To what level of radiation exposure does the HJ system limit personnel to during an event?
5 Rem
What rooms does the HJ AHU supply on the 120’ level?
Lower Cable Spreading Room
Inverter Room and Communication Equipment room
Corridor
When would the Battery Ventilation Essential Exhaust Fans be used? What trips them?
SIAS or LOP
high D/P
Why are there isolation dampers installed in the control building normal ventilation system?
it shares the ductwork with the control building essential units so the dampers isolate the normal and essential units from each other
How does HJ supports operations during a Station Blackout?
Provides environment to support equipment operation during the 16 hour coping period following a Station Blackout
What rooms does the HJ AHU supply on the 160’ level?
Upper Cable Spreading Room
Microwave Room
Lobby
During smoke removal in the control building, where is fresh air drawn in form?
outside air intake plenum
What rooms does the HJ AHU supply on the 100’ level?
Train A and B Switchgear Rooms
Class A, B, C, D battery rooms
Remote Shutdown Rooms
A LOP or SIAS signal will prevent smoke removal from what level?
100’
When would the Control Room Essential AHU be used? Where is it located?
Starts on a SIAS, CSAS, CRVIAS, CREFAS or LOP
74’ control building
What is the interlock associated with starting the Control Room Normal AHU?
Will not start unless both discharge dampers are open. A closure of either damper will trip the AHU
Where are the HJ Outside Air Normal AHU and Air washer pump located?
74’ level Control Building
What would cause the Control Room Normal AHU isolation dampers to close?
SIAS, LOP, CREFAS or CRVIAS
What system provides the makeup water for HJ Normal OSA AHU air washer? What provides the spray motive force?
Domestic Water
air washer pump
Why are the fire dampers in the class switchgear and battery rooms interlocked with the fire protection system?
if a CO2 discharge takes place, fire dampers are prevented from closing for 3.5 minutes to avoid over pressurization