Special-Agent Fire Extinguishing Systems and Portable Extinguishers Flashcards

1
Q

When would a special-agent fire extinguishing system need to be provided? (564)

A

Where standard automatic sprinkler systems are not the most effective way to address a particular fire risk. These locations may contain the following:
- Flammable and combustible liquids
- Water-reactive metals or chemicals
- Combustible metals that are flammable solids
- Food preparation equipment
- File storage or archives
- Electronic Information Technology (IT) Equipment
- Electrical transformers and switches
- High-value content such as museums

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Identify the appropriate evaluation and testing methods for special-agent fire extinguishing systems. (594-597)

A

Dry-chemical (NFPA 17) & Wet-Chemical (NFPA 17A): Inspector shall evaluate the application methods, agents, components, and inspection and testing requirements. Dry storage containers <150 lbs must be hydrostatically tested every 12 years. A qualified individual/personnel must verify the system is maintained and serviced as required and have reviewed monthly:
- System parts in correct location
- Manual actuators unobstructed
- Tamper indicators and seals intact
- Maintenance tags in place, up to date
- Obvious damage noted
- Gauges within operational limits
- Equipment modifications/repairs noted

Clean-Agent Systems (NFPA 2001 and NFPA 12A for Halon 1301). Annual inspections by qualified personnel required. Quantity and pressure checked semiannually. Records on tests and inspections must be maintained and available for inspector to review. Inspector must know agents used in systems, components, inspection and testing requirements. Storage containers must meet DOT and TC req’ts and be hydrostatically tested every 5 years. Protected enclosure and local application hoses pressure tested annually. Verify integrity of space not compromised by penetrations.

Carbon Dioxide Systems. Only contractors licensed by manufacturer should perform maintenance and testing. Inspectors should be familiar with inspecting:
- physical damage to components
- excessive corrosion
- change in hazard
- enclosure integrity
- up to date records for required tests, inspections, and maintenance.
Agent cylinders checked semiannually, hydrostatic testing every 5 years.

Foam Systems. NFPA 25. Specially trained personnel required to inspect, service, and test. Inspectors should:
- check concentrate tank for signs of sludge, damage, deterioration
- verify inspections performed, documented
- Semiannually check valves and alarms
- Annually check foam concentrates, foam equipment, and foam proportioning systems. verify qualitative tests performed on concentrate to certify no contamination

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Describe proper selection, distribution, inspection, and maintenance of portable fire extinguishers (597-602)

A
  • Nature of hazard to be protected (light, ordinary, extra)
  • Extinguisher size (based on hazard and max floor area)
  • Travel distance (based on hazard class)
  • Potential severity
  • Personnel available
  • Environmental conditions
  • Anticipated adverse chemical reactions between agent and burning material
  • Health and occupational safety concerns
  • Inspection and service required to maintain extinguishers (monthly inspections recommended)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Define the different fire hazard classifications (565)

A

Class A - combustible solids. Involves ordinary, solid, combustible materials such as wood, cloth, paper, rubber, and many plastics

Class B - flammable liquids. Involves flammable and combustible liquids and gases such as gasoline, oil, lacquer, paint, mineral spirits, and alcohol.

Class C - electrical. Involves energized electrical equipment where the electrical nonconductivity of the extinguishing agent is of major importance; materials involved are either Class A (wiring insulation) or Class B (lubricants), and they can be extinguished once the equipment is de-energized

Class D - combustible metals. Involves combustible metals such as aluminum, magnesium, potassium, sodium, titanium, and zirconium (particularly in their powdered forms). May require special extinguishing agents or techniques.

