5 Water Supply Flashcards
Mobile water supply apparatus generally carry how many gallons of water
1000 to 3500 gallons
Vehicles caring 1000 gallons of water or more of a fire pump are generally referred to as
Tankers
Water carrying apparatus with a standard fire pump and a large water tank used for fire attack or pumping water to pumpers on the fire ground referred to as
Pumper tankers
Vehicles carrying 1000 gallons of water or more without a fire pump but may utilize a small PTO driven pump, specifically designed to carry water to fire are called
Tenders
A method to offload tanker water where pressurized water stream is used to increase the velocity of a larger volume of water that is flowing by gravity through a dump valve
Jet assist
A method to offload tanker water where the tank is pressurized to assist in expelling the water through the dump valve
Pneumatic system
What determines the number of attack lines to be placed in service
The supply of water that can be maintained
Water delivery capacity of a pumper is limited by the
Capacity of the pump, the number of suction intakes, and discharges
Operation of a pumper is limited by
Engine speed and residual pressure
Pump systems must be capable of delivering the following
100% rated capacity at 150 psi.
70% of rated capacity at 200 psi.
50% of rated capacity at 250 psi
Pumpers are rated from which type of water source
At draft from the static water source
True/false pumpers cannot exceed their rated capacity if they are receiving water under positive pressure
False pumpers can exceed capacity when being fed positive pressure water
Which type of valve can be used to receive water from two different supply lines of minimum 2 1/2 inches
Gated suction Siamese valve
Minimum size of discharge outlets to provide the rated capacity of the pump
2 1/2 inches or larger
Usual practice is to install wanted to and a half inch discharge for each what in rated capacity of a pump
One 2 1/2 inch discharge for each 250 gallons per minute of rated capacity
The pump must not be operated about what percent of it’s rated peak speed for any length of time
80%
An increase in engine pump speed, RPM, that does not result in an increase in discharge pressure indicates what
That the pumper has reached it’s pumping capacity or limit of the water supply
Pump operators should maintain a residual pressure of what at all times
20 PSI or more at all times
The residual pressure of a pump should not be allowed to drop below what
10 psi except under extreme conditions
If minimum allowable residual pressure, 10 psi, is reached, the proper procedure is to
Notify the company officer lower discharge pressure never shut down a hose line without knowledge and consent
If action is required to limit the flow of water to increase residual pressure who should determine what actions to be taken to correct the problem
The incident commander
A measure of the reserve capacity of the hydrant is what
Residual pressure
As more water is taken from the hydrant what happens to residual pressure
It drops, The more water taken the less water remains as potential capacity
As flow rate increases what happens to friction loss
Friction loss increases
Hose that is designed to convey water to hose line nozzles, distributor nozzles, master stream appliances, portable hydrants, manifolds, standpipe and sprinkler systems, and pumps used by the fire department.
Attack hose
Hose that is designed for moving water between a pressurized water source and a pump that is supplying attack lines
Supply hose