When is panic hardware required on an exit door? (253)
When 50 or more people are in a room or occupancy
What is the minimum clear width for a door serving as a component of a means of egress? (251-252)
32” clear unobstructed width
How much of an exit access corridor may a door swing into and obstruct? (253)
No more than half of the corridor width
What is the maximum force that may be applied to release the latch on panic hardware? (254)
15 lbs
What is the maximum force that may be applied to set a door in motion after unlatching the panic hardware? (254)
30 lbs
What is the minimum required width for a stairway serving as part of the means of egress? (258)
44” for 50 or more people.
36” for less than 50 people.
What is the minimum width and maximum slope for a ramp that is part of the means of egress? When is a landing required? (260)
44” wide minimum with a maximum slope of 1:12. A landing is required every 30 feet in length.
What is the minimum required distance between two required exits? (271)
No less than one half the length of the overall diagonal dimension of the room or building area.
If more than two exits are required, at least two shall meet this rule, and the additional exits should be located so that they are available if the primary exits are blocked or unavailable.
In most cases, how many exits are required from a balcony, mezzanine, story based on occupant load? (270)
Two (2) exits with an occupant load of 500 or less.
Three (3) for occupant load >500 and <1,000.
Four (4) for occupant load 1,000 or greater
What is a dead end corridor? (272)
A corridor with no outlet to a means of egress and is more than 20 feet in length.
What are the three elements of a means of egress? (242)
Exit Access
Exit
Exit Discharge
Fire lanes must extend to within _______ feet of all portions of a building (unless otherwise required by local codes). (286)
150
What is the minimum required width of a fire lane and fire apparatus road? (286)
20 feet
What is the minimum required vertical clearance over a fire lane or fire apparatus road? (286)
13 ft 6 in
When is a turnaround required for a fire lane or fire apparatus access road? (288)
When it extends further than 150 feet from a public street or road.