Class K - kitchens. Involves oils and greases normally found in commercial cooking kitchen and food prep facilities using deep fryers. Through a process known as SAPONIFICATION, extinguishing agents turn fats and oils into a soapy foam that extinguishes a fire.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When are dry-chemical extinguishing systems used? (565)

A

Whenever rapid fire extinguishment is required and where reignition of burning materials is unlikely.
- Flammable liquid storage rooms
- Dip tanks
- Paint spray booths
- Exhaust duct systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Name types of dry-chemical application methods (567)

A

Fixed System: agent storage tanks, expellant storage tanks, a heat-detection and activation system, piping, and nozzles.
- Local application
- Total Flooding

Handheld Hoseline: trained personnel apply dry chemical from hose stations connected to the agent and expellant storage containers. Fuel loading docks, aircraft hangars, outdoor aircraft parking areas, and flammable liquid storage rooms may require this method.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

List the components in a dry-chemical extinguishing system (568)

A

~Storage container for agent and/or expellant gas. Range from 30 to 100 lbs, up to 2000 lbs. Must be in area -40deg F to 120deg F.
~Piping to carry agent and gas
~Nozzles
~Actuating Mechanism, responds to activation of fire detection system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Identify the common agents used in dry powder systems (569-571)

A

Dry powder systems are designed to extinguish Class D fires involving combustible metals. The agent must be carefully chosen for the hazard metal being protected.

NA-X: UL listed sodium carbonate-based with additives to enhance flow. Sodium, potassium, and sodium-potassium alloy fires. NOT for use on magnesium. Forms encasing crust causing oxygen deficiency. Can be in a fixed system, hand from pails, or portable extinguishers.

MET-L-X: sodium chloride (salt) based with flow additive. Magnesium, sodium, and potassium fires. Forms crust on burning metal. Applied first from fire extinguisher to control and then slowly to bury the fuel. Stable when stored in sealed containers, nonabrasive, and no known toxic effects.

LITH-X: graphite based, Conducts heat away from fuel after layer is applied. Developed for Lithium, but can be used on magnesium, zirconium, and sodium fires. Does not form a crust.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Identify the common agents used in dry chemical systems (567-568)

A

Sodium bicarbonate: Class B and C fires and has some effect on Class A surface fires. Chemically treated to be water-repellent and free-flowing. Successfully used on textile machinery.

Potassium bicarbonate: Aka Purple-K. Class B and C fires. Can extinguish twice the size of fire per pound as sodium bicarbonate. Chemically treated to be water-repellent and free-flowing.

Monoammonium phosphate: Class A, B, C. Multipurpose Dry-Chemical. Quickly extinguishes flaming combustion and melts to smother ordinary combustible materials. Can be corrosive to metals including extinguishing system nozzles, piping, and agent containers.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Differentiate between dry-chemical systems and wet-chemical systems (571)

A

The primary difference is the type of agent used.

Dry-chemical systems are used where wet would be ineffective. They smother (remove oxygen) or remove heat.

Wet-chemical systems are most effective in commercial cooking applications that produce grease-laden vapors. The wet chemical reacts with the oils and forms a soapy foam. Extinguishes fire by fuel removal, cooling, smothering, and flame inhibition.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What components are included in a clean-agent fire extinguishing system? (574)

A

Actuation devices, agent storage containers, piping, and discharge nozzles.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Why are CO2 systems dangerous to personnel? (575)

A

CO2 is an asphyxiant eliminating breathable oxygen from the atmosphere. The systems deliver a concentration that is lethal to humans.

Not as dangerous in a local application system delivered directly onto the fire as opposed to flooding, especially if outdoors or in a large building.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

List the means of actuation for CO2 systems. (577)

A

Automatic operation: Initiated by a listed smoke or fire detection device. This triggers control valves on the CO2 supply.

Normal manual operation: Person manually operates a control device that puts system through cycle of operation including predischarge alarms.

Emergency manual operation: Used only when the other two modes fail. Causes system to discharge immediately without warning.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Explain how foam proportioners operate. (579-580, 583-584)

A

Foam proportioners introduce the correct amount of foam concentrate into a water stream which makes the foam solution before introduction of air. The nozzle or sprinkler aerates the solution into finished foam.

