Provisioning Plant Flashcards
State the components (and their qty) of the provisioning plant system. State what type of cooling system the provisioning plant system is.
2x Cool Rooms (PORT and STBD)
1x Cold Room
2x Provisional Plant Compressors
Direct Cooling System
What should personnel do should they be stuck in the cold room?
Press the red safety button in the cold room to activate alarms outside the galley
State the standard defrosting time setting, and describe the defrosting cycle.
6h cycle (5.5h normal operation, 0.5h defrosting)
The compressor stops and and the heaters in the cold room turn on. This will cause an alarm to sound at the SCMMS due to increasing cold room temperature.
State the 2 purposes of the defrosting cycle.
Prevents icing from forming on the cooling fins of evaporator and blocking the flow of cold air, causing food to spoil faster.
Prevents ice from forming on the coaming of the cold room door, jamming it and trapping operators in the room.
State the 4 heaters installed in the cold room.
Door Heater: Melts ice on the door frame to prevent the door from jamming when excessive amounts of ice form
Defrost Heater: Melts ice on evaporator tubing to prevent restricted air flow
Pan heater: Due to the low temperatures in the cold room, condensation occurs very easily and water is collected in a pan. This heater prevents the water in the pan from freezing so it can flow off
Pipe heater: The pipe extends from the pan to outside the cold room. This heater prevents the water in the pipe from freezing so it can flow off.
State the 8 important valves for the provisional plant.
- Oil return v/v
- Oil p. Switch v/v
- Compressor inlet v/v
- Compressor outlet v/v
- Receiver inlet v/v
- Receiver outlet v/v
- Filter drier inlet v/v
- Filter drier outlet v/v
State the 7 side components of the provisional plant.
- Mufflers: Reduces the noise produced by the plant
- Oil Separator: Separates compressor L/O from Freon
- Receiver: A large space that can store Freon during pump down
- Filter Drier: Filters out contaminants and moisture from Freon
- Sight Glass: A window which allows operators to observe whether Freon is sufficient and/or contaminated
- Solenoid v/v: Controlled by the “Pump Down” switch. When the v/v is closed, pump down is initiated
- Accumulator: Stores any liquid Freon that may exist after the evaporator until it becomes gas, so that the compressor does not take in unwanted liquid Freon
State the changeover procedure from Provisional Plant 1 to Provisional Plant 2.
- Make sure the compressor is running. If it isn’t, open the cool/cold room door to force compressor to run.
- Switch Provisional 1 pump switch to “PUMP DOWN” In “Auto”, will cut out via the Low p.Switch after awhile
- Once Provisional 1 compressor stops, switch it to “MANU” and STOP”
- Open S/W inlet/outlet of condenser of Provisional Plant 2
- Close S/W inlet/outlet of condenser of Provisional Plant 1
- Close 8 v/vs of Provisional Plant 1
- Open 8 v/vs of Provisional Plant 2
- Check oil level and Freon level and ensure that both are > ¾
- Switch Provi 2 pump switch to “AUTO” and “RUN”
State the procedure to shutdown the entire provisional plant system in local mode.
- Pump down both units
- Close condenser suction and discharge valves
- Switch off cool and cold room fans
- STOP S/W cooling pump and OFF door heater
- Switch supply to OFF
State the 4 essential components to turn on/off to start/shutdown the provisioning refrigeration system completely
- Normal/Alternate (Power) Supply
- Door Heater
- S/W Cooling p/p
- Cool & Cold Room Fans
State the optimum operating parameters of the provisioning plant for Low Pressure, High Pressure, Oil Pressure, and S/W pump discharge pressure.
LP range: -20 ~ 15psig
HP range: 100 ~ 170psig
OP range: 4 ~ 11psig
S/W p: 1 ~ 2.5 bar
State the standard cut-in and cut-out parameters for LP range, HP trip and OP trip
- LP range: -20psig (cut-out), 15psig (cut-in)
- HP trip: >180psig
- OP trip <10psig
State the room temperatures of the cold room and cool room and their cooling medium.
Cold room: -14 – -18°C
Cool room: 2 – 6°C
Cooling medium: Seawater
State the 2 methods to perform emergency cooling for the condenser in case the S/W pump is down.
- Connect fire hose to provisional plant emergency cooling connection and spray water on provisional plant (found in AHU 20, next to provi plant)
- Open connecting v/v between the firemain and the provisional plant S/W cooling line (found in sewage compartment, below greywater panel, to provide S/W cooling from firemain line.)
State how the SCMMS alarm can activate when the condenser is on NORMAL. State how the compressor starts and stops when it is on AUTO.
On NORMAL, SCMMS alarm will activate when S/W p/p is down.
On AUTO, the compressor starts and stops based on the LPS.