H1 LT2 Flashcards

1
Q

Why is it important to install a plastic meter cover over the meter socket?

A

Prevents shock hazard when energized

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What type of cable does the supply authority usually use?

A

Neutral-supported cable, type NS75

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What type of insulation is used for 10 AWG cable?

A

Polyethylene or XLPE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the consumer responsibilities in relation to an electrical service?

A

Installation of equipment and conductors between the service head and main switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where are underground supply conductors fed from?

A

Transformer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What does the CEC define grounding as?

A

Permanent and continuous conductive path to the earth.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What must be secured at the main service box to ensure bonding conductors are connected to the grounding conductor?

A

Bonding screw (or strap)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the two ways to manufacture a field-assembled grounding electrode?

A

Directly buried bare copper conductor or bare copper conductor encased in concrete footings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When using in-situ grounding electrodes, what is the requird depth for metallic reinforcement of concrete slab, concrete piling, or concrete foundation and iron pilings?

A

600 mm below finished grade

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What types of manufactured electrodes are there?

A

Concrete-encased plate electrode, plate electrode, rod electrode

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where should the grounding conductor be connected when an in-situ grounding electrode is used?

A

As close as possible to where the water pipe enters the building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which two items bond the grounded conductor bus to the metal enclosure of the service box?

A

Bonding jumper, bonding strap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How are the conductors in the neutral-supported cable type NS75 arranged?

A

Two insulated aluminum conductors wrapped around a bare steel-reinforced aluminum conductor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What can the neutral of 10 AWG cable be?

A

Bare or insulated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the minimum depth requirement for burying the duct in an underground supply?

A

900 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What does bonding mean according to the CEC?

A

Joining non-current-carrying metal parts to form a path.

17
Q

What is the minimum contact surface for a McGregor ground?

A

0.4 m

18
Q

What is required when running a feeder from one building to another?

A

Grounded service conductor must have its potential re-established

19
Q

What effect does corrosion have on electrodes?

A

Affects durability and life expectancy

20
Q

Where must the McGregor ground be encased?

A

Bottom 50 mm of concrete foundation footing

21
Q

What should be used for underground feeder conduits or cables?

A

Feeder’s bonding conductor

22
Q

What is the minimum size of copper bonding conductor required for AWG copper feeder conductors according to CEC?

A

10 AWG copper

23
Q

Considering an overhead service entrance, why is there a minimum clearance above grade necessary for the supply conductors?

A

To avoid accidental contact

24
Q

What is the purpose of a service mast?

A

Support supply conductors

25
Q

When must the mast be guyed?

A

When > 1.5 m above roof line