Systems Test 5 Flashcards
- LOT 202.14 SG Feedwater Pumps*
- *
What speed controllers provide input to the Low / High Pressure governor valves?
- Manual:*
- *0 RPM - 5700 RPM**
- SG Level Control:*
- *3300 RPM - 5600 RPM**
SG Level Control:
- D/P= FW Pressure - Steam Pressure
- Reference D/P 0%: 65 psid
- Reference D/P 100%: 169 psid
Note:
Whichever controller is lower is the one that has control of speed.
- LOT 202.09 Steam Dumps*
- *
How does the operator determine the correct setpoint for the Header Pressure Controller (PK-0557) on CP007?
Desired Pressure/Span of PI-557*10
1185 psig/1400 psig *10 = 8.46 turns
- LOT 202.10 Condensate*
- *
What are the start permissives and trips for the condensate pumps?
- Start Permissives:*
- *Discharge Valve Closed**
- No Automatic Actions*
Recirc Valve Closed
Opens and begins modulating on pump start
Shuts when pump secures [5 sec TD]
Suction Valve Open
Adequate NPSH
- Trips:*
- *Low NPSH**
- Low D/P*
NO AUTO STARTS
Note:
Controlled from CP008
- LOT 202.13 Feedwater*
- *
How is DA level control achieved?
- Manual:*
- *Used when < 5% Feed Flow**
- Single Element:*
- *Used 5% - 20% Feed Flow**
- *DAST Level ONLY**
- Average of DST #1/#2 Level compared to LK-7406 setpoint (CP008)*
- Three Element:*
- *Used > 20% Feed Flow**
- *DAST Level**
- Average of DST #1/#2 Level compared to LK-7406 setpoint (CP008)*
- *Feed Flow compared to Condensate Flow**
- Sum of all 4 feed flows*
Controls CD-7406A (Low Flow) [<40%] and CD-7406 (High Flow) [≥ 40%] (Switch at 40% is automatic)
- LOT 202.04 Turbine Lube Oil*
- *
What will auto start the Bearing Oil Pump?
Lube Oil Pressure - Low 2 (11 psig)
- LOT 202.04 Turbine Lube Oil*
- *
How does the mechanical overspeed device work?
- *MOP/SOB provides oil pressure to the top of Interface valve (125 psig)**
- HP Seal Oil B/U Line*
> 111% RPM will reposition plunger and allow LO to drain
Will cause interface valve to open (< 100 psig) and allow EHC to drain
Trips Turbine
- LOT 202.13 Feedwater*
- *
What is required to reset a FW isolation?
- P-14:*
- *Reset SI/P-14 (CP006) w/ P-4 False**
- *Reset FW Cont & Bypass Valves (CP006)**
- *FW Isolation Switches to “Open” (CP006)**
- Allows control of PBVs, FWIVs, and FWIBs*
SI:
Reset SI (CP001)
Reset SI/P-14 (CP006) w/ P-4 False
Reset FW Cont & Bypass Valves (CP006)
FW Isolation Switches to “Open” (CP006)
Allows control of PBVs, FWIVs, and FWIBs
- P-4 w/ Tavg Low (574 ˚F) [2/4]:*
- *Reset Low Tavg (CP006)**
- Resets all valves except MFRVs*
- *FW Isolation Switches to “Open” (CP006)**
- Allows control of PBVs, FWIVs, and FWIBs*
- *P-4 must be False to operate MFRVs**
- LOT 202.13 Feedwater*
- *
What will auto start/trip a FWBP?
- Auto Start:*
- *Trip of running pump**
Start Permissives:
Lube Oil Pressure > 8 psig
DAST Level > 6%
Oil Pressure ≥ 11 psig
Local switch not in stop
Trip:
Lube Oil Pressure < 8 psig
DAST Level < 6%
UV on switchgear
Overcurrent
Breaker Closing:
- Opens Discharge MOV (Locks in open signal for 3 min)
- Recirc valve will modulate (8000 gpm)
Start permissives being met will be indicated by blue light on 13.8 kV switchgear
- Does not indicate whether MCR switch is in Stop/PTL
- *
Note:
By procedure a standby FWBP will have it’s discharge MOV already open
- LOT 202.21 Isophase*
- *
What must be done if both fans on the Isophase are lost?
Reduce Power to 50%
Lower Isophase Current to 18,500 Amps
Lower load at 5%/min
Generator Current on CP007
Normal current rating is 36,600 Amps
Note:
Isophase trouble on CP010.
- LOT 202.10 Condensate*
- *
What is the minimum flow required through the GSS condenser?
5600 gpm
Ensured by FV-7022
- LOT 202.09 Steam Dumps*
- *
What causes the #1 and #2 solenoids to de-energize?