Balanced pressure proportioner: foam concentrate line connected to each fire pump discharge outlet or system riser. The foam pump provides pressure equal to the fire pump pressure. One of the most reliable methods. The same system can discharge foam and just water at the same time to different outlets.

Around-the-pump proportioner: Does not have a separate pump

Pressure proportioning tank system: Small amount of water goes into concentrate tank and releases foam by displacement

Couple water motor-pump proportioner:

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Describe the letter symbols and pictorial symbols used for the different classes of fire (587)

A

Class A: Green Triangle, Trash Can & Log Fire
Class B: Red Square, Gas Tank Fire
Class C: Blue Circle, Plug and Outlet Fire
Class D: Yellow Star, Partial Gear Fire
Class K: Black Hexagon, Cooking Pan Fire

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What should properly placed fire extinguishers exhibit? (592)

A
  • Visible and marked with legible signage
  • Not blocked by storage or equipment
  • Near points of egress or ingress
  • Near normal paths of travel
  • Placed in proper physical environment for extinguisher (correct height, in a cabinet/recessed to protect extinguisher and people, correct temperature)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What are the standard mounting heights for a fire extinguisher? (593)

A

~ 40lbs or less, top no more than 5’ above floor
~ >40lbs, top no more than 3-1/2’ above floor
~ Clearance between bottom and floor should not be less than 4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Describe the inspection requirements for dry-chemical systems (566)

A

~Review installation plans
~Review manufacturers’ specification sheets
~Inspect new installations
~Witness acceptance tests of those new installations
~Perform periodic inspections of existing systems

Dry-chemical (NFPA 17) & Wet-Chemical (NFPA 17A): Inspector shall evaluate the application methods, agents, components, and inspection and testing requirements. Dry storage containers <150 lbs must be hydrostatically tested every 12 years. A qualified individual/personnel must verify the system is maintained and serviced as required and have reviewed monthly:
- System parts in correct location
- Manual actuators unobstructed
- Tamper indicators and seals intact
- Maintenance tags in place, up to date
- Obvious damage noted
- Gauges within operational limits
- Equipment modifications/repairs noted

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What is included in an inspection of wet-chemical systems?

A

Dry-chemical (NFPA 17) & Wet-Chemical (NFPA 17A): Inspector shall evaluate the application methods, agents, components, and inspection and testing requirements. Dry storage containers <150 lbs must be hydrostatically tested every 12 years. A qualified individual/personnel must verify the system is maintained and serviced as required and have reviewed monthly:
- System parts in correct location
- Manual actuators unobstructed
- Tamper indicators and seals intact
- Maintenance tags in place, up to date
- Obvious damage noted
- Gauges within operational limits
- Equipment modifications/repairs noted

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

List some of the items an inspector should verify when inspecting clean-agent systems

A

Clean-Agent Systems (NFPA 2001 and NFPA 12A for Halon 1301). Annual inspections by qualified personnel required. Quantity and pressure checked semiannually. Records on tests and inspections must be maintained and available for inspector to review. Inspector must know agents used in systems, components, inspection and testing requirements. Storage containers must meet DOT and TC req’ts and be hydrostatically tested every 5 years. Protected enclosure and local application hoses pressure tested annually. Verify integrity of space not compromised by penetrations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What should inspectors look for when inspecting CO2 systems?

A

Carbon Dioxide Systems. Only contractors licensed by manufacturer should perform maintenance and testing. Inspectors should be familiar with inspecting:
- physical damage to components
- excessive corrosion
- change in hazard
- enclosure integrity
- up to date records for required tests, inspections, and maintenance.
Agent cylinders checked semiannually, hydrostatic testing every 5 years.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What items do inspectors need to verify when inspecting foam fire suppression systems?

