3.8 "Electrical Power Systems" Flashcards
LCO 3.8.1 title
AC Sources - Operating
LCO 3.8.1 requirement
The following AC electrical sources shall be operable:
- 2 qualified circuits between the offsite transmission network and the onsite Class 1E AC Electrical Power Distribution System
- 2 EDGs, each capable of supplying 1 train of the onsite Class 1E AC Electrical Power Distribution System
LCO 3.8.1 applicability
Modes 1-4
LCO 3.8.1 required actions < 1 hour
- 1 offsite circuit inoperable, then perform offsite source checks for the operable offsite circuit w/in 1 hour
- 1 EDG inoperable, then perform offsite source checks w/in 1 hour
- 3 or more AC sources inoperable, then enter LCO 3.0.3 immediately
LCO 3.8.2 title
AC Sources - Shutdown
LCO 3.8.2 requirement
The following AC electrical sources shall be operable:
- 1 qualified circuits between the offsite transmission network and the onsite Class 1E AC Electrical Power Distribution System
- 1 EDGs, each capable of supplying 1 train of the onsite Class 1E AC Electrical Power Distribution System
LCO 3.8.2 applicability
- Modes 5 and 6
- During movement of irradiated fuel assemblies
LCO 3.8.2 required actions < 1 hour
- The required offsite circuit inoperable, then declare affected required feature(s) with no offsite power available inoperable OR suspend core alterations and movement of irradiated fuel assemblies, initiate action to suspend operations involving positive reactivity additions, AND initiate action to restore required offsite power circuit to operable immediately
- The required EDG inoperable, then suspend core alterations and movement of irradiated fuel assemblies, initiate action to suspend operations involving positive reactivity additions, AND initiate action to restore required EDG to operable
LCO 3.8.3 title
Diesel Fuel, Lube Oil, and Starting Air
LCO 3.8.3 requirement
- For each EDG, the stored fuel oil, lube oil, and starting air subsystem shall be w/in limits, and both diesel fuel oil transfer systems shall be operable
- Separate Condition entry is allowed for each EDG
LCO 3.8.3 applicability
When associated EDG is required to be operable
LCO 3.8.3 required actions < 1 hour
Required action and associated completion time not met OR stored fuel oil, lube oil, or starting air subsystem not w/in limits for reasons other than fuel oil or lube oil inventory < 7 day supply and > 6 day supply, or fuel oil properties not w/in limit, then declare associated EDG(s) inoperable immediately
LCO 3.8.4 title
DC Sources - Operating
LCO 3.8.4 requirement
The Left Train and Right Train DC electrical power sources shall be operable
LCO 3.8.4 applicability
Modes 1-4
LCO 3.8.4 required actions < 1 hour
NONE