What is the purpose of the Essential Chiller Compressor?
A two stage, centrifugal compressor that takes suction on the cooler shell, increases the refrigerant gas pressure, and discharges to the condenser
What powers the Essential Chilled Water pumps? Where are they located?
PH powered 20 hp electric motor
74’ control building next to essential chillers
When a chiller is shutdown, why do we have an electric heating coil energized in the oil sump?
To ensure proper oil viscosity and to prevent excessive Freon absorption
Concerning the Essential Chiller Cooler, what is installed above the tube bundle to provide balanced suction pressure throughout the cooler? What other function does it serve?
Flow equalizer plates
These plates also prevent liquid carry over into the compressor
In reference to the essential chillers, what is stacking and where does it occur?
occurs in the condenser
stacking is when the refrigerant accumulates in the condenser due to low differential pressure
How is the system affected by a loss of PB?
The compressor will have no power
What are the two paths for liquid refrigerant to get from the condenser to the flash economizer on the essential chiller?
flash gas chamber
high side float valve chamber
What is the normal source of makeup water to the Expansion tank? Backup? Emergency?
Normal: DW
Backup: CT
Emergency: FP
How is the Essential chiller compressor cooled and lubricated?
Refrigerant cooled and oil lubricated
Why are bypasses installed around the RHPCVs?
They ensure adequate condenser cooling flowrate during the most limiting postulated EW system condition of a 17% degraded EW pump while being currently aligned to fuel pool cooling loads
What is the capacity of the EC Expansion Tank? Where is it located?
80 gallons
74’ control building
What maintains the motor cooling flow?
D/P between the condenser and the cooler
When the chiller starts, what energizes to block a restart attempt?
A 20 min restart relay
How is the system affected by a loss of PH?
The chilled water circ. pump and lube oil pump will lose power
What feature of the Essential chiller compressor increases efficiency?
An inlet connection is provided between the first and second stages to allow single stage compression of refrigerant gas returning from the flash economizer. This means the flash gas only requires one stage of compression
In the Essential chiller condenser, the integrated thermal economizer consists of approximately how much of the condenser tubes?
12% of the condenser tubes
What is the back up make up water supply for EC?
CT
What are the basic flow paths of the two fluids flowing through the Essential Chiller Cooler?
Low pressure, liquid refrigerant on the shell side absorbs heat from chilled water flowing through the tubes as the refrigerant flashes to vapor
How is refrigerant flow controlled in the Essential Chiller Compressor?
By the inlet guide vanes installed in the suction. These vanes are controlled by the temperature of the chilled water leaving the chiller
What signals would automatically start the EC water system?
SIAS, CSAS, CREFAS, CRVIAS, LOP, AFAS 1 and 2
When would I start the chilled water pump independently of the chiller from the local push button on the supply MCC breaker?
Routinely done to perform chemical sampling of the chilled water
What is the purpose of the high side float valve chamber and low side float valve chamber in the essential chiller flash economizer?
high side- serves as a level controller for the condenser
low side-controlled by flash economizer level, allows refrigerant to enter the cooler and maintains the D/P between the economizer and the cooler
What is “stacking”?
The liquid refrigerant remains in the condenser since there is not enough condenser refrigerant gas pressure to drive the liquid through the flash economizer to the cooler
How is EC affected by the loss of the SP system?
chillers will trip on condenser high refrigerant pressure
How long after the chilled water pump starts will the oil pump energize?
23 seconds
What system serves as the essential standby power source for the EC system?
DG system
How much Nitrogen is charged into the EC Expansion Tank? What is the basis for that number? What is the minimum pressure in the system to prevent flashing at the highest point in the system?
> 25 psig
Added to keep oxygen out
10 psig with pumps not in service
We maintain it at this pressure since the tank is lower (elevation of surge tank relative to motive force elevation) than most surge tanks, so the additional pressure helps to maintain that surge volume throughout the rest of the system
The chilled water supplied to the AHUs and ACUs will cool what spaces?
Control Room Essential ventilation
DC equipment Room Essential Cooling
Electrical Penetration Room cooling
HPSI Pump Room cooling
CS Pump Room cooling
LPSI Pump Room cooling
ESF switchgear and equipment room cooling
AFP Room cooling
Essential Cooling
Water Pump room cooling
For how long after a seismic event can the CST feed make up water to the EC expansion tank?
24 hours
Where are the Essential Chilled Water pumps operated from?
Control switch in the Control room, and locally at the breaker