Can overhead wiring be located above a pool.
No.
Unless certain conditions are met, these are laid out well in appendix B.
How close to a pool may metal equipment be when not required to be bonded?
More than 1.5 m, or suitable separated by a fence.
What is the smallest size copper bonding conductor for equipment near a permanent in ground pool?
6 awg.
Must the rebar of a pool’s construction be bonded?
Yes, at a minimum of four points equally spaced.
Each deck box must have one bonding conductor going straight to ____________.
The Panelboard supplying the equipment associated with the deck box.
When can a junction box be immersed in water?
If approved for it, and only in decorative pools.
How many bonding connections must be provided for in a deck box?
3 on the inside and at least 1 #6 lug on the outside.
Can you use a deck box as a general raceway for conductors?
No, the only conductors within a deck box are for the supply of underwater equipment.
Where would you find a definition of a watertight enclosure?
Sec 22-102.
Must forming shells allow for the connection of threaded rigid conduit?
Yes, this helps make it watertight.
What is the maximum operating voltage of dry niche luminaires?
300V.
How far must the controls for a spa/hot tub/hydromassage bathtub?
At least 1 m or an integral part of the equipment.
What must commercial hut tubs have which is not required in residential units?
An emergency shut off switch, located within sight and no more than 15m away.
What is a leakage current collector?
A corrosion resistant pipe section which allows a bonded path for loose current in the water to flow. Bonded with a #6 awg conductor.
When is a leakage current collector not required?
When the only electrical equipment is identified as an insulated wet end pump.