A

Foam Systems. NFPA 25. Specially trained personnel required to inspect, service, and test. Inspectors should:
- check concentrate tank for signs of sludge, damage, deterioration
- verify inspections performed, documented
- Semiannually check valves and alarms
- Annually check foam concentrates, foam equipment, and foam proportioning systems. verify qualitative tests performed on concentrate to certify no contamination

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What are the main factors that influence the proper distribution of portable fire extinguishers? (597)

A
  • Nature of hazard to be protected (light, ordinary, extra)
  • Extinguisher size
  • Travel distance
  • Potential severity
  • Personnel available
  • Environmental conditions
  • Anticipated adverse chemical reactions between agent and burning material
  • Health and occupational safety concerns
  • Inspection and service required to maintain extinguishers
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

What should an inspector look for when inspecting portable fire extinguishers? (601-602)

A
  • Proper location, visible, accessible
  • Not obstructed
  • Suitable for hazard being protected
  • Check inspection tag to see if maintenance is due
  • Examine nozzle or horn for obstructions
  • Verify lock pins or tamper seals intact
  • Signs of physical damage
  • Fully charged with expellant and agent
  • Proper operating pressure on gauge
  • Check collar tag for current info and/or damage
  • Required signage in place
  • Legible operating instructions
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

Special-agent fire extinguishing systems are classified by the: (565)
A. type of occupancy.
B. type of fire they will extinguish.
C. type of agent used in the system.
D. amount of time it takes to expel the agent.

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

What type of special-agent fire extinguishing system is used when rapid fire extinguishment is required and where reignition is unlikely? (565)
A. Dry powder systems
B. Clean agent systems
C. Dry-chemical systems
D. Wet-chemical systems

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

What type of special-agent fire extinguishing system is used for combustible metal fires? (571)
A. Dry powder systems
B. Foam agent systems
C. Dry-chemical systems
D. Carbon dioxide systems

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

Which special-agent fire extinguishing system is most effective on fires in commercial cooking equipment that produces grease-laden vapors? (572)
A. Dry powder systems
B. Clean agent systems
C. Dry-chemical systems
D. Wet-chemical systems

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

What general category of fire extinguishing agents effectively leaves no residue? (574)
A. Dry powder systems
B. Clean agent systems
C. Dry-chemical systems
D. Carbon dioxide systems

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

Which special-agent fire extinguishing system is extremely cold and can freeze exposed skin? (577)
A. Dry powder systems
B. Clean agent systems
C. Dry-chemical systems
D. Carbon dioxide systems

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

Which system is used when water alone may not be an effective fire extinguishing agent? (580)
A. Foam system
B. Dry powder system
C. Dry-chemical system
D. Carbon dioxide system

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

The value of a fire extinguisher lies in: (584)
A. how big it is.
B. its ease of use.
C. where it is located.
D. the speed with which it can be used.

A

D

33
Q

Portable fire extinguishers are classified by the: (585)
A. type of fire they will extinguish.
B. type of agent used in the system.
C. amount of time it takes to expel the agent.
D. type of occupancy in which they are located.

A

A

34
Q

How are portable fire extinguishers rated? (585)
A. Type of occupancy and intended use
B. Intended use and type of agent used
C. Intended use and extinguishing capability
D. Type of agent used and location in an occupancy

A

C

35
Q

Which aspect of fire protection with portable fire extinguishers is essential, but often overlooked? (592)
A. Size
B. Training
C. Extinguisher capability
D. Extinguisher placement

A

D

36
Q

What is required for a special-agent extinguishing system to be considered successful? (564)
A. The cost of maintenance
B. Ease of use by occupant/owners
C. It must completely extinguish the fire
D. It controls or contains a fire until the fire department arrives

A

C

37
Q

Which class of fire involves energized electrical equipment? (565)
A. Class A
B. Class B
C. Class C
D. Class D

A

C

38
Q

Which of the following tasks regarding dry-chemical systems is an Inspector I MOST likely to be required to perform? (566)
A. Inspect new installations
B. Conduct acceptance tests
C. Evaluate application methods
D. Evaluate inspection and testing requirements

