LOT 202.09 Steam Dumps Flashcards
- LOT 202.09 Steam Dumps*
- *
What causes the #3 solenoid to energize?
- Tavg Mode:*
- *C-9**
- Condenser Vacuum > 22” Hg AND CW breaker Shut [1/4]*
AND
- *C-7 OR C-8**
- C-7: 10% load reduction OR 5%/min*
- C-8: EH pressure 1245.8 psig [2/3] OR TVs closed [2/4]*
- Pressure Mode:*
- *C-9**
- Condenser Vacuum > 22” Hg AND CW breaker Shut [1/4]*
AND
Steam Header Pressure > Setpoint
If C-7 energizes #3 solenoid, must reset on CP007 to de-energize #3 solenoid.
- LOT 202.09 Steam Dumps*
- *
What is the stroke time of the steam dumps?
- Trip Open:*
- *3 seconds**
- Trip Closed:*
- *5 seconds**
- Modulate:*
- *20 seconds**
- LOT 202.09 Steam Dumps*
- *
Where do the steam dumps discharge steam?
Condensers
- Each bank consists of 3 steam dumps
- 1 dump/condenser
- LOT 202.09 Steam Dumps*
- *
What causes the #1 and #2 solenoids to de-energize?
P-12: Tavg < 563 ˚F [2/4]
Two redundant channels. One for each solenoid.
Can bypass P-12 for Bank #1 Steam Dumps by placing switches on CP007 to Bypass Interlock. (Spring returns to ON)
- Must take switch to OFF/RESET to secure C/D feature.
- LOT 202.09 Steam Dumps*
- *
What causes the #4 solenoid to energize?
Turbine Trip (C-8):
- *High 1: Tavg - Tref > 13 ˚F**
- Trips open steam dump banks 1 and 2*
- *High 2: Tavg - Tref > 26 ˚F**
- Trips open steam dump banks 3 and 4*
No Deadband
Load Rejection (C-7):
- *High 1: Tavg - Tref > 7.41 ˚F**
- Trips open steam dump banks 1 and 2*
- *High 2: Tavg - Tref > 11.81 ˚F**
- Trips open steam dump banks 3 and 4*
Setpoint changes based on chart
- *3 ˚F deadband at 592 ˚F Tavg**
- Allows Rods a chance to fix deviation*
Active in Tavg MODE only.
- Note:*
- Tavg driven off Auctioneered High Tavg
- Tref driven of PT-505
- LOT 202.09 Steam Dumps*
- *
How does the operator determine the correct setpoint for the Header Pressure Controller (PK-0557) on CP007?
Desired Pressure/Span of PI-557*10
1185 psig/1400 psig *10 = 8.46 turns
- LOT 202.09 Steam Dumps*
- *
What is the steam dump capacity?
40%
12 steam dumps (3.33%/Steam Dump)
Controls pressure/temperature following a 50% load reject (10% is covered by rods)
- LOT 202.09 Steam Dumps*
- *
When is steam pressure mode used?
Startup (< 15% power)
Shutdown
Cooldown
- LOT 202.09 Steam Dumps*
- *
How do the steam dumps and steam dump drain valves respond to a loss of power or air?
- Steam Dumps:*
- *Fail Shut**
- Steam Dump Drains:*
- *Fail Open**
- LOT 202.09 Steam Dumps*
- *
What does the Imp Selector switch do on CP007?
- Defeat PT-505:*
- *PT-506 used for C-5 interlock**
- Defeat PT-506:*
- *Nothing**
C-5: Turbine Impulse pressure < 15% [1/1]
- Stops AUTO outward rod motion.