Ch. 12 water-based fire suppression system Flashcards
On page 504 of Fire Inspection and Code Enforcement, NFPA reports, the fire death rate per thousand in sprinkler-equipped hotels and motels is _____ as compared to ____ in hotels and motels without sprinkler systems.
1.6; 9.1
On page 505/506 of Fire Inspection and Code Enforcement, four basic types of automatic sprinkler systems:
dry pipe
wet pipe
deluge
preaction
On page 509 of Fire Inspection and Code Enforcement, Post indicating valve uses a ___ valve while a post indicator valve assembly uses a ___ valve.
gate valve; butterfly valve
On page 510 of Fire Inspection and Code Enforcement, used to limit the flow of water to one direction is what type of operating valve?
A. Trim valve
B. Check Valve
C. Drip check valve
D. Drain valve
Check valve
On page 510 of Fire Inspection and Code Enforcement, primarily used as drains and test valves , may be globe, ball or gate valve is what type of operating valve?
A. Trim valve
B. Check Valve
C. Drip check valve
D. Drain valve
Trim valves
On page 510 of Fire Inspection and Code Enforcement, used for drains and to keep water from freezing in pipes and damaging them is what type of operating valve?
A. Trim valve
B. Check Valve
C. Drip check valve
D. Drain valve
Drip check valve
On page 511 of Fire Inspection and Code Enforcement, the arrangement of pipes is created by using one of two methods:
pipe scheduled tables
hydraulic calculations
On page 511 of Fire Inspection and Code Enforcement, the ____ method is limited to light and ordinary hazards.
pipe schedule table
On page 513 of Fire Inspection and Code Enforcement, a type of spray sprinkler capable of producing characteristic large water droplets and that is listed for its capability of providing fire control of specific high-challenge fire hazards is what type of sprinkler?
A. Control mode Specific application (CSMA) sprinkler
B. Early suppression fast response (ESFR)
C. Old - style / conventional
D. Quick-response early suppression (QRES)
CSMA sprinkler
On page 514 of Fire Inspection and Code Enforcement, designed to suppress fires in high-challenge hazards such as warehouses; developed as a result of the research into residential-type sprinklers that must react rapidly to protect life in the room of origin is what type of sprinkler?
A. Control mode Specific application (CSMA) sprinkler
B. Early suppression fast response (ESFR)
C. Old - style / conventional
D. Quick-response early suppression (QRES)
ESFR sprinkler
On page 514 of Fire Inspection and Code Enforcement, designed to cover an area greater than 15 feet x 15 feet is what type of sprinkler?
A. Control mode Specific application (CSMA) sprinkler
B. Old style/conventional
C. Extended coverage (EC)
D. Quick-response early suppression (QRES)
EC sprinkler
On page 514 of Fire Inspection and Code Enforcement, designed to direct 40 - 60 % of its discharge in a downward direction is what type of sprinkler?
A. Control mode Specific application (CSMA) sprinkler
B. Early suppression fast response (ESFR)
C. Old - style / conventional
D. Quick-response early suppression (QRES)
Old style/conventional
On page 515 of Fire Inspection and Code Enforcement, designed to provide increased life safety in hotels, motels, and similar residential occupancies is what type of sprinkler?
A. Control mode Specific application (CSMA) sprinkler
B. Early suppression fast response (ESFR)
C. Old - style / conventional
D. Quick-response early suppression (QRES)
QRES sprinklers
On page 515 of Fire Inspection and Code Enforcement, standard sprinkler may have an operating temperature of ______ degrees Fahrenheit.
165 degrees Fahrenheit
On page 519 of Fire Inspection and Code Enforcement, NFPA 13D requires only ___ gpm for any single sprinkler.
18 gpm
On page 519 of Fire Inspection and Code Enforcement, when there are two or more sprinklers, each requires ____ gpm as a minimum water supply.
13 gpm
On page 519 of Fire Inspection and Code Enforcement, spacing for sprinklers in residential systems is a maximum of ____ square feet per sprinkler.
144 square feet
On page 519 of Fire Inspection and Code Enforcement, the maximum spacing between sprinklers is ___ feet with the maximum allowable distance of a sprinkler from a wall being ____ feet.
12 feet; 6 feet
On page 522 of Fire Inspection and Code Enforcement, basic pressure ranges in which water mist systems operate are as follows:
low pressure system:
175 psi or less
On page 522 of Fire Inspection and Code Enforcement, basic pressure ranges in which water mist systems operate are as follows:
intermediate pressure system:
175 - 500 psi