A

A

39
Q

Which type of dry-chemical fixed application method introduces a concentration of agent into a closed area? (566)
A. Total flooding
B. Local application
C. Fire extinguishers
D. Handheld hoseline

A

A

40
Q

What is the biggest disadvantage to dry-chemical systems? (567)
A. Cost
B. Difficult to find
C. Complicated to use
D. Require extensive cleanup

A

D

41
Q

Which dry-chemical agent is also known as ordinary dry chemical? (567)
A. Sodium carbonate
B. Sodium bicarbonate
C. Potassium bicarbonate
D. Monoammonium phosphate

A

B

42
Q

Which dry-chemical system component may contain both the agent and the pressurized expellant gas? (568)
A. Nozzles
B. Hydrants
C. Storage container
D. Actuating mechanism

A

C

43
Q

Which dry-chemical system component releases agent into the piping system? (568)
A. Nozzles
B. Hydrants
C. Storage container
D. Actuating mechanism

A

D

44
Q

Which type of dry powder agent is sodium chloride (salt) based? (571)
A. Halon
B. NA-X®
C. LITH-X®
D. MET-L-X®

A

D

45
Q

Wet-chemical fire extinguishing agents are delivered to the hazard area in the form of a: (572)
A. drip.
B. foam.
C. spray.
D. stream.

A

C

46
Q

Which type of clean system agent is no longer produced but may still be in service? (573)
A. Halon
B. NA-X®
C. LITH-X®
D. MET-L-X®

A

A

47
Q

What is critical to total flooding applications of carbon dioxide (CO2) systems in order for them to be effective? (576)
A. Room integrity
B. Predischarge alarms
C. Cost of maintenance
D. Proper training in use

A

A

48
Q

Which type of foam system method extinguishes a fire by intervening between the fuel and the fire? (578)
A. Cooling
B. Separating
C. Smothering
D. Suppressing

A

B

49
Q

Which type of foam fire extinguishing system is wheel mounted and may have a water supply connection capability? (579)
A. Fixed
B. Mobile
C. Portable
D. Semifixed

A

B

50
Q

The four elements necessary to produce high-quality fire fighting foam include foam concentrate, water, mechanical agitation, and: (580)
A. air.
B. gas.
C. halon.
D. carbon dioxide (CO2).

A

A

51
Q

The stage of foam formation that mixes water with foam liquid concentrate is: (580)
A. aeration.
B. blending.
C. separating.
D. proportioning.

A

D

52
Q

What percentage of finished foam is water? (580)
A. 1% to 5%
B. 45½% to 50%
C. 94% to 99½%
D. 100%

A

C

53
Q

Which foam expansion rate is used primarily to extinguish fires involving liquid fuels? (581)
A. Trace
B. Low
C. Medium
D. High

A

B

54
Q

Which foam expansion rate is useful as a space-filling agent? (582)
A. Trace
B. Low
C. Medium
D. High

A

D

55
Q

Which foam proportioner is one of the most reliable methods of foam proportioning? (583)
A. Around-the-pump proportioner
B. Balanced pressure proportioner
C. Pressure proportioning tank system
D. Coupled water motor-pump proportioner

A

B

56
Q

Which foam proportioner is the most common type of built-in proportioner installed in mobile fire apparatus? (583)
A. Around-the-pump proportioner
B. Balanced pressure proportioner
C. Pressure proportioning tank system
D. Coupled water motor-pump proportioner

A

A

57
Q

Which foam proportioner allows for automatic proportioning over a wide range of flows and pressures and does not depend on an external power source? (584)
A. Around-the-pump proportioner
B. Balanced pressure proportioner
C. Pressure proportioning tank system
D. Coupled water motor-pump proportioner

A

C

58
Q

Which fire extinguisher agent is subject to freezing if not kept in a heated area or an antifreeze agent added? (586)
A. Foam
B. Water
C. Dry chemical
D. Carbon dioxide (CO2)

