Is section 28 supplemental?

A

Yes, it amends the general sections of the CEC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What kind of equipment typically requires low voltage protection?

A

Pinching cutting or crushing equipment;

Anything liable to create a hazard upon automatic startup.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If using a manual motor starter, what typically should it be rated in?

A

Horsepower rated.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Why must conductors terminating to a hot motor require a certain length?

A

So that the conductor can act as a heat sink down it’s length.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Under what circumstance may a motor’s supply conductors be sized on 90 º?

A

On a class A motor, when using 90 degree wire.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Why must each motor have a manual disconnecting means?

A

So that anyone doing service can ensure the power is cut off.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where can FLA estimates be found in the CEC?

A

Tables 44 (3Φ), 45 (1Φ) and D2 (DC).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When sizing conductors for a continuous motor, what multiplier must be used on the FLA for the largest motor?

A

1.25.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What table is used for sizing overcurrent devices for motors?

A

Table 29.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If a service factor is not marked, what is it’s assumed service factor multiplier?

A

1.15.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is a special rating, typically linked to hermetic refrigerant compressors?

A

Locked rotor current.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When using a part winding or a star delta starter, what must be done special for sizing the motor supply conductors?

A

There are six supply wires so the ampacity must be increased accordingly (0.8).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When sizing a wound rotor motor’s resistor wires, what temperature insulation must be used?

A

90 Degrees.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When sizing overcurrents for mutiple motors, what must be done?

A

Calculate OC for the largest motor, then add the FLAs of the rest;

If started simultanaeously, then treat all as one large motor, then use Table 29.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When sizing conductors for non continuous motors, what table must be used?

A

Table 27.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Which table gives insulation requirements for Class of motors?

A

Table 37.