LOT 202.21 Iso Phase Bus and Duct Cooling Flashcards
1
Q
- LOT 202.21 Isophase*
- *
What cools the Isophase HX?
A
CL-ACW
If lost, must open return damper and take temp logs every 30 mins
2
Q
- LOT 202.21 Isophase*
- *
What must be done if both fans on the Isophase are lost?
A
Reduce Power to 50%
Lower Isophase Current to 18,500 Amps
Lower load at 5%/min
Generator Current on CP007
Normal current rating is 36,600 Amps
Note:
Isophase trouble on CP010.