A

B

59
Q

Which fire extinguisher agent extinguishes primarily through a smothering action? (587)
A. Foam
B. Water
C. Dry chemical
D. Carbon dioxide (CO2)

A

D

60
Q

Which fire extinguisher agent is especially suitable for controlling fires outdoors? (589)
A. Foam
B. Water
C. Dry chemical
D. Carbon dioxide (CO2)

A

C

61
Q

Which type of fire extinguisher stores expellant gas and extinguishing agent in a single chamber? (590)
A. Loaded-stream extinguisher
B. Pump-operated extinguisher
C. Stored-pressure extinguisher
D. Cartridge-operated extinguisher

A

C

62
Q

Clearance between the bottom of the extinguisher and the floor should never be less than: (593)
A. 3 inches (76 mm).
B. 4 inches (100 mm).
C. 5 inches (127 mm).
D. 6 inches (152 mm).

A

B

63
Q

What is the greatest concern for extinguisher reliability? (593)
A. Placement
B. Distribution of units
C. Type of agent used in units
D. Temperature of the environment

A

D

64
Q

Who is responsible for verifying to the inspector that dry-chemical systems are maintained and serviced? (594)
A. Fire marshal
B. Owner/occupant
C. Building manager
D. Qualified individual

A

D

65
Q

How often are dry-chemical agent storage containers less than 150 pounds (75 kg) required to be hydrostatically tested? (595)
A. Every 5 years
B. Every 7 years
C. Every 12 years
D. Every 14 years

A

C

66
Q

In a clean-agent system, the quantity and pressure of the clean agent must be checked: (596)
A. every 3 months.
B. every 4 months.
C. semiannually.
D. annually.

A

C

67
Q

How often do all components of clean-agent systems need to be inspected by qualified personnel? (596)
A. Weekly
B. Monthly
C. Quarterly
D. Annually

A

D

68
Q

What kind of test is required every five years for clean-agent storage containers? (596)
A. Pressure
B. Acceptance
C. Hydrostatic
D. Requirement

A

C

69
Q

In addition to the clean-agent system inspections and tests, what else must be inspected annually? (596)
A. Wall mounts
B. Personnel records
C. Protected enclosure
D. Ventilation equipment

A

C

70
Q

Who should perform maintenance and testing on CO2 extinguishing systems? (596)
A. Fire Inspector I
B. Fire Inspector II
C. Licensed representatives of the owner/occupant
D. Licensed representatives of the system manufacturer

A

D

71
Q

How often should CO2 agent cylinders be checked and changed if necessary? (596)
A. Weekly
B. Monthly
C. Semiannually
D. Annually

A

C

72
Q

How often should valves and alarms attached to foam systems be checked? (597)
A. Weekly
B. Monthly
C. Semiannually
D. Annually

A

C

73
Q

Foam concentrates, foam equipment, and foam proportioning systems should be checked: (597)
A. weekly.
B. monthly.
C. semiannually.
D. annually.

A

D

74
Q

The general method for locating and distributing extinguishers consists of: (597)
A. analyzing the cost.
B. the size of the occupancy.
C. the training level of the occupants.
D. classifying occupancies based on hazard levels.

A

D

75
Q

What is the most important factor in determining the distribution of Class B extinguishers? (599)
A. Travel distance to the hazard
B. Training level of the occupants
C. Maximum floor area to be protected
D. Occupancy classifications based on hazard levels

A

A

76
Q

When it comes to fire extinguishers, inspectors are responsible for: (600)
A. training occupants in their use.
B. hiring consultants to provide training.
C. training occupants on maintenance and inspection.
D. providing information and recommendations for training.

A

D

77
Q

NFPA® 10 recommends portable fire extinguishers be inspected: (600)
A. weekly.
B. monthly.
C. semiannually.
D. annually.

A

B

78
Q

Who is responsible for keeping accurate records of fire extinguisher inspections? (601)
A. Fire marshal
B. Owner/occupant
C. Building manager
D. Qualified individual

A

B