What is the capacity of each Spray Pond Filter?
600 gpm
What are the Spray Pond Pumps rated for?
16300 gpm
What directs the use of DS or TB as makeup water?
Chemistry Control Instruction
What system provides hypochlorite to the SP system?
Chlorine Injection system (CI)
What would a loss of Instrument Air have on the SP system?
Level indication will have to be obtained locally at the Spray Ponds
What type of filter is the Spray Pond Filter?
Gravity type sand filters
What is the purpose of the Spray Pond Chemical Addition system?
To maintain our Ultimate Heat Sink chemistry within specified parameters in order to optimize the heat transfer surfaces of the DG coolers and the EW heat exchangers
What sort of electrical protection do I have for the Spray Pond Filter pump?
Overcurrent
What is the normal position of the Spray Pond Crosstie valves? Why?
Normally locked closed to ensure the two ponds remain independent of each other
What effect would a loss of Spray Pond system have on the operation of the plant?
If one or both trains becomes inoperable, plant shutdown would be required
If the associated DG is running, it would overheat so it would need to be shutdown
Impacts the operation of the Shutdown Cooling system, so actions are required to restore core cooling
If there is a LOCA and makeup is lost to the Spray Ponds, what two actions must be taken and how long do I have to complete them?
If two trains of shutdown cooling are in service, then one train must be shutdown
At least one of the spray ponds crosstie valves must be open
24 hours
Which SP pump does not require being primed prior to starting the pump?
Unit 3 B pump
What other motive force component must be in operation for the SP Chemical addition pumps to operate?
recirculation pump
What is the capacity of the acid chemical storage tank? What is the capacity of the acid injection pumps?
2500 gallons
6 gph
What electrical protection is provided for the SP Backwash Sump Pump?
Overcurrent
How many spray headers are provided in each pond?
Four
What seismic category does the Spray Pond fall under?
Category 1
Describe the flowpath for hypochlorite addition to the Spray Ponds
From WRF, hypo transports via a hypo header external to the protected area. Egress through the fence to the individual units and then to the spray pond distribution system
What is the only chemical that can be added in conjunction with any other chemical?
sulfuric acid
Of the three automatic air hypo injection valves, which one can be used in manual?
.25 gpm Hypo valve
What is the purpose of the SP Corrosion Test Racks?
Installed to monitor the corrosive effect of the Spray Pond water on piping and heat exchanger
When would the SP Backwash Sump Pump auto start?
With local control switch in AUTO, they will automatically start upon a receipt of a backwash sump high level signal and automatically stop upon receipt of a low level signal.
When a Spray Pond pump starts, what else starts with it? Why?
Spray Pond pump house Exhaust Fan to ensure pump operability