
- SGNR Level Instruments:*
- *LT-0518/0528: DP1203**
LT-0537/0547: DP1204
Physically located in QDPS RPU-N (35’ EAB Relay Room)
Note:
Instruments fail low on loss of power
- LOT 201.29 Fire Protection*
- *
Which fire hydrants are required for tech specs?
- ECW Intake Structure:*
- *Fire Hydrant #13**
- Restore OR Route hose within 1 hr*
- AFWST:*
- *Fire Hydrant #7 (Unit 1)**
- Restore OR Route hose within 1 hr*
- *Fire Hydrant #20 (Unit 2)**
- Restore OR Route hose within 1 hr*
- Fire Pump Hose House:***
- *Fire Hydrant #10**
- Restore OR Route hose within 1 hr*
Note:
Only required by 0PGP03-ZR-0018.
- LOT 202.23 OL-ACW*
- *
What TCVs can be controlled from the control room?
- CP007:*
- *Gen H2 cooler**
- Both TCVs*

Raising demand causes bypass to open and suction to close.
Note:
All other TCVs are local control only
- LOT 202.22 Circulating Water*
- *
What reservoir temperature will require running all four CW pumps?
69 ˚F
Running all four CW Pumps < 69 ˚F will raise the plant’s condensate depression and lower overall efficiency.
- LOT 202.28 AFW*
- *
What is the minimum speed of the terry turbine?
- *1900 RPM**
- 45 sec after start*
Must trip terry turbine if < 1900 RPM to prevent damage
- LOT 202.28 AFW*
- *
Where are MOV-0514 and MOV-0143 physically located?
- MOV-0514: Trip / Throttle Valve
- MOV-0143: MS Supply
- MOV-0514:*
- *Terry Turbine Cubicle (IVC 10’)**
- MOV-0143:*
- *By SG PORVs (IVC 58’)**
Must leave MOV-0143 open (≥ 2 hrs) or water collects in pipe and will result in overspeed of terry turbine.
- LOT 202.12 FW Heaters / Drips/ Vents*
- *
What will trip the LP HTR Drip Tank Pump?
LP HTR Drip Tank Level - Low (7.5”)
Seal Water Pressure - Low (30 psig)
- *FW HTR 15/16 Level - High [1/2]**
- Respective train’s FW Heater*
Powered from 1D Switchgear.
Note:
Pump Discharge MOV must be closed to start pump.
- LOT 202.23 OL-ACW*
- *
What are the starting permissives and auto starts for the OL-ACW pumps?
- Auto Start:*
- *System Pressure - Low (68 psig)**
- Downstream of the strainer*
- *Trip of Running Pump**
- Starting Permissives:*
- *Seal Water Pressure ≥ 18 psig [Unit 1 ONLY]**
- Will not trip pump*
Note:
Pressure indicator on CP009 is pressure downstream of strainer NOT pump discharge pressure.
- LOT 202.18 Generator Seal Oil*
- *
What pressure does the Air Side Seal Oil Pump (ASSO) maintain the generator seal oil system normally operate at?
- *87 psig**
- 12 psig > than H2 pressure (75 psig)*
Pressure equalizing valves maintain Air side and Oil side at the same pressure.
- LOT 202.12 FW Heaters / Drips/ Vents*
- *
Where does the FW heater drains empty into the condensate system?
- LP Heater Drip Pumps:*
- *Between FW Heater 15 and 16**
- MSDT Pump Discharge:*
- *Upstream of DA inlet valves**
- FW Heater 11:*
- *DA**
Note:
LP Heater Drip Pump seals also come from condensate.

- LOT 202.23 OL-ACW*
- *
What powers the OL-ACW pumps?
- Pump 11:*
- *LC 1D2**
- Pumps 12/13:*
- *LC 1D1**
Controlled on CP009/Locally
- LOT 202.28 AFW*
- *
What is the minimum volume in the AFWST as required by LCO 3.7.1.3 AFWST?

485,000 gals

LCO 3.7.1.3 AFWST
Applicability: MODES 1 - 3
- LOT 202.15 SGWLC*
- *
What is program SGWL?
- *70.7%**
- SGNR Level*
7300 cabinets maintain program level
- LOT 202.20 Stator Cooling Water*
- *
What will auto start the standby SCW pump?
Running Pump D/P - Low (≤ 20 psid)

- LOT 202.22 Circulating Water*
- *
What systems utilize the CW discharge piping?
OL-ACW
ECW Blowdown
- *LWPS**
- Connects to OL-ACW (MAB Chiller 11 in overhead)*

- LOT 202.28 AFW*
- *
What is the major concern when cross-connecting AFW trains?
Runout of Pump (675 gpm)

Will not see on flow meters
- LOT 202.18 Generator Seal Oil*
- *
What pressure does the HSSO D/P Regulator, ASSO D/P regulator, and the Turbine Backup Pressure Regulator maintain?
- ASSO D/P Regulator:*
- *12 psid**
- 5 psid starts DC Pump*
- Turbine (ASSO) Backup Pressure Regulator:***
- *8 psid**
- Supplied from Turbine LO*
Note:
If supplying air side seals from the BOP in the TGLO System, must reduce H2 pressure to < 2 psig.
- LOT 201.29 Fire Protection*
- *
What auto starts the fire protection pumps?
Pump 1:
Header Pressure 130 psig [5 sec TD]
Loss of Power to Panel
Pump 2:
Header Pressure 120 psig [10 sec TD]
Loss of Power to Panel
Pump 3:
Header Pressure 110 psig [15 sec TD]
Loss of Power to Panel
Jockey pump maintains system pressure > 130 psig (35 gpm)
Note:
Jockey pump operated locally in “Hand” position. Auto position non-functional.
- LOT 202.28 AFW*
- *
When will the terry turbine (MOV-0514) trip on overspeed?
- *114%**
- 100% speed is 3600 RPM*
Manual linkage reset after mechanical overspeed (4100 RPM)
Note:
Trip pushbutton on CP006/ASP is an electrical overspeed.
- LOT 202.15 SGWLC*
- *
If a SG Pressure channel fails, how does steam flow fail?
- SG Pressure Fails High:*
- *Steam Flow Fails High**
- SG Pressure Fails Low:*
- *Steam Flow Fails Low**
- LOT 202.22 Circulating Water*
- *
What is the CW pump securing sequence?
- Third and Fourth Pumps:*
- *Once Discharge MOV 80% Open, Pump Stops**
Discharge MOV fully Closes
- First and Second Pumps:*
- *Once 2nd pump’s Discharge MOV 95% Open, BOTH PUMPS TRIP**
Valves Remain As-Is (95% Open / Fully Open)
Must wait 5 mins between securing pumps
Note:
PTL:**Bypasses 5 min TD but Discharge MOVs will still fully close