10 Fire Protection Systems Flashcards
According to their intended use, standpipe systems are designated
Class I, class II, class III
The piping arrangement that carries water vertically and sometimes horizontally through a building for firefighting operations
Standpipe system
NFPA 14
Standard for the installation of standpipe and hoes systems
Class one standpipe system
Provides 2 1/2 inch hose connections and designated locations in the building for full-scale firefighting generally intended for fire department use rather than brigades or occupants
Class II standpipe system
Provide an inch and a half hose connections at designated locations for first aide firefighting. Generally intended for fire brigades and occupant use
Class III standpipe system
Combination of class one and class two systems can be used for full-scale or first aide firefighting. Both system connections present
Standpipe system types were completely redefined beginning when
1993 addition of NFPA 14
Five categories of standpipe system types
Automatic wet, automatic dry, semi automatic dry, manual dry, manual wet.
Standpipes one classified by types means
Whether or not the piping is wet or dry
Automatic dry standpipe system
Typing normally filled with pressurized air, with use of a dry pipe valve to admit water automatically upon opening a hose valve. Connected to available water supply capable of supplying firefighting
Semi automatic dry standpipe system
Piping normally filled with air pressurized or not. Operate with the use of a deluge valve to admit water into system when remote actuation device located at hose station, such as a pull station, Is operated. Also water supply feeds it for firefighting.
Manual dry standpipe system
Filled with air, do not have reconnected water supply. FDC must be used to supply water
Manual wet standpipe system
Typing normally full of water for the purpose of allowing weeks to be detected. Water supply provided by small connection to domestic water piping. Not capable of supplying water for firefighting. FDC must be used
Manual standpipe systems require
Connection to fdc for water supply
The vertical pipe or riser running through or along the outside of the building not quit with the interior lines on the FDC can feed it
Dry standpipe system.
Exterior dry standpipe systems are usually the result of what
Laws that are newer than the building
The building that has brought over a wide area maybe equipped with how many standpipes
Two or more dry systems, possibility separate from each other
A drawback to large dry standpipe systems
The time it takes to drive the air out the pipe before the line to be charged fully
Standpipe system that is connected to a water source and contains water at all times. Water must be under enough pressure to allow fire attack without need from numbers
Wet standpipe system
NFPA 14 requires that a water supply for class I and class III standpipe systems be able to deliver want to residual pressure at the outlet of the topmost hose connection
100 psi flowing 500 gallons per minute to the two topmost furthest connections.
For class II standpipe system and of NFPA 14 requires the flow of my how much
100 GPM for 30 min and maintain residual pressure of 65 psi at furthest connection
In Addition to the primary water supply on an automatic or semi automatic wet standpipe system what else is required
One or more FDC with a reliable water source nearby
In what setting are two remotely located FDCs required for each zone with the pumping range of fire apparatus in addition to the automatic water supply
High-rise buildings
When two or more sources seen a wet standpipe system which source will be the one that provides the water
The water source providing the highest pressure
This device in a standpipe system keeps possibly contaminated water from entering the potable water system
Check valve
When available which water source is almost always used as the primary source for fire protection systems
Public water works system
No other water source will need to be used standpipe system when
The Public Works system supplies enough pressure to satisfy code
The exception to public waterworks being the primary water source for standpipe systems, is in what setting
Industrial warehousing more similar, where additional water sources may be required
The most common standpipe systems in medium and high-rise apartment and office buildings
Wet system, supplied by public water works
These are used to boost the pressure in a primary supply for standpipe which usually Public Works system but could be a water tank
Pressure pumps
An alternative water supply system for standpipes, mounted on the ground with supplying wanted to story buildings were mounted above ground in taller structures
Gravity tank
Gravity tanks may hold as much as how many gallons of water
100,000 gallons of water
With a gravity tank, the pump is used to fill the tank but not to eight in developing pressure. In the system what supplies the pressure required in the standpipe system
Gravity
Pressure tanks are generally found only on what type of standpipe system
Smaller systems where they supply house lines with water for initial attack by the occupants
Pressure tanks can be located anywhere in the water supply system and generally do not exceed how many gallons and capacity
3000 gallons
What happens after a water supply 10 for standpipe system is empty
It is useless as a source therefore pumper is needed to supply the system
That’s with dry systems it went system may consist of two or more risers that may be separate or interconnected therefore firefighters must be aware of
The type of system and which one they are working on
There is one fire department intake for each riser each and take serves one riser and one riser only in which case
When standpipe riser is are separate
Post-indicator valve’s usually are found on what type of property
Industrial warehouse properties
Gate valves or outside stem and your valves for standpipes usually are installed on which type of building
Apartment buildings office and stores
Before attempting to use a standpipe system firefighter should check to make sure what
Post-indicator valve is are in the open position
The two common type of post-indicator valve us, PIV, are
Window type, butterfly type
When a PIV is not placed on the outside of the building the gate valve are outside stem and yoke might be located on the intake pipe where
In the basement or just inside the first floor if the building has no basement close to the outside wall of the building
FDC is required on which classes of standpipe systems
All class one and class III standpipe systems
On automatic and semi automatic systems FDC serves as
Auxiliary water supply
As a rule most FDC are provided with one 2 1/2 inch inlet for
Each 250 gallons per minute of design flowrate