What types of fires does the AFFF system fight?
Class A & B fires
How many foam pumps and tanks are in each foam pump room?
1 foam pump & 1 foam tank in each foam pump room.
What system needs to be activated before AFFF system can be activated? What is the % of foam in the AFFF mixture?
Fire Main & Sprinkler System
3%
State the pumping capacity, tank capacity, and delivering pressure of the foam pump. State how long an operation of releasing AFFF can last.
Pumping capacity: 18mᶟ/hr
Tank Capacity: 4460L each tank
Delivering pressure: 3 bar
Can last for 15 mins of operation
State the 5 locations of the AFFF release system.
- Tank deck zone
- Hangar/elevator room
- Flight deck Fwd/Aft
- Aviation fuel pump room
- Aviation fuel dispenser room
What’s the 4-step process to activating the AFFF system?
Step 1: Ensure presence of power supply
Step 2: Ensure all necessary valves are opened/closed
Step 3: Select mode of operation & start foam pump
Step 4: Open valve to selected coverage area