Current Values + Rules (2) Flashcards
Burning parts due to too high of a current can cause/do:
- damage the part
- change the metallurgical properties of the part
- cause excessive magnetic fields or magnetization
High current issues using the Wet-Fluorescent application
Particles will:
- reduced mobility
- adhere to surface rather than leakage field migration (excessive “background”)
- highly attracted to non-relevant leakage fields
High current issues using the Wet-Visible application
Particles will:
- reduced mobility
- adhere to surface rather than leakage field migration (excessive “background”)
- highly attracted to non-relevant leakage fields
High current issue using the Dry Powder application
Particles will:
- reduced mobility
- adhere to surface rather than leakage field migration (excessive “background”)
- highly attracted to non-relevant leakage fields
- excessive longitudinal field attraction to magnetic poles of part under test (“furring”)
How to tell if a part under test is being supplied a sufficient amperage?
- indications are evident after applying the pre-calculated amperage
- Indications are evident on a field strength indicator (gauss/hall meter)
- use of artificial defect shims (QQI’s)
What are “rule of thumb” formulas?
From ASTM Standards as a way to provide a “starting amperage” necessary to test the part.
- always best to start with a low amp and work to higher ones
Rule of thumb formula (Direct Contact - Headshot)
12-32amps per mm of specimen diameter/thickness/cross-section
(300-800amps/mm)
- should always be expressed using metric (mm)
Example: 30mm X 20amp/mm = 600amp
Rule of thumb values are chosen with considerations to:
- Specimen geometry (range of thickness or diameters of the overall specimen)
- Specimen effective contact area (How much of the specimen in contact with conductive heads in comparison to specimen geometry)
Rule of thumb formula (Direct Contact - Prod Method)
minimum prod spacing of 2-3” (50-75mm) and maximum spacing of 8” (203mm)
material <3/4” (19mm) thick = 90-115 amp/in of spacing (3.5-4.5amp/mm)
material >3/4” (19mm) thick = 100-125amp/in (4.0-5.0amp/mm)
Example: 100amp x 6” (prod space) = 560amp
Rule of thumb formula (Coil Method)
Low fill: cross-sectional area of the part is less that 10% coil diameter
(45000/L/D) x (1/n)
High fill: diameter of coil is <2X cross-sectional area of part.
(35000/L/D+2)x(1/n)
n = coil turns
Length/Diameter Ratio
specimen has a L/D greater than 15 it can still be inspected but must be done in sectioned magnetizing shots.
Coil limitation: section of specimen being inspected =/<9in out of either side of the coil.
Rule of thumb formula (Indirect Contact - Central Conductor Method)
high fill conductor: 12-32amp/mm outside diameter
Example: 150mm x 20amp = 3000amp
low fill conductor: Central conductor diameter + 2x wall thickness of test specimen x 12-32amp/mm
Effective inspection area on the specimen when using a central conductor
4X the diameter of the conductor