P-12: Tavg < 563 ˚F [2/4]
Two redundant channels. One for each solenoid.
Can bypass P-12 for Bank #1 Steam Dumps by placing switches on CP007 to Bypass Interlock. (Spring returns to ON)
- Must take switch to OFF/RESET to secure C/D feature.
- LOT 202.14 SG Feedwater Pumps*
- *
What are the SGFPT’s speed increase permissives?
Turbine Exhaust Valve Open
Suction Valve Open
Suction Pressure > 189 psig
Turning Gear Stopped
Applicable when SGFPT’s speed < 3300 RPM
- LOT 202.06 EHC*
- *
How does the load drop anticipator work?
Actuated When:
Turbine Load > 30% (Reheat Pressure)
AND
Generator Breaker manually opened
Overspeed Protection Controller:
Two OPC Solenoids Energize (Open)
Drains EHC Fluid from Governor / IVs ONLY
Will remain closed for 8 sec
Resets and repeats as necessary until turbine load < 30% (Reheat Pressure)
- LOT 202.06 EHC*
- *
What will auto start the standby EHC pump?
- Auto Start:*
- *Low Pressure (1600 psig)**
- Permissive:*
- *EHC Reservoir Tank Level > Extreme Low 2 (7.62”)**
- Will NOT trip running pump*
Normal: 1900 psig - 2100 psig
- Relief (2350 psig)
Switches located on CP007.
- LOT 202.26 Service / Instrument Air*
- *
What happens as IA pressure lowers?
- 122 psig / 119 psig / 116 psig / 113 psig:*
- *Compressors 11 - 13 / 14 Start**
- Lead / Standby / Lag / Air Cooled*
- 100 psig:*
- *Service Air Isolation Closes**
- Reset on ZLP-134 (TGB 29’ by compressors 11/12/13)*
- 90 psig:*
- *IA to yard Closes**
- 88 psig:*
- *Low Power FRVs drift closed**
- 80 psig:*
- *IA Dryer Bypass Opens**
- Reset by valve*
- *Letdown Header Orifice header isolation valves drift Closed**
- 67 psig:*
- *MFRVs drift Closed**
60 psig:
Manually Trip the Rx
MSIVs drift Closed
Service / IA Air pressure indicated on CP008.
- LOT 202.10 Condensate*
- *
What will a high level in FW Heaters 15/16 cause?
Closes Inlet/Outlet valve for respective string
Opens Bypass MOV
Trips associated LPHD Pump
Relays for automatic High level actuation comes from LPHD pump control power.
NO AUTO FEATURES FOR FW HTRS 13/14
Note:
Anticipated following a Rx Trip
- LOT 202.04 Turbine Lube Oil*
- *
What are the turning gear start permissives?
Bearing Oil Lift Pressure > 850 psig
Bearing Oil Header Pressure (PT-6217) > 3.7 psig**
Turning Gear Engaged
Turbine at zero speed
- Controlled locally and CP007.
- Turning gear will disengage from shaft at 3 RPM
- Physically located between LP turbine and generator
*Note: Turning Gear (CP007) must be in auto/manual and shaft speed \< 600 RPM for pressure to be felt on PT-6217.*
- LOT 202.19 Generator H2 Gas*
- *
What are the main generator H2 limits?
45 psig - 85 psig
Must trip turbine if limits exceeded.
Note:
H2 / CO2 purity, pressure, and cold gas temp on CP007.
- LOT 202.14 SG Feedwater Pumps*
- *
What will auto start the SGFPT’s EOPs?
Bearing Oil Pressure < 12 psig
Does not supply interface valve so SGFPT will trip.
1 EOP/SGFPT
Note:
Powered from 250VDC Swbd 1A
- LOT 202.13 Feedwater*
- *
What supplies steam to the deaerator?
Aux Steam
Used During S/U
Switch on CP008
- *Main Steam**
- Used < 25% and during load rejection*
Extraction Steam
8th stage of HP turbine (25% - 100%)
Supplied from 2 of 6 crossunder piping
- LOT 202.13 Feedwater*
- *
What Deaerator Storage Tank level setpoints will cause automatic /operator actions?
- High 2 (89%/90%):*
- *DA Inlet MOVs Close (CD-574/CD-575)**
Extraction Steam Block / Non-Return valves Close
FW HTR 11A/B Drain to DA Valves Close
- 86%:*
- *High Level Dump Valves Open (FW-7175/7175A)**
- 30%:*
- *POP09 requires Rx Trip**
- 6%:*
- *FWBPs Trip**
Normal Level is 70%
Note:
Meter on CP008 and ICS will stop indicating at 30%