Sub Floors Flashcards
What are the minimum clearance requirements for a sub-floor?
150mm
400mm in a termite declared area
What are the minimum stump embedment requirements?
.3 x Stump height or 450mm (whichever is greater)
How do you determine bearer lamination requirements? What would be the spacing for laminating 90mm bearers?
2 x Depth of bearer
Nail every 180mm
How many footing types are there in 1684? What are the kPa requirements for those footings?
5 Footing types
Footings 1-4 - 125Kpa
Footing 5 - 100Kpa
If a bearer is joined half on a stump, what are the bearing requirements?
50mm bearing minimum
What is the minimum bearing requirement for a joist?
30mm
If lapped then 3 x Joist depth
What zone is Melbourne when working out brick ventilation requirements
Melbourne Zone C
What maximum offset can a Stump or Bearer be from an internal load bearing wall (LBW)
Offset max 1.5 x depth of joist
For sub-floor ventilation, what equation is used for ventilation requirements per m2 of wall?
6000mm2 per meter of wall.
1 vent 230 x 75mm = 52 holes @ 11x11mm = 121 x 52 = 6292mm2
How far from an external corner should brick vents be placed?
600mm maximum
For loadbearing walls parallel to bearers, how far can a bearer cantilever?
Up to 25% of their allowable span
If an inspector is carrying out a sub-floor stump inspection, what are they looking for?
Footing depths
Correct footing diameter
Clean holes
Appropriate bearer span
For bearers supporting LBW at right angles, what is the permissible cantilever for 90mm bearer with a sheet roof?
11%
CHECK THIS AS 1684.4 PAGE 35 Table 4.1