Fire Detection and Alarm Systems Flashcards
What is the basic function of the fire alarm control unit (FACU)
Basic Function: Serves as the brain for the alarm system.
More specifically: It supervises and monitors the integrity of wiring and components of the fire alarm system. Receives signals from alarm-initiating devices, processes signals, produces output signals that activate audible and visual appliances, and transmits signals to an off-site monitoring station when provided.
May also: provide two-way firefighter communication; remove annunciator integration; control elevators, HVAC, fire doors, dampers, locks; pressurize stairwells; operate smoke control systems; activate special fire suppression systems.
List types of notification appliances
Audible
Visual
Textural
Tactile
Name types of alarm-signaling systems
Protected Premises Systems including:
~ Conventional Alarm Systems
~ Zoned Conventional Alarm Systems
~ Addressable Alarm Systems
Supervising Station Alarm Systems including:
~ Central Station System
~ Proprietary System
~ Remote Receiving System
Public Emergency Alarm Reporting Systems
Emergency Communications Systems
~ Voice notification systems
~ Two-way Communication Systems
~ Mass Notification Systems
What are the placement requirements for manual pull boxes?
Per NFPA 72, shall be mounted on walls or columns with operable parts between 42” - 48” above the floor. Plain sight, unobstructed. At least one station on each floor. Maximum travel distance 200 feet.
Name some of the general inspection considerations for a fire inspector
Inspector should:
o Note the function aspect of the fire detection and alarm system
o Recognize physical and environmental conditions that may negatively affect system operation or render the system inoperable
o Recognize conditions that may trigger an unwanted alarm and recommend corrective action to reduce/eliminate possible nuisance alarms
Inspection considerations:
o Check for changes to building or use of rooms
o Verify all equipment, especially initiating and signaling devices, are free from dust, dirt, paint, and other foreign material
o Verify manual pull stations, audible or visual warning devices and any other components are not blocked or obstructed in any way.
o Verify that the monitoring system is operational.
What should an inspector witness during an acceptance test?
- Inspection of all wiring for proper support
- Looking for wear, damage or any other defects that may render the insulation ineffective.
- Inspect conduit for solid connections and proper support
- Check backup batteries for clean connections and proper charge.
List inspection requirements for different types of occupant notification devices.
Audible Notification
* A method for providing occupant notification of fire.
* NFPA requires these to be 15 decibels above the average or normal sound level or 5 decibels above the maximum sound level that last for 1 minute in the occupancy.
* Do not exceed 120 decibels
* If the ambient sound in a building is above 105 dB the building must have visual notification.
* Noise levels are taken 5 ft. from the floor, except in sleeping areas where they are taken at pillow level.
Visual Notification
* ADA requires these in any portion of new or renovated construction accessible to a hearing impaired person.
* Installed in two locations: wall mount or ceiling mount
* Where required, these must be installed in corridors that are less than 20 ft. wide. Any wider and room spacing requirements are applied.
* Must be mounted 15 feet from the end of the corridor and must not be spaced more than 100 ft. on center.
* Any interruptions in a hallway, like a fire door, requires to each area to be viewed as separate.
* When two or more strobes are in the field of vision, the strobes must be synchronized to flash at the same time.
List fire alarm system components.
Fire Alarm Control Unit (FACU)
Primary Power Supply
Secondary Power Supply
Initiating Devices
Notification Appliances
Explain Fixed-Temperature Heat Detectors including types
Fixed Temperature Heat Detectors are relatively inexpensive, least prone to nuisance alarms and must be properly placed where heat is expected to accumulate.
Includes Frangible Bulb, Fusible Link, Bimetallic Heat Detector, and Continuous Line Heat Detectors.
Explain Rate-of-Rise Heat Detectors including types
Rate-of-Rise Heat Detectors respond at a lower temperature, reliable but can be activated under non-fire conditions. Includes Pneumatic Rate-of-Rise Line Heat Detector (large areas), Pneumatic Rate-of-Rise Spot Heat Detector (self contained unit), Rate-Compensation Heat Detector (areas subject to regular temperature changes), and Electronic Spot-Type Heat Detector (thermistors).
Explain Smoke Detectors and types of Smoke Detectors
Smoke Detectors, preferred for residences and health and institutional facilities. Sense presence of fire more quickly than heat-detection. Includes Photoelectric Smoke Detectors (good for smoldering fire detection), Ionization Smoke Detectors (good for rooms with highly combustible materials), Duct Smoke Detectors, and Video-Based Detectors.
Explain Flame Detectors and Types
Sometimes called a light detector. Three types:
Ultraviolet
Infrared (good for large areas)
Combination UV and IR
List main types of automatic alarm-initiating devices
Fixed-Temperature Heat Detectors
Rate-of-Rise Heat Detectors
Smoke Detectors
Flame Detectors
Sprinkler Waterflow Alarm-Initiating Devices
Manually Actuated Alarm-Initiating Devices
Explain types of signals from a fire detection and alarm system
Alarm Signal: fire condition detected
Supervisory Signal: monitored condition in system is off-normal. Problem with an accessory to the system.
Trouble Signal: Power system failure or other system malfunction such as removal of an initiating device like a smoke detector. Problem with the fire detection and alarm system.
Explain types of alarm-signaling systems
Protected Premises Systems including:
~ Conventional Alarm Systems (cannot identify initiating device location)
~ Zoned Conventional Alarm Systems (identifies zone of alarm activation)
~ Addressable Alarm Systems (identifies specific device activated)
Supervising Station Alarm Systems including:
~ Central Station System (independent listed business, most reliable)
~ Proprietary System (same ownership as building)
~ Remote Receiving System (not listed, operates as a business)
Public Emergency Alarm Reporting Systems (connects property with fire department alarm and communications center)
Emergency Communications Systems (supplementary system)
~ Voice notification systems (one-way for occupant notification)
~ Two-way Communication Systems (firefighter communication)
~ Mass Notification Systems (large number of people on widescale basis)
Describe manual alarm-initiating devices
Pull Stations
~ single action
~ double action
May be protected by a listed cover in areas subject to damage or accidental activation
May have to break glass with small mallet, not recommended
May use dye or residue to deter malicious false alarms
Describe service testing and inspection methods for fire detection and alarm systems
Describe inspection and testing methods for suppression system equipment
Explain methods to evaluate fire detection and suppression system equipment for life safety, property conservation and hazards.
Which fire alarm component serves as the brain of alarm systems? (608)
A. Initiating device
B. Notification appliance
C. Fire alarm control unit (FACU)
D. Secondary power supply (SPS)
C
How many types of specialty signals are most fire detection and alarm systems equipped with? (613)
A. 1
B. 2
C. 3
D. 4
C
The type of fire detection and alarm system required depends upon the: (614)
A. age of the building.
B. budget of the owner/resident.
C. type of occupancy of the building.
D. location of nearest fire department.
C
What are automatic alarm-initiating devices more commonly known as? (623)
A. Alarms
B. Initiators
C. Detectors
D. Activators
C
Which type of fire detection systems are among the oldest still in service? (624)
A. Heat detection devices
B. Flame detection devices
C. Smoke detection devices
D. Combination detection devices
A
Manual pull stations are usually ____ in color with white lettering that specifies what they are and how they are to be used. (635)
A. red
B. blue
C. black
D. green
A
Periodic testing of fire detection and alarm signaling systems is referred to as: (637)
A. signal testing.
B. a service test.
C. readiness testing.
D. an acceptance test.
B
Most of the time, who has to test fire alarm systems on their own and document results? (638)
A. Occupants
B. Fire inspectors
C. Third-party experts
D. Building contractors
A