Gas - Valves and Regulators Flashcards
What do the lubricated gas shut-off valve and spring loaded gas shut-off valve have in common?
Both open and close with a quarter of a turn.
Servo-operated and redundant gas valves are both types of _________ gas valves.
Combination.
In a servo-operated valve, the force that opens the main valve is caused by:
A. A solenoid.
B. Gas pressure from a regulator.
C. The inlet gas pressure of the valve.
D. A spring[][][][][][][][][][][][][][][][][][][][][][][][][]
B. Gas pressure from a regulator.
In a redundant gas valve, the force that opens the main valve is caused by:
A. A solenoid.
B. Gas pressure from the regulator.
C. The inlet gas pressure of the valve.
D. A Spring[][][][][][][][][][][][][][][][][][][][][][][][][]
C. The inlet gas pressure of the valve.
If the main gas valve of a redundant gas valve failed open with debris when the call for heat is satisfied, the main flame would:
A. Go out.
B. Keep burning until the flame safeguard lost the pilot flame.
C. Keep burning indefinitely[][][][][][][][][][][][][][][][][][][][][][][][][][][][][][][]
A. Go out.
True or False?
Rod-and-tube type gas control valves are primarily used on service water heaters.
True.
True or False?
The invar rod expands more than the copper tube.
False.
True or False?
Hydraulically-operated valves use an expanding liquid inside a sensing bulb, capillary tube, and bellows.
True.
True or False?
Snap or clicker mechanisms are used to provide two positions of the valve, full open and completely closed.
True.
True or False?
ECO stands for energy cut-off.
True.
True or False?
A seismic valve once activated must be manually reset.
True.
True or False?
A cable release valve is always activated manually.
False.
Referring to the figure below, the letter “A” indicates which of the following?
A. Appliance shut-off valve.
B. “B” Cock[][][][][][][][][][][][][][]]
C. “B” Cock[][][][][][][][][][][][][][]]
D. Branch isolation valve[][]]
A. Appliance shut-off valve.
Referring to the figure below, the letter “C” indicates which of the following?
A. Appliance shut-off valve.
B. “A” Cock[][][][][][][][][][][][][][][]
C. “B” Cock[][][][][][][][][][][][][][]]
D. Branch isolation valve[][][]
C. “A” Cock.
Referring to the figure below, the letter “D” indicates which of the following?
A. Appliance shut-off valve.
B. “A” Cock[][][][][][][][][][][][][][][]
C. “B” Cock[][][][][][][][][][][][][][]]
D. Branch isolation valve[][]]
C. “B” Cock.
Referring to the figure below, the letter “B” indicates which of the following?
A. Appliance shut-off valve.
B. Pilot valve[][][][][][][][][][][][][]]
C. Safety shut-off valve[][][][]]
D. Branch isolation valve[][]]
C. Safety shut-off valve.
Referring to the figure below, the letter “E” indicates which of the following?
A. Appliance shut-off valve.
B. Appliance regulator[][][][][]
C. Automatic gas valve[][][][]]
D. Safety shut-off valve[][][][]]
B. Appliance regulator.
Referring to the figure below, when the reset button is depressed:
A. Only pilot gas can pass through the valve.
B. Only main gas can pass through the valve.
C. The igniter is energized and the main burner can light.
D. All the gas flow is interrupted until the thermocouple reaches temperature.
A. Only pilot gas can pass through the valve.
Referring to the figure below, a weak magnet will cause the valve to:
A. Fail in the open position.
B. Shut off the power to the thermocouple.
C. Close the reset button to block gas flow[]
D. Shut off all gas flow[][][][][][][][][][][][][][][][][][][][]
D. Shut off all gas flow.
Referring to the figure below, this valve can be mounted:
A. In any vertical or horizontal position.
B. Only in the horizontal upright position.
C. In any vertical position[][][][][][][][][][][][][][][]
D. In a horizontal position with a rotation of up to 90°
B. Only in the horizontal upright position.
Referring to the figure below, installing the valve backwards in the gas line could result in:
A. Gas leaking through the valve when it is not energized.
B. No gas flow when the valve is energized[][][][][][][][][][][][][]]
C. Gas pressure holding the valve closed and it will never open.
D. Continuous uninterrupted gas flow at all times[][][][][][][][][][][][][][]]
A. Gas leaking through the valve when it is not energized.
Referring to the figure below, this valve is known as:
A. Diaphram gas valve.
B. Servo gas valve[][][][]]
C. Redundant gas valve.
D. Solenoid valve[][][][][]]
D. Solenoid valve.
Referring to the figure below, this valve is known as:
A. Diaphram gas valve.
B. Servo gas valve[][][][]
C. Redundant gas valve.
D. Solenoid valve[][][][][][]
A. Diaphram gas valve.
Referring to the figure below, if the pressure port is plugged on installation of the valve:
A. The valve will never fully open.
B. The valve will never tightly close.
C. The valve will not accurately control manifold pressure.
D. The valve will respond very slowly to a call for heat[][][][]
B. The valve will never tightly close.
Referring to the figure below, if the vent line becomes completely plugged with carbon:
A. The valve will never open.
B. The valve will never close.
C. The valve will not accurately control manifold pressure.
D. The valve will respond very slowly to a call for heat[][][][]
A. The valve will never open.
Referring to the figure below, only during a call for heat (burner operating) it is noticed that there is a flare on the vent line. This could be due to:
A. Dirt under the main diaphram.
B. Pin holes in the main diaphram.
C. The armature has broken off[][][]
D. The armature spring has broken.
B. Pin holes in the main diaphram.
Referring to the figure below, only during the off cycle of the burner it is noticed that there is a flare on the vent line in the combustion chamber. This could be due to:
A. Dirt under the diaphram.
B. The armature spring has broken.
C. The armature has broken[][][][][][]]
D. Pin holes in the main diaphram[]]
B. The armature spring has broken.
Referring to the figure below, the letter “A” indicates the:
A. Safety shut-off valve magnet.
B. Main appliance shut-off valve.
C. “A” cock[][][][][][][][][][][][][][][][][][][][]]
D. Combination “A” cock and “B” cock.
C. “A” cock.
Referring to the figure below, the letter “B” indicates the:
A. Safety shut-off valve magnet.
B. Main appliance shut-off valve.
C. “A” cock[][][][][][][][][][][][][][][][][][][][]]
D. Appliance regulator[][][][][][][][][]
D. Appliance regulator.
Referring to the figure below, the letter “C” indicates the:
A. Safety shut-off valve magnet.
B. Main automatic valve actuator.
C. “A” cock[][][][][][][][][][][][][][][][][][][][][]
D. Combination “A” cock and “B” cock.
B. Main automatic valve actuator.
Referring to the figure below, the letter “D” indicates the:
A. Safety shut-off valve magnet.
B. Main appliance shut-off valve.
C. “A” cock[][][][][][][][][][][][][][][][][][][][][]]
D. Combination “A” and “B” cock[]
A. Safety shut-off valve magnet.
Referring to the figure below, this valve is know as:
A. Diaphram gas valve.
B. Servo gas valve[][][][]
C. Solenoid valve[][][][][]
D. Redundant gas valve.
B. Servo gas valve.
Referring to the figure below, what condition would result if the valve was installed backwards?
A. The valve would provide poor control of the pilot gas.
B. The valve would open when it was not energized[][][][]
C. The valve will not open to allow a flow of gas[][][][][][][][]
D. The main valve will not open and not close[][][][][][][][][][]
B. The valve would open when it was not energized.
Referring to the figure below, if the servo regulator diaphram ruptured, the most likely result would be:
A. When energized it will not regulate gas flow.
B. The valve will close and never open[][][][][][][][]
C. The valve will not energize[][][][][][][][][][][][][][][][]]
D. The valve will fail wide open[][][][][][][][][][][][][][][]
A. When energized it will not regulate gas flow.
Referring to the figure below, this valve is commonly known as:
A. Diaphram gas valve.
B. Solenoid valve[][][][][]
C. Servo valve[][][][][][][][]
D. Redundant valve[][][]]
D. Redundant valve.
Referring to the figure below, this valve regulates the pressure to:
A. Both pilot and main burner.
B. Main burner only[][][][][][][][][]]
C. Pilot only[][][][][][][][][][][][][][][][][]
D. Neither main burner nor pilot.
A. Both pilot and main burner.
Referring to the figure below, the first action on a call for heat is:
A. Gas flows to the pilot burner.
B. Pilot valve opens[][][][][][][][][][][]
C. Pilot operator is energized[][]]
D. Both main and pilot valve energize together.
C. Pilot operator is energized.
Referring to the figure below, the valve operation is caused by the:
A. Spring tension.
B. Expansion of the invar rod.
C. Expansion of the copper tube.
D. Inlet pressure of the gas[][][][][]]
C. Expansion of the copper tube.
Referring to the figure below, extreme corrosion of the copper tube may cause:
A. The valve to stay wide open.
B. The valve to remain closed[][]
C. Water to enter into the gas line.
D. Gas to enter into the hot water tank.
B. The valve to remain closed.
Referring to the figure below, a rupture of the bellows will cause:
A. Water to enter the gas line.
B. Gas to enter the hot water tank.
C. The valve to fully close[][][][][][][][]
D. The valve to fully open[][][][][][][][]
D. The valve to fully open.
Which regulator is used at a gas meter to reduce service pressure?
Service regulator.
Which regulator is used downstream of a service regulator but upstream of an appliance regulator?
System regulator.
Which regulator is used at the appliance?
Appliance regulator.
Which element of a regulator is usually a spring?
Loading element.