CP- Containment hydrogen purge Flashcards
In both of the containment purge subsystems, what happens when the exhaust rad monitors sense high radiation levels? The external rad monitors?
alarm
system isolates
What will stop a containment purge besides RU-37 and Ru-38 detecting radiation?
CIAS
How is the CP system affected by a loss of Non-Class 125 VDC?
Containment Refueling Purge AHU outlet dampers fail closed which will prevent operation of the AHU
Containment Power Access Purge AHU inlet damper fails closed which prevents operation of the AHU
What does the containment purge refueling purge subsystem AHU consist of?
filter, heating and cooling coils two fans
Concerning the Power Access Purge Normal Exhaust AFU, what is the purpose of the charcoal filter and second HEPA filter?
Charcoal filter removes fission product gases (mainly iodine) by adsorption
Second HEPA filter removes any carbon dust emitted from the charcoal filters
What is the flow path of the Containment Purge refueling purge subsystem?
outside air is drawn in through a single AHU with two fans. sends air through dampers and isolation valves to containment
two exhaust fans drawn air out of containment through dampers to the plant vent
some of the exhaust air flow goes through rad monitors with two external rad monitors as well
What does the containment purge power access purge exhaust AFU consist of? Where is it controlled from? Where is it located?
moderate, HEPA, charcoal, and HEPA filters and a fan
control room
aux. building roof
Where is the Power Access Purge Supply AHU controlled from? Where is it located?
Control Room
aux. building roof
What does the containment purge power access purge AHU consist of?
inlet damper, moderate and high efficiency filters, coils, fan and exhaust damper
Which radiation monitors continuously monitor Purge discharge flow to the plant vent?
RU-37 and RU-38
Where does the containment purge system purge the containment atmosphere to? Where does the filtered and treated make-up come from?
plant vent stack
outside air
What is the flow path of the containment purge power access purge subsystem?
outside air drawn in to a single AHU to containment
containment atmosphere is exhausted through isolation valves, heater and into exhaust AFU and then to the plant vent with rad monitors internal and external
How many containment purge refueling purge exhaust fans are normally running while the system is in operation?
two, keeping containment at a slight negative pressure
What happens if monitors RU-37 and RU-38 detect excessive radiation?
Initiate a CPIAS and stop the purge
The Power Access Purge has what two modes?
Venting or depressurization mode
Power Access Purge mode