D2 - LT4 - CEC Section 12 Wiring Methods Flashcards

1
Q

What is the general rule for all underground installation depths?

Rule 12-012

A

minimum depths of cover are required

cover refers to the minimum distance between the top surface of the installation and the finished grade

Refer to Subrule(1) Table 53 to find minimum depths of cover

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What additional precautions are taken for underground installations?

Rule 12-012

A

Subrules (4) & (10)

require a bed of screened sand around the installation with clean backfill over top.

This ensures that large objects will not corrode or penetrate through the sand bed, damaging the installation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What happens if the minimum cover requirements cannot be reached?

Rule 12-012

A

Subrule (2)

permits a reduction of 150mm, provided a suitable form of mechanical protection is placed above the installation.

Subrule (3) lists the approved forms of protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does NMSC stand for?

A

Non-Metallic Sheathed Cable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What considerations are taken when selecting the correct conductor?

A
  • moisture
  • corrosive action
  • temperature
  • degree of enclosure
  • mechanical protection
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is NMSC?

A

an assembly of 2 or more insulated conductors having an outer sheath of non-metallic, moisture-resistant, flame-retardant, insulating material.

is available with 2, 3 or 4 current-carrying conductors ranging in size from #14 AWG through to #2 AWG

Has a voltage rating of 300V

2-wire NMSC contains a black, white, and bare (or green) conductor

3-wire NMSC contains a black, white, red, and bare (or green) conductor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
A
How well did you know this?