CP- Containment hydrogen purge Flashcards

1
Q

In both of the containment purge subsystems, what happens when the exhaust rad monitors sense high radiation levels? The external rad monitors?

A

alarm

system isolates

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will stop a containment purge besides RU-37 and Ru-38 detecting radiation?

A

CIAS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How is the CP system affected by a loss of Non-Class 125 VDC?

A

Containment Refueling Purge AHU outlet dampers fail closed which will prevent operation of the AHU

Containment Power Access Purge AHU inlet damper fails closed which prevents operation of the AHU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does the containment purge refueling purge subsystem AHU consist of?

A

filter, heating and cooling coils two fans

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Concerning the Power Access Purge Normal Exhaust AFU, what is the purpose of the charcoal filter and second HEPA filter?

A

Charcoal filter removes fission product gases (mainly iodine) by adsorption
Second HEPA filter removes any carbon dust emitted from the charcoal filters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the flow path of the Containment Purge refueling purge subsystem?

A

outside air is drawn in through a single AHU with two fans. sends air through dampers and isolation valves to containment

two exhaust fans drawn air out of containment through dampers to the plant vent

some of the exhaust air flow goes through rad monitors with two external rad monitors as well

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does the containment purge power access purge exhaust AFU consist of? Where is it controlled from? Where is it located?

A

moderate, HEPA, charcoal, and HEPA filters and a fan

control room

aux. building roof

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where is the Power Access Purge Supply AHU controlled from? Where is it located?

A

Control Room

aux. building roof

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does the containment purge power access purge AHU consist of?

A

inlet damper, moderate and high efficiency filters, coils, fan and exhaust damper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which radiation monitors continuously monitor Purge discharge flow to the plant vent?

A

RU-37 and RU-38

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where does the containment purge system purge the containment atmosphere to? Where does the filtered and treated make-up come from?

A

plant vent stack

outside air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the flow path of the containment purge power access purge subsystem?

A

outside air drawn in to a single AHU to containment

containment atmosphere is exhausted through isolation valves, heater and into exhaust AFU and then to the plant vent with rad monitors internal and external

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How many containment purge refueling purge exhaust fans are normally running while the system is in operation?

A

two, keeping containment at a slight negative pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens if monitors RU-37 and RU-38 detect excessive radiation?

A

Initiate a CPIAS and stop the purge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The Power Access Purge has what two modes?

A

Venting or depressurization mode

Power Access Purge mode

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the two subsystems of the CP system? Purposes?

A

Refueling Purge Subsystem – provides ventilation air for personnel comfort when the plant is shutdown during refueling operations and maintenance

Power Access Purge Subsystem – provides ventilation air to allow operator access for limited periods during power operation. Also used to control pressure in the containment by periodically venting a portion of the containment air to the plant vent

17
Q

How is the system affected by a loss of IA?

A

Air operated dampers and valves fail closed, which will cause associated AHUs, AFU, supply or exhaust fans to trip

18
Q

When does the WC system provide cooling to the Power Access Purge AHU?

A

When outside temperature is too high

19
Q

Why is there a heater installed up stream of the Power Access Purge Normal Exhaust AFU?

A

To maintain humidity low to prevent damage to the charcoal filter down stream

20
Q

What provides cooling in the Refuel Purge AHU and how is it controlled?

A

Normal Chilled Water

Automatically controlled to maintain inlet air temperature at a preset value

21
Q

How is the CP system affected by a loss of Class 120 VAC?

A

Causes the CP system to shutdown and isolate from the containment

Power is lost to RU-37 (A Train) or RU-38 (B Train), which are used to generate CPIAS

22
Q

Operating together as necessary for containment atmosphere clean-up is the Power access purge subsystem and what other system?

A

HC pre-access Normal AFUs

23
Q

How does Instrument Air interact with the CP system?

A

Provides air for the operation of dampers, valves, controllers, and air operated containment isolation valves in the CP system

24
Q

How does the Power Access Purge Supply AHU handle outside temperature being too low?

A

Electric heating coils are energized

25
Q

When would I use Venting mode?

A

Utilized to depressurize the containment atmosphere during normal power operation or prior to power access purge

26
Q

When is the Refueling Purge Supply AHU operated and where is it located?

A

Only in Mode 5 or 6

Located on the Aux Building roof