IOI Flashcards
When does FWLC transfer to single element?
26% Rx power
When should FWLC to start-up level control?
3 mlbm/hr
62.2% core flow is how many mlbm/hr?
70 mlbm/hr
When is aux cooling tower put in service?
before 75%
When should all heater drain pumps be pumping forward, or ensure all condensate and condensate booster pumps are running?
approx 70%
What is max power with first stage and/or second stage MSR out of service?
95%
max power with one LPFWH string and 1 first stage reheater out of service?
90%
What’s the max power with 1 HDP out of service?
88%
What’s the max power with 2 HDP out of service?
79%
What is max power with 1 HPFWH out of service?
95%
What is max power with 1 LPFW heater out of service?
90%
What is max power with 1 LPFWH and 1 HPFWH out of service?
90%
What is rated steam flow and feed flow?
Steam – 18.97 mlbm/hr
FW – 18.94 mlbm/hr
What is rated core flow?
112.5 mlbm/hr
what is max tech spec steam dome pressure?
< 1045 psig
what is feedwater temp?
420 deg F
What is core thermal power?
<= 4408 MWt
What is the turbine roll-up ladder?
240 rpm - turning gear FE01 valve closes
400 rpm - vibrations
540 rpm - shaft-lift secures
800 rpm - TG standstill secures
1650 rpm - Aux oil pump secures
1800 rpm -- Tg test vent rps transmitters SO temps SCW temps Gen H2 Gen Auxilliaries PW Bypass valves
When should the offgas adsorbers be placed in treat?
936 psig
what should be done at 400 psig?
1 RFPT in service
additional condensate pump in service
When should second RWCU pump and filter be put in service?
> 200 psig